Summary

B-08-0480
Building
Closed
GOOD SAMARITAN CAMPUS PROF OFF
Other
CENTRAL UTILITY PLANT - GOOD SAM HOSPITAL
12/05/2008
12/05/2008
01/12/2011
02/11/2011

Locations

Reviews

There are no reviews for this permit application, or you are not authorized to view them.

Fees

There are no fees for this permit application, or you are not authorized to view them.

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Foundation/Rebar Inspection In Progress 08/11/2008
Monty Johnson ((253) 770-3326)
Foundation/Rebar Inspection In Progress 08/19/2008
Monty Johnson ((253) 770-3326)
Plumbing Below Slab Inspection In Progress 08/26/2008
Monty Johnson ((253) 770-3326)
Foundation/Rebar Inspection Approved 09/11/2008
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection Approved 09/11/2008
Monty Johnson ((253) 770-3326)
Plumbing Below Slab Inspection In Progress 09/18/2008
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection In Progress 1/29/2009 1/30/2009 01/30/2009
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection In Progress 2/6/2009 2/6/2009 02/06/2009
rfore
Frame Inspection In Progress 2/19/2009 2/20/2009 02/20/2009
rfore
Wallboard / Drywall Inspection In Progress 2/23/2009 2/24/2009 02/24/2009
rfore
Frame Inspection In Progress 2/27/2009 2/27/2009 02/27/2009
rfore
Frame Inspection In Progress 3/5/2009 3/5/2009 03/05/2009
rfore
Wallboard / Drywall Inspection In Progress 3/12/2009 3/12/2009 03/12/2009
Monty Johnson ((253) 770-3326)
Frame Inspection In Progress 3/12/2009 3/13/2009 03/13/2009
Monty Johnson ((253) 770-3326)
Combination Frame And Rough In Inspection In Progress 3/16/2009 3/17/2009 03/17/2009
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Approved 3/16/2009 3/17/2009 03/17/2009
Monty Johnson ((253) 770-3326)
Frame Inspection Approved 3/17/2009 3/17/2009 03/17/2009
Monty Johnson ((253) 770-3326)
Roof Sheathing Inspection In Progress 3/19/2009 3/19/2009 03/19/2009
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection In Progress 3/20/2009 3/20/2009 03/20/2009
Shannon King ((253) 840-6684)
Roof Sheathing Inspection In Progress 3/24/2009 3/24/2009 03/24/2009
Monty Johnson ((253) 770-3326)
Comment Building Div Inspection In Progress 3/30/2009 3/30/2009 03/30/2009
Monty Johnson ((253) 770-3326)
Frame Inspection In Progress 4/1/2009 4/1/2009 04/01/2009
rfore
Frame Inspection In Progress 4/1/2009 4/2/2009 04/02/2009
Monty Johnson ((253) 770-3326)
Frame Inspection In Progress 4/3/2009 4/3/2009 04/03/2009
rfore
Wallboard / Drywall Inspection Approved 4/3/2009 4/6/2009 04/06/2009
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection In Progress 4/7/2009 4/7/2009 04/07/2009
rfore
Frame Inspection In Progress 4/8/2009 4/8/2009 04/08/2009
Monty Johnson ((253) 770-3326)
Frame Inspection In Progress 4/13/2009 4/14/2009 04/14/2009
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection In Progress 4/17/2009 4/17/2009 04/17/2009
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Approved 4/20/2009 4/20/2009 04/20/2009
Monty Johnson ((253) 770-3326)
Frame Inspection Approved 4/20/2009 4/20/2009 04/20/2009
Monty Johnson ((253) 770-3326)
Frame Inspection Approved 5/4/2009 5/5/2009 05/05/2009
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Approved 5/4/2009 5/5/2009 05/05/2009
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection In Progress 5/8/2009 5/11/2009 05/11/2009
rfore
Firewall/Firestop Inspection In Progress 8/21/2009 8/21/2009 08/21/2009
rfore
Gas Test Inspection Approved 01/04/2010
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Approved 1/4/2010 01/04/2010
Monty Johnson ((253) 770-3326)
Plumbing Final Inspection Approved 6/17/2010 06/17/2010
Monty Johnson ((253) 770-3326)
Fire & Smoke Damper Test Inspection Approved 07/15/2010
Ray Cockerham ((253) 841-5585)
Exit Lighting Test Inspection In Progress 07/15/2010
Ray Cockerham ((253) 841-5585)
Building Final Inspection In Progress 07/16/2010
Ray Cockerham ((253) 841-5585)
Exit Lighting Test Inspection Approved 7/13/2010 7/16/2010 07/16/2010
kenb
Engineering Final Inspection Approved 7/16/2010 07/19/2010
lesley
Planning Final Inspection Approved 7/16/2010 07/19/2010
Katie Baker ((253) 435-3604)
Footing/Setback Inspection VOID 12/09/2021
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection VOID 12/09/2021
Monty Johnson ((253) 770-3326)
Comment Building Div Inspection VOID 12/09/2021
Monty Johnson ((253) 770-3326)
Plumbing Below Slab Inspection VOID 12/09/2021
Monty Johnson ((253) 770-3326)
Plumbing Final Inspection VOID 12/09/2021
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection VOID 1/21/2009 1/22/2009 12/09/2021
rfore
Mechanical Rough In Inspection VOID 3/31/2009 4/1/2009 12/09/2021
rfore
Frame Inspection VOID 4/16/2009 4/17/2009 12/09/2021
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection VOID 1/14/2010 12/09/2021
Monty Johnson ((253) 770-3326)
Comment Building Div Inspection VOID 1/27/2010 12/09/2021
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection VOID 2/19/2010 12/09/2021
Monty Johnson ((253) 770-3326)
Fire Final Inspection VOID 4/14/2010 12/09/2021
kenb
Plumbing Rough In Inspection VOID 6/16/2010 12/09/2021
Monty Johnson ((253) 770-3326)
Building Final Inspection VOID 7/1/2010 12/09/2021
Monty Johnson ((253) 770-3326)
Building Final Inspection VOID 7/15/2010 12/09/2021
Ray Cockerham ((253) 841-5585)
Fire Final Inspection VOID 7/16/2010 12/09/2021
kenb
Building Final Inspection VOID 9/24/2010 12/09/2021
Monty Johnson ((253) 770-3326)

Conditions

Condition Status Category
General Permit Conditions Resolved Standard Conditions
Building Division
Final approval by the Building Official is required prior to occupancy. WORK SHALL NOT PROCEED UNTIL THE INSPECTOR HAS APPROVED THE STAGES OF CONSTRUCTION SURFACE STORM WATER SHALL BE DIVERTED FROM THE BUILDING SITE AND SHALL NOT DRAIN ONTO ADJACENT PROPERTIES. Rain drains shall connect to the storm sewer or discharge at the street. I hereby acknowledge that I have read this Permit/Application, that the information given is correct: that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Once work has started (passed a required inspection) one inspection per year must be completed to keep active or it will formally expire and become null and void. BY LEAVING THE CONTRACTOR INFORMATION SECTION BLANK, I HEREBY CERTIFY FURTHER THAT CONTRACTORS (GENERAL OR SUBCONTRACTORS) WILL NOT BE HIRED TO PERFORM ANY WORK IN ASSOCIATION WITH THIS PERMIT. I ALSO CERTIFY THAT IF I DO CHOOSE TO HIRE A CONTRACTOR (GENERAL OR SUBCONTRACTOR) I WILL ONLY HIRE THOSE CONTRACTORS THAT ARE LICENSED BY THE STATE OF WASHINGTON.
Building Permit Standard Conditions Resolved Standard Conditions
Building Division
PERMIT CONDITIONS: FIRE REVIEW CONDITIONS: 1. THIS REVIEW DOES NOT APPROVE THE UNDERGROUND STORAGE TANK LOCATION OR SIZING. SIZING WILL BE BASED ON THE FUTURE HOSPITALS NEEDS AND WILL BE ADDRESSED LATER THROUGH DOH'S REVIEW. 2. A FIRE DEPARTMENT KNOX BOX IS REQUIRED. 3. AN AUTOMATIC FIRE SPRINKLER AND FIRE ALARM SYSTEM WILL BE REQUIRED FOR THIS BUILDING. SYSTEM SHALL BE DESIGNED PER CITY ORDINANCES. 4. FIRE FINAL INSPECTION IS REQUIRED. BUILDING: Install approved address on the building which is visable from the road. The size of the lettering shall comply with the Fire Dept. requirements. 841-6666 It is the responsibility of the contractor or owner to make sure that this building complies with all the requirements of the International Codes and the Uniform Plumbing Code. All redlines on the approved plans shall become part of the project. You shall comply with all requirements of Chapter 17 for Special Inspection, see the Cities list of authorized companies. THE CONTRACTOR SHALL NOT EMPLOY THE SPECIAL INSPECTION COMPANY OR THE INSPECTOR SECTION 1701.1 UBC You shall comply with all the requirements of the Geotechnical Engineer Report and incorporate all their conclusions and recommendations into the project. Section 1802 IBC This job requires Structural Observation as stated in Section 1702 Wash. State Amendments. A written field report of observed deficiencies and how the deficiencies shall be resolved will be sent to the Building Official of the City. Final electrical inspection approval is required prior to the building department final approval. The foundation inspection shall only be made after the surveyor of record verifies the location of the foundation to the approved site plan. The APPROVED CONSTRUCTION PLANS and ALL ENGINEERING must be posted on the job at all inspections in a visible and readily accessible location.