Summary

B-19-1101
Commercial - Tenant Improvement/Remodel
Permit(s) Issued
CAFARO NORTHWEST PARTNERSHIP
Alteration/Remodel
INTERIOR DEMO AND SOME SEISMIC UPGRADES ROUND 1 ENTERTAINMENT VENUETRAFFIC IMPACT FEES TO BE ASSESSED DURING PENDING TI BUILDING PERMIT - BRBLDG/MECH
12/17/2019
01/10/2022
07/15/2023

Locations

Property
6021010051

Property
6021590070

Property
6021590090

* Address
3500 S MERIDIAN

Reviews

Documents Returned For Corrections

Date Returned Name
04/22/2022 62-900-10 Complete Set (Stamped)
Review Type Outcome Est. Completion Date Completed
Engineering Traffic Review Approved 02/28/2022 04/20/2022
Fire Review Approved 02/28/2022 03/02/2022
Building Review Approved 02/28/2022 02/28/2022
Engineering Review VOID 02/28/2022 02/28/2022
Planning Review Approved 02/28/2022 02/25/2022
Mechanical Review Approved 01/16/2022 01/07/2022
Planning Review In Progress 02/05/2021
Planning Review In Progress 02/05/2021
Building Review Approved 01/27/2021
Fire Review Approved 01/19/2021
Engineering Review Approved 01/15/2021
Building Review Incomplete 02/19/2020 11/17/2020
Engineering Review Approved 12/17/2019 03/27/2020
Planning Review In Progress 12/17/2019 03/18/2020
Fire Review Incomplete 01/15/2020 02/19/2020
Building Review Incomplete 01/15/2020 02/19/2020
Fire Review Incomplete 12/17/2019 01/15/2020
Building Review Incomplete 12/17/2019 01/15/2020

Fees

Paid Fees Amount Paid Owing Date Paid
Building Division Fee (Hourly) $130.00 $130.00 Paid 09/03/2021
No
WA State Building Code Council Fee (Residential) $25.00 $25.00 Paid 04/08/2021
No
Plumbing Plan Review Fee $94.58 $94.58 Paid 04/08/2021
No
Mechanical Plan Review Fee $149.56 $149.56 Paid 04/08/2021
No
Building Division Fee (Hourly) $130.00 $130.00 Paid 04/08/2021
No
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 04/08/2021
No
Mechanical Permit Fee $230.09 $230.09 Paid 04/08/2021
No
Planning Building Permit Fee $120.00 $120.00 Paid 04/08/2021
No
Plumbing Permit Fee $145.50 $145.50 Paid 04/08/2021
No
Building Permit Fee $4,777.50 $4,777.50 Paid 04/08/2021
No
Planning Landscape Review Fee $300.00 $300.00 Paid 04/08/2021
No
Building Plan Review Fee $3,105.38 $3,105.38 Paid 01/03/2020
No
Building Division Fee (Hourly) $130.00 $130.00 Paid 01/10/2022
Building Division Fee (Hourly) $260.00 $260.00 Paid 02/18/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Carbon Monoxide Detectors Inspection Pending
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Pending
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection Pending
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Pending
Monty Johnson ((253) 770-3326)
Engineering Final Inspection Pending
Jason Little ((253) 435-3636)
Exit Lighting Test Inspection Pending
Monty Johnson ((253) 770-3326)
Shear Wall Inspection Pending
Monty Johnson ((253) 770-3326)
Fire Final Inspection Pending
David Drake ((253) 864-4171)
Plumbing Final Inspection Pending
Monty Johnson ((253) 770-3326)
Combination Frame And Rough In Inspection Pending
Monty Johnson ((253) 770-3326)
Frame Inspection Pending
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
12/22/2021
1 ; complete all firestop at rated wall as per city approved plans as discussed with Tom and complete marking and identification of rated wall as per section 703.7 of I.B.C. prior to next inspection. ( as noted on frame inspection dated12/16/2021)

Mechanical Final Inspection Pending
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
12/22/2021
1 ; called in error per contractor - not ready

Ceiling Grid/T-Bar Inspection Pending
Monty Johnson ((253) 770-3326)
Energy (Insulation) Inspection Pending
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Pending
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
01/27/2022
1 ; provide city approved plans on-site at time of gas pipe test inspection. not ready

Comment Building Div Inspection Pending
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
02/24/2022
1 ; talked with contractor about demo requirements of ceiling grid.

Plumbing Rough In Inspection In Progress 7/16/2021 07/16/2021
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection In Progress 7/20/2021 07/20/2021
Monty Johnson ((253) 770-3326)
Frame Inspection Failed 8/13/2021 08/13/2021
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Failed 8/27/2021 08/27/2021
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Failed 8/31/2021 08/31/2021
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Failed 8/31/2021 08/31/2021
Monty Johnson ((253) 770-3326)
Frame Inspection Failed 9/7/2021 09/07/2021
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection In Progress 9/7/2021 09/07/2021
Shannon King ((253) 840-6684)
Frame Inspection In Progress 9/15/2021 09/15/2021
Shannon King ((253) 840-6684)
Plumbing Rough In Inspection Failed 9/17/2021 09/17/2021
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Failed 9/17/2021 09/17/2021
Shannon King ((253) 840-6684)
Plumbing Rough In Inspection In Progress 10/1/2021 10/01/2021
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Not Ready 10/1/2021 10/01/2021
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Failed 10/7/2021 10/07/2021
Shannon King ((253) 840-6684)
Frame Inspection Failed 12/7/2021 12/07/2021
Shannon King ((253) 840-6684)
Combination Frame And Rough In Inspection Partial Pass 12/10/2021 12/10/2021 12/15/2021
Gary Webster ((253) 841-5590)
Energy (Insulation) Inspection Not Ready 12/16/2021 12/16/2021 12/16/2021
Shannon King ((253) 840-6684)
Canceled by contractor
Outstanding
12/16/2021
Cancelled by contractor - no insulation installed at time of inspection.

Frame Inspection Failed 12/16/2021 12/16/2021 12/16/2021
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
12/16/2021
1 ; complete all firestop at rated wall as per city approved plans as discussed with Tom and complete marking and identification of rated wall as per section 703.7 of I.B.C. prior to reinspection.

Frame Inspection Failed 12/22/2021 12/22/2021 12/22/2021
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
12/22/2021
1 ; complete all firestop at rated wall as per city approved plans as discussed with Tom and complete marking and identification of rated wall as per section 703.7 of I.B.C. prior to next inspection. ( as noted on frame inspection dated12/16/2021)

Mechanical Final Inspection Not Ready 12/22/2021 12/22/2021 12/22/2021
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
12/22/2021
1 ; called in error per contractor - not ready

Ceiling Grid/T-Bar Inspection Partial Pass 1/14/2022 1/14/2022 01/14/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
01/14/2022
1:temp bracing and support of grid at seismic upgrade areas ok, contractor states all grid to be removed at later date

Energy (Insulation) Inspection Not Ready 1/14/2022 1/14/2022 01/14/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
01/14/2022
1:provide special insp approval on seismic upgrades insp for seismic stitching of walls

Foundation/Rebar Inspection Failed 1/19/2022 1/19/2022 01/19/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
01/19/2022
1 ; complete install of slab dowels at plumbing trench pour back. ( vapor barrier complete)

Mechanical Rough In Inspection Not Ready 1/24/2022 1/24/2022 01/24/2022
Shannon King ((253) 840-6684)
Not Ready
Outstanding
01/24/2022
Not Ready - Call to reschedule (cancel per contractor)

Mechanical Rough In Inspection Failed 1/27/2022 1/27/2022 01/27/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
01/27/2022
1 ; provide city approved plans on-site at time of gas pipe test inspection. not ready

Comment Building Div Inspection Not Ready 2/24/2022 2/24/2022 02/24/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
02/24/2022
1 ; talked with contractor about demo requirements of ceiling grid.

Building Final Inspection Partial Pass 7/20/2022 7/20/2022 07/20/2022
Shannon King ((253) 840-6684)
Building Final Inspection VOID 01/16/2023
CityView System Manger

Conditions

Condition Status Department Category Expiration Date Due Date
General Permit Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy. * Work shall not proceed until the inspector has approved the stages of construction. * Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties. * I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. * TO SCHEDULE INSPECTIONS, CHECK PERMIT STATUS OR TO MAKE PAYMENTS ON THE CITY WEB SITE VISIT https://secure.cityofpuyallup.org/
Engineering Commercial Standard Conditions Open Engineering Division Standard Conditions
: * THE APPLICANT IS RESPONSIBLE TO CALL THE INSPECTION LINE AT 877-232-6456 TO SCHEDULE INSPECTIONS. UTILITY INSPECTIONS ARE REQUIRED PRIOR TO BACKFILLING. * Curb, gutter, sidewalk and approach must be poured per City Standards. * Any addition/expansion to the foot print of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction.
Building Permit Standard Conditions Open Building Division Standard Conditions
: PERMIT CONDITIONS: 1- COMPLY WITH 2015 IFC AND 2015 IBC 2- TOTAL COVERAGE REQUIRED IN THE CITY OF PUYALLUP 3- EXIT LIGHTING TEST REQUIRED CONTRACTOR TO PROVIDE LIGHT METER 4- SEPERATE PERMITS REQUIRED FOR FIRE ALARM AND FIRE SPRINKLER 5- FIRE WATCH IS REQUIRED WHEN EITHER SYSTEM IS DOWN 6- RTU'S WILL BE REQUIRED TO BE TESTED FOR SHUT DOWN WITH FIRE ALARM CONTRACTOR AND HVAC CONTRACTOR. 7- FIRE EXTINGUISHERS REQUIRED PER CODE FOR EVERY 75' OF TRAVEL. 8- A KNOX BOX IS REQUIRED AT THE FRONT ENTRY ON THE EXTERIOR OF THE BUILDING 9- PIV MUST HAVE A KNOX LOCK OR APPROVED LOCK WITH AN EXTRA KEY PROVIDED IN KNOX BOX 10- EXISTING BUILDINGS WILL NEED TO CONTACT CENTRAL PIERCE FIRE & RESCUE AND UPDATE THE KEY IN THE KNOX BOX 11- IF THE FIRE ALARM REMOTE ANNUNICATOR IS LOCATED OUTSIDE, IT WILL BE REQUIRED TO BE REINSTALLED INSIDE A VESTIBULE. 12- ALL FIRE HYDRANTS ARE TO BE FREE AND CLEAR FROM BRUSH AND DEBRIS. 13- ALL ABOVE ITEMS TO BE COMPLETED PRIOR TO FIRE FINAL. FIRE FINAL REQUIRED BEFORE BUILDING FINAL INSPECTION REQUEST CODES: 2252 EXIT LIGHT TEST 9200 FIRE BUILDING FINAL SCHEDULE YOUR INSPECTION BY PHONE OR ONLINE THROUGH THE CITY OF PUYALLUP ONLINE PERMIT SYSTEM. THEN CALL MORNING OF INSPECTION BETWEEN 7AM - 8PM TO SET UP A TIME. INSPECTIONS ARE MONDAY - THURSDAY THERE WILL BE NO INSPECTIONS ON FRIDAYS. HTTPS://SECURE.CITYOFPUYALLUP.ORG/ INSPECTION LINE 1-877-232-6456 (USE MUTE TO AVOID BACKGROUND NOISE) DAVID DRAKE AT 253-864-4171 OR RAY COCKERHAM AT 253-841-5585
Pipeline Notfication Rcw 19.122.033 Open Engineering Division Standard Conditions
: Effective January 1, 2013 RCW 19.122 Before conducting any construction or excavation within 100 feet of a right-of-way or utility easement containing a transmission pipeline a person must notify the pipeline companies of the scheduled excavation through the one-number locator service 811. Notification must occur in a window of not less than 2 business days but not more than 10 business days before beginning the excavation. If a transmission pipeline company is notified that excavation work will occur near a pipeline, a representative of the company must consult with the excavator on-site prior to excavation.
Fire Review Conditions Open Development & Permitting Services Standard Conditions
: Onsite review for code compliance.

Related Permit & Planning Applications

There are no related items for this permit application.

Documents & Images

Date Uploaded File Type Name
12/17/2019 Plans b-19-1101 plumbing fixture worksheet.pdf
12/17/2019 Plans b-19-1101 plumbing fixture worksheet.pdf
12/17/2019 Plans b-19-1101 resub 1 structural calcs.pdf
12/17/2019 Plans b-19-1101 resub 1 revised plans.pdf
12/15/2021 Report Inspection Report (Combination Frame And Rough In Inspection)
12/16/2021 Report Inspection Report (Energy (Insulation) Inspection)
12/16/2021 Report Inspection Report (Frame Inspection)
12/22/2021 Report Inspection Report (Frame Inspection)
12/22/2021 Report Inspection Report (Mechanical Final Inspection)
01/10/2022 Form Revisions to Existing Com Applications - Gas Piping (Flattened)
01/10/2022 Plans 062-900 MP-300 R-1 (2) (Stamped)
01/10/2022 Letter Permit - Detailed
01/10/2022 Receipt Receipt for transaction:2022-000032
01/20/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/20/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/20/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/24/2022 Report Inspection Report (Mechanical Rough In Inspection)
01/24/2022 Report Inspection Report (Mechanical Rough In Inspection)
01/24/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/27/2022 Report Inspection Report (Mechanical Rough In Inspection)
01/27/2022 Report Inspection Report (Mechanical Rough In Inspection)
01/27/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/27/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/27/2022 Report Inspection Report (Mechanical Rough In Inspection)
01/27/2022 Report Inspection Report (Foundation/Rebar Inspection)
01/28/2022 Report Inspection Report (Gas Test Inspection)
01/28/2022 Report Inspection Report (Gas Test Inspection)
01/28/2022 Report Inspection Report (Foundation/Rebar Inspection)
04/22/2022 Plans 62-900-10 Complete Set (Stamped)
04/22/2022 Form 62-900 Revisions to Existing Bldg Permit App - Demo (Flattened)
02/24/2022 Report Inspection Report (Comment Building Div Inspection)
02/24/2022 Report Inspection Report (Comment Building Div Inspection)
07/20/2022 Report Inspection Report (Building Final Inspection)
12/05/2022 Letter Permit Expiration Notice