CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

B-21-0583


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

B-21-0583
Commercial - Tenant Improvement/Remodel
Finaled
Alteration/Remodel
TI COMBINE (2) SUITES INTO 1 OFFICE ~ STEWART TITLE
08/02/2021
09/22/2021
11/07/2022
05/11/2022

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Building Review Approved 09/20/2021
Building Review Incomplete 08/25/2021
Planning Review In Progress 08/25/2021
Fire Review Approved 08/24/2021
Engineering Traffic Review Approved 08/17/2021
Engineering Review Approved 08/10/2021

Fees

Paid Fees Amount Paid Owing Date Paid
Planning Building Permit Fee $30.00 $30.00 Paid 10/12/2021
No
WA State Building Code Council Fee (Residential) $25.00 $25.00 Paid 10/12/2021
No
Planning Landscape Review Fee $90.00 $90.00 Paid 10/12/2021
No
Plumbing Plan Review Fee $34.45 $34.45 Paid 10/12/2021
No
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 10/12/2021
No
Building Division Fee (Hourly) $130.00 $130.00 Paid 10/12/2021
No
Plumbing Permit Fee $53.00 $53.00 Paid 10/12/2021
No
Mechanical Plan Review Fee $478.14 $478.14 Paid 10/12/2021
No
Building Permit Fee $1,038.55 $1,038.55 Paid 10/12/2021
No
Mechanical Permit Fee $735.60 $735.60 Paid 10/12/2021
No
Building Plan Review Fee $675.06 $675.06 Paid 10/12/2021
No
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Frame Inspection Not Ready 12/6/2021 12/06/2021
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 12/16/2021 12/16/2021 12/16/2021
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Partial Pass 1/20/2022 1/20/2022 01/20/2022
Shannon King ((253) 840-6684)
Ceiling Grid/T-Bar Inspection Passed w/ Conditions 3/24/2022 3/24/2022 03/24/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
03/24/2022
1:screw all diffusers to grid, (west half of building)

Mechanical Rough In Inspection Partial Pass 3/24/2022 3/24/2022 03/24/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
03/24/2022
insp for diffusers in grid approved with west half of building having all diffusers screwed to grid

Plumbing Final Inspection Failed 4/28/2022 4/28/2022 04/28/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
04/28/2022
1:strap water heaters to walls and add expansion tanks 2:provide flush handle on open side of toilet at north bathroom 3:provide hammer arrestors at dishwasher and ice maker (all quick acting valves) 4:provide dbl check at hard lined coffee maker.

Mechanical Final Inspection Failed 4/28/2022 4/28/2022 04/28/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
04/28/2022
1:provide balance report and access to roof.

Plumbing Final Inspection Failed 5/2/2022 5/2/2022 05/02/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
05/02/2022
1 ; complete install of expansion tank. 2 ; provide Dbl. check at hard lined coffee maker as required on last plumbing final inspection dated 4/28/2022.

Mechanical Final Inspection Failed 5/2/2022 5/2/2022 05/02/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
05/02/2022
1 ; provide balance report and ladder for roof top access as per last mechanical final inspection dated 4/28/2022

Plumbing Final Inspection Failed 5/5/2022 5/5/2022 05/05/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
05/05/2022
1 ; complete install of expansion tank. 2 ; provide Dbl. check at hard lined coffee maker as required on last plumbing final inspection dated 4/28/2022. 1:provide dbl check at coffee per last 2 insp 2:plumbing vents to be 10ft away or 2 ft above intakes on roof

Mechanical Final Inspection Failed 5/5/2022 5/5/2022 05/05/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
05/05/2022
1 ; provide balance report and ladder for roof top access as per last mechanical final inspection dated 4/28/2022 1:provide osa on balance report 2:plumb vents to be min 10ft away or 2ft above intakes on roof

Mechanical Final Inspection Failed 5/9/2022 5/9/2022 05/09/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
05/09/2022
1 ; provide balance report and ladder for roof top access as per last mechanical final inspection dated 4/28/2022 1:provide osa on balance report 2:plumb vents to be min 10ft away or 2ft above intakes on roof

Other/Miscellaneous
Carried Forward
05/09/2022
1 ; provide balance report with min. o.s.a. as required per City approved plans.

Plumbing Final Inspection Failed 5/9/2022 5/9/2022 05/09/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
05/09/2022
1 ; complete install of expansion tank. 2 ; provide Dbl. check at hard lined coffee maker as required on last plumbing final inspection dated 4/28/2022. 1:provide dbl check at coffee per last 2 insp 2:plumbing vents to be 10ft away or 2 ft above intakes on roof

Other/Miscellaneous
Carried Forward
05/09/2022
1 ; provide back flow certification test report prior to plumbing final.

Building Final Inspection Failed 5/9/2022 5/9/2022 05/09/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
05/09/2022
1 ; provide exit plan from architect at Building final inspection. 2 ; complete all lever action door hardware. 3 ; remove thumb turns from doors and complete door signage as discussed with contractor.

Carbon Monoxide Detectors Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Combination Frame And Rough In Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Comment Building Div Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Energy (Insulation) Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Shear Wall Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Engineering Final Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Foundation/Rebar Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Frame Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection VOID 05/11/2022
Monty Johnson ((253) 770-3326)

Conditions

Condition Status Department Category Expiration Date Due Date
General Permit Conditions Resolved Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy. * Work shall not proceed until the inspector has approved the stages of construction. * Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties. * I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. * TO SCHEDULE INSPECTIONS, CHECK PERMIT STATUS OR TO MAKE PAYMENTS ON THE CITY WEB SITE VISIT https://secure.puyallupwa.gov
Engineering Commercial Standard Conditions Resolved Engineering Division Standard Conditions
: * Any addition/expansion to the foot print of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. * Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Building Permit Standard Conditions Resolved Building Division Standard Conditions
: PERMIT CONDITIONS: 1- COMPLY WITH 2018 IFC AND 2018 IBC 2- EXIT LIGHTING TEST REQUIRED CONTRACTOR TO PROVIDE LIGHT METER 3- A SEPARATE PERMIT MAY BE REQUIRED IF FIRE ALARM OR SRPINKLER SYSTEM IS ALTERED 4- RTU'S WILL BE REQUIRED TO BE TESTED FOR SHUT DOWN. 5- FIRE EXTINGUISHERS REQUIRED PER CODE 6- ALL ABOVE ITEMS TO BE COMPLETED PRIOR TO FIRE FINAL. FIRE FINAL REQUIRED BEFORE BUILDING FINAL INSPECTION REQUEST CODES: 2252 EXIT LIGHT TEST 9200 FIRE BUILDING FINAL SCHEDULE YOUR INSPECTION BY PHONE OR ONLINE THROUGH THE CITY OF PUYALLUP ONLINE PERMIT SYSTEM. THEN CALL MORNING OF INSPECTION BETWEEN 7AM - 8AM TO SET UP A TIME. INSPECTIONS ARE MONDAY - THURSDAY THERE WILL BE NO INSPECTIONS ON FRIDAYS. HTTPS://SECURE.CITYOFPUYALLUP.ORG/ INSPECTION LINE 1-877-232-6456 (USE MUTE TO AVOID BACKGROUND NOISE) DAVID DRAKE AT 253-864-4171 OR RAY COCKERHAM AT 253-841-5585
Pipeline Notfication Rcw 19.122.033 Resolved Engineering Division Standard Conditions
: Effective January 1, 2013 RCW 19.122 Before conducting any construction or excavation within 100 feet of a right-of-way or utility easement containing a transmission pipeline a person must notify the pipeline companies of the scheduled excavation through the one-number locator service 811. Notification must occur in a window of not less than 2 business days but not more than 10 business days before beginning the excavation. If a transmission pipeline company is notified that excavation work will occur near a pipeline, a representative of the company must consult with the excavator on-site prior to excavation.