CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

F-11-0116


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

F-11-0116
UNKOWN LEGACY PERMIT TYPE
Expired
SOUND PROPERTIES LLC
Other
COMM PHO EVER INSTALL HOOD SUPPRESSION - PHO EVER COMM
10/24/2011
01/10/2012
01/09/2013

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 10/28/2011

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Suppression System (other than Sprinklers) Fee $230.00 $230.00 Paid 10/24/2011
No
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Suppression System Test Inspection Failed 1/13/2012 01/13/2012
rfore
Suppression System Final Inspection Approved 1/17/2012 01/17/2012
rfore
Suppression System Test Inspection VOID 12/10/2021
Legacy user

Conditions

Condition Status Category
Fire Suppression Hood Conditions Resolved Standard Conditions
Commercial Cooking Hood Suppression: 1Hook to fire alarm system or provide audio or visual indication of system discharge. IFC 904.3.4 2 Provide manual activation in path of egress no closer than 10’ nor no more than 20’ from hood. IFC 904.11.1 3 Provide K-fire extinguishers according to IFC 904.11.5. HOOD SUPPRESSION INSPECTION CODES: 5401 SUPPRESSION SYSTEM TEST INSPECTION 5402 SUPPRESSION SYSTEM FINAL INSPECTION

Related Permit & Planning Applications

There are no related items for this permit application.

Documents & Images

No documents are currently available for viewing.


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.