CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

F-15-0016


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

F-15-0016
Fire Construction Permit
Closed
BCC PUYALLUP LLC
Other
INSTALL 3 FUEL TANKS (2-25K & 1-30K) ~ SOUTH HILL DATA CENTER
02/24/2015
04/10/2015
04/09/2016
11/04/2015

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review VOID 12/09/2021

Fees

Paid Fees Amount Paid Owing Date Paid
Legacy Fee $795.00 $795.00 Paid 02/24/2015
No
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Final Inspection In Progress 8/11/2015 08/11/2015
rfore
Fire Final Inspection Approved 11/3/2015 11/4/2015 11/04/2015
rfore
IFC Permit Inspection VOID 8/4/2015 12/09/2021
rfore
IFC Permit Inspection VOID 8/10/2015 8/11/2015 12/09/2021
rfore

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Resolved Building Division Standard Conditions
: CONDITIONS: 1 PROVIDE LNI FINAL ELECTRICAL APPROVAL ON ALL ELECTRICAL ASSOCIATED WITH THE TANKS. 2 THIS PERMIT IS FOR 2-25,000 GALLON FUEL TANKS ONLY. 3 PROVIDE A SPECIAL INSPECTION REPORT ON THE SEISMIC ANCHORAGE OF THE TANKS. 4 PROVIDE PROOF THAT THE PAD CONCRETE MEETS THE 6,000 PSI REQUIREMENT. 5 REQUIRED INSPECTIONS: IVR-5100 IFC PERMIT INSPECTION IVR-5108 FIRE FINAL INSPECTIN

Related Permit & Planning Applications

There are no related items for this development permit application.

Documents & Images

No documents are currently available for viewing.


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.