CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCTI20221484
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 02/06/2023 |
Mechanical Duct Work Fee | $14.10 | $14.10 | Paid | 02/06/2023 |
Building Permit Fee | $1,273.75 | $1,273.75 | Paid | 02/06/2023 |
Mechanical Permit Fee | $40.00 | $40.00 | Paid | 02/06/2023 |
Building Plan Review Fee | $827.94 | $827.94 | Paid | 10/12/2022 |
Mechanical Plan Review Fee | $35.17 | $35.17 | Paid | 10/12/2022 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 02/06/2023 |
Resubmittal Fee | $130.00 | $130.00 | Paid | 11/09/2022 |
Resubmittal Fee | $130.00 | $130.00 | Paid | 03/09/2023 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $2,740.96 | $2,740.96 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Frame Inspection | Not Ready | 3/2/2023 | 3/2/2023 | 03/02/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/02/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Mechanical Final Inspection | Not Ready | 3/2/2023 | 3/2/2023 | 03/02/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/02/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Frame Inspection | Not Ready | 3/15/2023 | 3/15/2023 | 03/15/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/15/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Carried Forward
03/15/2023
1 ; provide complete set of City approved plans with revision for added framing as discussed with contractor. not ready
|
||||
Mechanical Final Inspection | Not Ready | 3/15/2023 | 3/15/2023 | 03/15/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/15/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Carried Forward
03/15/2023
1 ; complete mechanical rough-in as discussed with contractor.
|
||||
Ceiling Grid/T-Bar Inspection | Not Ready | 3/15/2023 | 3/15/2023 | 03/15/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/15/2023
1 ; complete all ceiling grid requirements as per city approved plans,
|
||||
Frame Inspection | Partial Pass | 3/16/2023 | 3/16/2023 | 03/16/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/16/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Carried Forward
03/16/2023
1 ; provide complete set of City approved plans with revision for added framing as discussed with contractor. not ready
|
||||
Ceiling Grid/T-Bar Inspection | Partial Pass | 3/24/2023 | 3/24/2023 | 03/24/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
03/24/2023
1 ; complete all ceiling grid requirements as per city approved plans,
|
||||
Other/Miscellaneous
Carried Forward
03/24/2023
1. approved for cover in area covered up with out inspections only
|
||||
Mechanical Final Inspection | Not Ready | 3/28/2023 | 3/28/2023 | 03/28/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/28/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Carried Forward
03/28/2023
1 ; complete mechanical rough-in as discussed with contractor.
|
||||
Frame Inspection | Not Ready | 3/28/2023 | 3/28/2023 | 03/28/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
03/28/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Carried Forward
03/28/2023
1 ; provide complete set of City approved plans with revision for added framing as discussed with contractor. not ready
|
||||
Mechanical Final Inspection | Partial Pass | 3/29/2023 | 3/29/2023 | 03/29/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
03/29/2023
1 ; complete all framing. mechanical rough-in,& electrical cover approval from L&I prior to next frame inspection. ( not ready)
|
||||
Other/Miscellaneous
Resolved
03/29/2023
1 ; complete mechanical rough-in as discussed with contractor.
|
||||
Mechanical Final Inspection | Not Ready | 4/7/2023 | 4/7/2023 | 04/07/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/07/2023
1. cancelled by contractor
|
||||
Ceiling Grid/T-Bar Inspection | Not Ready | 4/7/2023 | 4/7/2023 | 04/07/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/07/2023
1 ; complete all ceiling grid requirements as per city approved plans,
|
||||
Other/Miscellaneous
Carried Forward
04/07/2023
1. approved for cover in area covered up with out inspections only
|
||||
Other/Miscellaneous
Carried Forward
04/07/2023
1. cancelled by contractor
|
||||
Mechanical Final Inspection | Not Ready | 4/12/2023 | 4/12/2023 | 04/12/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/12/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Carried Forward
04/12/2023
1.complete mono coat as discussed with contractor
2. complete drywall penetration's as discussed with contractor
3. not ready
|
||||
Ceiling Grid/T-Bar Inspection | Not Ready | 4/12/2023 | 4/12/2023 | 04/12/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
04/12/2023
1 ; complete all ceiling grid requirements as per city approved plans,
|
||||
Other/Miscellaneous
Carried Forward
04/12/2023
1. approved for cover in area covered up with out inspections only
|
||||
Other/Miscellaneous
Carried Forward
04/12/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Carried Forward
04/12/2023
1. complete perimeter wires as discussed with contractor
2. provide tie wires at all wires that exceed 1 and 6
3. provide positive attachment at light fixtures as discussed with contractor
4 complete drywall at wall in shoe storage area as per city approved plans
5.not ready
|
||||
Ceiling Grid/T-Bar Inspection | Failed | 4/26/2023 | 4/26/2023 | 04/26/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/26/2023
1 ; complete all ceiling grid requirements as per city approved plans,
|
||||
Other/Miscellaneous
Resolved
04/26/2023
1. approved for cover in area covered up with out inspections only
|
||||
Other/Miscellaneous
Resolved
04/26/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Carried Forward
04/26/2023
1. complete perimeter wires as discussed with contractor
2. provide tie wires at all wires that exceed 1 and 6
3. provide positive attachment at light fixtures as discussed with contractor
4 complete drywall at wall in shoe storage area as per city approved plans
5.not ready
|
||||
Other/Miscellaneous
Carried Forward
04/26/2023
1. complete perimeter wires as discussed with contractor
2. provide tie wires at all wires that exceed 1 and 6
3. provide positive attachment at light fixtures as discussed with contractor
4 complete drywall at wall in shoe storage area as per city approved plans
5.not ready
|
||||
Mechanical Final Inspection | Not Ready | 4/26/2023 | 4/26/2023 | 04/26/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
04/26/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Carried Forward
04/26/2023
1.complete mono coat as discussed with contractor
2. complete drywall penetration's as discussed with contractor
3. not ready
|
||||
Other/Miscellaneous
Carried Forward
04/26/2023
1.complete mono coat as discussed with contractor
2. complete drywall penetration's as discussed with contractor
3. not ready
|
||||
Fire Or Smoke Damper Inspection | VOID | 5/16/2023 | 5/17/2023 | 05/17/2023 |
David Drake ((253) 864-4171) | ||||
Building Final Inspection | Not Ready | 5/19/2023 | 5/19/2023 | 05/19/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Carried Forward
05/19/2023
1. complete guard rail at mezzanine as discussed with contractor
2.provide duct report at time of next inspection
3. not ready
|
||||
Building Final Inspection | Failed | 5/25/2023 | 5/25/2023 | 05/25/2023 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Resolved
05/25/2023
1. complete guard rail at mezzanine as discussed with contractor
2.provide duct report at time of next inspection
3. not ready
|
||||
Other/Miscellaneous
Carried Forward
05/25/2023
1. complete min. 42'' guard rail at mezzanine as discussed with contractor.
|
||||
Erosion And Sediment Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Comment Building Div Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Comment Engineering Div Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Footing/Setback Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Foundation/Rebar Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Underfloor Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Slab/Insulation Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Block Wall Rebar Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Shear Wall Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Firewall/Firestop Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Energy (Insulation) Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Re-Roof Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Refrigeration Line Test Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Exhaust/Vent Fans Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Cover Inspection/Thrust Blocks Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Emergency Radio Test Review Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Engineering Final Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Floodproof Certification Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Elevation Verification Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Planning Final Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Mechanical Final Inspection | VOID | 05/30/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Outstanding
04/26/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Outstanding
04/26/2023
1.complete mono coat as discussed with contractor
2. complete drywall penetration's as discussed with contractor
3. not ready
|
||||
Other/Miscellaneous
Outstanding
04/26/2023
1.complete mono coat as discussed with contractor
2. complete drywall penetration's as discussed with contractor
3. not ready
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Building Permit Standard Conditions | Open | Standard Conditions | |||
:
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
|||||
Fire Review Conditions | Open | Standard Conditions | |||
:
• Comply with 2018 IFC and 2018 IBC
• L&I Final required prior to Fire Final
• Exit lighting test required, contractor to provide light meter
• Separate permits required for Fire Alarm and Fire Sprinkler
• RTU’S will be required to be tested for shut down
• Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection.
• Fire extinguishers required per code
• A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System.
• Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box
• All above items to be completed prior to fire final. Fire final required before building final
Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
There are no related items for this permit application.
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.