CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCTI20221702
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 01/26/2023 |
Appliance Vent - Separate Fee | $9.60 | $9.60 | Paid | 01/26/2023 |
Building Permit Fee | $111.25 | $111.25 | Paid | 01/26/2023 |
Mechanical Permit Fee | $40.00 | $40.00 | Paid | 01/26/2023 |
Plumbing Fixtures Fee | $39.00 | $39.00 | Paid | 01/26/2023 |
Plumbing Permit Fee | $40.00 | $40.00 | Paid | 01/26/2023 |
Building Plan Review Fee | $72.31 | $72.31 | Paid | 11/29/2022 |
Mechanical Plan Review Fee | $32.24 | $32.24 | Paid | 11/29/2022 |
Plumbing Plan Review Fee | $51.35 | $51.35 | Paid | 11/29/2022 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 01/26/2023 |
Sewer System Development ChargeFee - Tenant Improvment/Addition | $3,551.67 | $3,551.67 | Paid | 01/26/2023 |
Water System Development ChargeFee - Tenant Improvment/Addition | $2,854.20 | $2,854.20 | Paid | 01/26/2023 |
Resubmittal Fee | $130.00 | $130.00 | Paid | 01/12/2023 |
Resubmittal Fee | $130.00 | $130.00 | Paid | 01/12/2023 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
Water System Development ChargeFee - Tenant Improvment/Addition | $0.00 | $0.00 | Paid | 12/12/2022 |
$2,854.20
|
||||
Totals: | $7,351.62 | $7,351.62 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Building Final Inspection | Not Ready | 1/31/2023 | 1/31/2023 | 01/31/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
01/31/2023
1.this was a comment inspection
2. precon meeting to talk about work to be performed on site
3. contractor to start demo once exposed he will schedule a comment inspection
|
||||
Comment Building Div Inspection | Not Ready | 2/2/2023 | 2/2/2023 | 02/02/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
02/02/2023
1. contractor did partial demo to get game plan on plumbing ,and framing
2.discussed path for project
|
||||
Plumbing Rough In Inspection | Failed | 2/21/2023 | 2/21/2023 | 02/21/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
02/21/2023
1. provide as-built of plumbing from architect and resubmit to city for review and approval
2.not ready
|
||||
Plumbing Rough In Inspection | Partial Pass | 3/7/2023 | 3/7/2023 | 03/07/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
03/07/2023
1. provide as-built of plumbing from architect and resubmit to city for review and approval
2.not ready
|
||||
Firewall/Firestop Inspection | Failed | 3/8/2023 | 3/8/2023 | 03/08/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
03/08/2023
1. complete fire stopping in wall as discussed with contractor
|
||||
Frame Inspection | Failed | 3/8/2023 | 3/8/2023 | 03/08/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
03/08/2023
1. remove screws from top of wall that connect to gridded ceiling
2. provide bracing detail for top of wall as discussed with contractor
3.OWNER HAS OPTED TO NOT INSTALL DRYER PER APPROVED CITY PLANS AT TIME OF INSPECTION NO ELECTRICAL OR DRYER VENT WAS INSTALLED
|
||||
Firewall/Firestop Inspection | Passed | 3/9/2023 | 3/9/2023 | 03/09/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
03/09/2023
1. complete fire stopping in wall as discussed with contractor
|
||||
Frame Inspection | Passed | 3/9/2023 | 3/9/2023 | 03/09/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
03/09/2023
1. remove screws from top of wall that connect to gridded ceiling
2. provide bracing detail for top of wall as discussed with contractor
3.OWNER HAS OPTED TO NOT INSTALL DRYER PER APPROVED CITY PLANS AT TIME OF INSPECTION NO ELECTRICAL OR DRYER VENT WAS INSTALLED
|
||||
Wallboard / Drywall Inspection | Failed | 3/13/2023 | 3/13/2023 | 03/13/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
03/13/2023
1. rescrew areas where over penetrated as discussed with contractor
|
||||
Wallboard / Drywall Inspection | Passed | 3/14/2023 | 3/14/2023 | 03/14/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
03/14/2023
1. rescrew areas where over penetrated as discussed with contractor
|
||||
Exit Lighting Test Inspection | Passed | 3/22/2023 | 3/23/2023 | 03/23/2023 |
David Drake ((253) 864-4171) | ||||
Fire Final Inspection | Passed | 3/29/2023 | 3/29/2023 | 03/29/2023 |
David Drake ((253) 864-4171) | ||||
Plumbing Final Inspection | Not Ready | 3/30/2023 | 3/30/2023 | 03/30/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
03/30/2023
1. provide engineering final approval prior to scheduling the final building inspection
|
||||
Engineering Final Inspection | Passed | 3/31/2023 | 3/31/2023 | 03/31/2023 |
Michael Rosenau ((253) 344-6753) | ||||
Building Final Inspection | Failed | 4/3/2023 | 4/3/2023 | 04/03/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
04/03/2023
1.this was a comment inspection
2. precon meeting to talk about work to be performed on site
3. contractor to start demo once exposed he will schedule a comment inspection
|
||||
Other/Miscellaneous
Carried Forward
04/03/2023
1. provide occupancy signage at front door as discussed with contractor
2.provide open toilet seat
3.provide boot protection at angle stops in bathroom
4.provide hammer arrestors at washing machine
|
||||
Plumbing Final Inspection | Not Ready | 4/3/2023 | 4/3/2023 | 04/03/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
04/03/2023
1. provide engineering final approval prior to scheduling the final building inspection
|
||||
Other/Miscellaneous
Carried Forward
04/03/2023
1. see notes on building final todays date
|
||||
Building Final Inspection | Passed | 4/4/2023 | 4/4/2023 | 04/04/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
04/04/2023
1. provide occupancy signage at front door as discussed with contractor
2.provide open toilet seat
3.provide boot protection at angle stops in bathroom
4.provide hammer arrestors at washing machine
|
||||
Plumbing Final Inspection | Passed | 4/4/2023 | 4/4/2023 | 04/04/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
04/04/2023
1. see notes on building final todays date
|
||||
Comment Engineering Div Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Footing/Setback Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Foundation/Rebar Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Slab/Insulation Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Roof Sheathing Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Shear Wall Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Energy (Insulation) Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Combination Frame And Rough In Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Ceiling Grid/T-Bar Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Hydronic Piping Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Mechanical Rough In Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Refrigeration Line Test Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Exhaust Hood Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Light Test For Grease Duct Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Exhaust/Vent Fans Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Medical Gas Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Fire Or Smoke Damper Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Cover Inspection/Thrust Blocks Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Emergency Radio Test Review Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Planning Final Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Mechanical Final Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Comment Building Div Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Outstanding
02/02/2023
1. contractor did partial demo to get game plan on plumbing ,and framing
2.discussed path for project
|
||||
Plumbing Rough In Inspection | VOID | 04/04/2023 | ||
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Outstanding
03/07/2023
1. provide as-built of plumbing from architect and resubmit to city for review and approval
2.not ready
|
Condition | Status | Category |
---|---|---|
Building Permit Standard Conditions | Open | Standard Conditions |
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
||
Fire Review Conditions | Open | Standard Conditions |
• Comply with 2018 IFC and 2018 IBC
• Total coverage required in the city of puyallup subject to field inspection.
• L&I Final required prior to Fire Final
• Exit lighting test required, contractor to provide light meter
• A separate permit may be required if fire alarm or sprinkler system is altered
• Separate permits required for Fire Alarm and Fire Sprinkler
• RTU’S will be required to be tested for shut down
• Fire extinguishers required per code
• Address or suite number required on space
• Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box
• All above items to be completed prior to fire final. Fire final required before building final
Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
There are no related items for this permit application.
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.