CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20230139


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20230139
Commercial - Tenant Improvement/Remodel
Closed
VANNOY SARA JO & CHRISTIAN
Alteration/Remodel
Construct a new cat cafe within the existing shell of the building.- CATFFEINATED CAFE
02/07/2023
01/04/2024
09/29/2025
07/17/2025

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Building Review Approved 12/28/2023 12/28/2023
Engineering Traffic Review Approved 12/28/2023 12/19/2023
Fire Review Approved 12/28/2023 12/18/2023
Planning Review Approved 12/28/2023 12/14/2023
Engineering Review Approved 12/28/2023 12/14/2023
Fire Review Approved 03/10/2023 03/10/2023
Building Review Failed 03/10/2023 03/02/2023
Engineering Traffic Review Approved 03/10/2023 02/27/2023
Engineering Review Approved 03/10/2023 02/15/2023
Planning Review Approved 03/10/2023 02/14/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 01/03/2024
Building Permit Fee $713.75 $713.75 Paid 01/03/2024
Plumbing Permit Fee $40.00 $40.00 Paid 01/03/2024
Plumbing Fixtures Fee $52.00 $52.00 Paid 01/03/2024
Building Plan Review Fee $274.01 $274.01 Paid 02/07/2023
Plumbing Plan Review Fee $59.80 $59.80 Paid 02/07/2023
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 01/03/2024
Building Plan Review Fee $189.93 $189.93 Paid 01/03/2024
$463.94
Sewer System Development Charge Fee - Tenant Improvment/Addition $4,250.50 $4,250.50 Paid 01/03/2024
Water System Development Charge Fee - Tenant Improvment/Addition $1,922.86 $1,922.86 Paid 01/03/2024
Resubmittal/Revision Fee $130.00 $130.00 Paid 03/23/2023
Building Division Fee (Hourly) $540.00 $540.00 Paid 07/24/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Not Ready 2/8/2024 2/8/2024 02/08/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
02/08/2024
1:talked about plan changes and frame requirments

Plumbing Rough In Inspection Partial Pass 2/8/2024 2/8/2024 02/08/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
02/08/2024
below slab plumbing approved to include interceptor.

Slab/Insulation Inspection Passed 2/13/2024 2/13/2024 02/13/2024
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Partial Pass 3/7/2024 3/7/2024 03/07/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
03/07/2024
1:supply ok 2:provide test on dwv

Frame Inspection Not Ready 5/16/2024 5/16/2024 05/16/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
05/16/2024
1. provide test on DWV at time of next inspection 2.complete positive attachment at all single top plates as discussed with contractor 3.complete all fire stop as discussed with contractor 4. provide fastener and plates at bottom plates per city approved plans 5. complete hangers at rafters in entry as discussed with contractor 6.complete duct seal 7. remove insulation from mechanical in attic to verify sealing of ducts 8.complete all seismic bracing on duct work 9.not a complete list

Frame Inspection Passed 5/22/2024 5/22/2024 05/22/2024
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
05/22/2024
1. provide test on DWV at time of next inspection 2.complete positive attachment at all single top plates as discussed with contractor 3.complete all fire stop as discussed with contractor 4. provide fastener and plates at bottom plates per city approved plans 5. complete hangers at rafters in entry as discussed with contractor 6.complete duct seal 7. remove insulation from mechanical in attic to verify sealing of ducts 8.complete all seismic bracing on duct work 9.not a complete list

Energy (Insulation) Inspection Passed 5/29/2024 5/29/2024 05/29/2024
Kevin Spruell ((253) 841-5590)
Comment Building Div Inspection Partial Pass 5/30/2024 5/30/2024 05/30/2024
Kevin Spruell ((253) 841-5590)
Wallboard / Drywall Inspection Passed 6/5/2024 6/5/2024 06/05/2024
Kevin Spruell ((253) 841-5590)
Planning Final Inspection VOID 07/05/2024
Nabila Comstock ((253) 770-3361)
Comment Building Div Inspection Not Ready 7/8/2024 7/8/2024 07/08/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/08/2024
1. discussed requirements for building final

Fire Final Inspection Not Ready 7/8/2024 7/8/2024 07/09/2024
David Drake ((253) 864-4171)
Erosion And Sediment Inspection Passed 07/09/2024
Jeff Hill ((253) 204-5633)
Comment Engineering Div Inspection Passed 07/09/2024
Jeff Hill ((253) 204-5633)
Cover Inspection/Thrust Blocks Inspection Passed 07/09/2024
Jeff Hill ((253) 204-5633)
Comment Engineering Div Inspection Failed 7/9/2024 07/09/2024
Jeff Hill ((253) 204-5633)
Corrections:


Other/Miscellaneous
Carried Forward
07/09/2024
certify RPBA's

Comment Engineering Div Inspection VOID 07/11/2024
Jeff Hill ((253) 204-5633)
Corrections:


Other/Miscellaneous
Outstanding
07/09/2024
certify RPBA's

Engineering Final Inspection Passed 7/11/2024 07/11/2024
Jeff Hill ((253) 204-5633)
Corrections:


Other/Miscellaneous
Resolved
07/11/2024
Certify RPBA's

Exit Lighting Test Inspection VOID 07/11/2024
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 07/11/2024
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 07/11/2024
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 07/11/2024
David Drake ((253) 864-4171)
Fire Final Inspection Passed w/ Conditions 7/11/2024 07/11/2024
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Carried Forward
07/11/2024
Approved pending cleanup of the space and building final inspections.

Ceiling Grid/T-Bar Inspection Partial Pass 7/12/2024 7/12/2024 07/13/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/13/2024
date of inspection 7/12/2024 1.complete perimeter wires as discussed with contractor 2. complete tie wire at can light 3.ok to drop tiles as discussed with contractor

Building Final Inspection Partial Pass 7/12/2024 7/12/2024 07/16/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/16/2024
date of inspection 7/13/2024 1.seal line set house on roof 2.label equipment on roof for space it is servicing 3.remove debri from roof 4.provide access,service platform, service plug and light at duct heater in attic per mech code 5.provide plumbing boots at supply in storage room 6.provide and maintain clear access at corridor where bathrooms are 7.seal penetration's at mini split drain line 8.do not use ice maker untel air gap is verified or RPBA is installed and certified 9.see email from building official on back corridor future access 10. provide permanent roof access as discussed with contractor 11. pay after hours inspection fee for todays inspection prior to scheduling next inspection 12.TCO granted for 10 working days 13.all ceiling corrections approved

Comment Building Div Inspection Partial Pass 7/26/2024 7/26/2024 07/26/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
07/26/2024
1. discussed requirements for building final

Other/Miscellaneous
Carried Forward
07/26/2024
received backflow cert for ice maker

Comment Building Div Inspection Not Ready 1/7/2025 1/7/2025 01/07/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
01/07/2025
1. discussed requirements for building final

Other/Miscellaneous
Carried Forward
01/07/2025
talked about final requirements

Building Final Inspection Passed 1/17/2025 1/17/2025 01/17/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
01/17/2025
date of inspection 7/13/2024 1.seal line set house on roof 2.label equipment on roof for space it is servicing 3.remove debri from roof 4.provide access,service platform, service plug and light at duct heater in attic per mech code 5.provide plumbing boots at supply in storage room 6.provide and maintain clear access at corridor where bathrooms are 7.seal penetration's at mini split drain line 8.do not use ice maker untel air gap is verified or RPBA is installed and certified 9.see email from building official on back corridor future access 10. provide permanent roof access as discussed with contractor 11. pay after hours inspection fee for todays inspection prior to scheduling next inspection 12.TCO granted for 10 working days 13.all ceiling corrections approved

Footing/Setback Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Foundation/Rebar Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Underfloor Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Block Wall Rebar Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Roof Sheathing Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Shear Wall Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Firewall/Firestop Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Plumbing Below Slab Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Combination Frame And Rough In Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Re-Roof Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Hydronic Piping Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Refrigeration Line Test Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Exhaust Hood Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Light Test For Grease Duct Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Exhaust/Vent Fans Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Medical Gas Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Plumbing Final Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Plumbing Rough In Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Ceiling Grid/T-Bar Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Corrections:


Other/Miscellaneous
Outstanding
07/13/2024
date of inspection 7/12/2024 1.complete perimeter wires as discussed with contractor 2. complete tie wire at can light 3.ok to drop tiles as discussed with contractor

Comment Building Div Inspection VOID 04/02/2025
Joyce Kennedy ((253) 841-5405)
Corrections:


Other/Miscellaneous
Outstanding
01/07/2025
1. discussed requirements for building final

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2018 IFC and 2018 IBC • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • RTU’S will be required to be tested for shut down • Fire extinguishers required per code • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Miscellaneous Condition Resolved Prior to Issuance
Building Division
CE20220037 - COMPLIANCE WILL NEED TO BE RESOLVED PRIOR TO ISSUANCE PER BLDG. OFFICIAL
Side Sewer Sample Tee Resolved Prior to Issuance
Engineering Division
The sampling tee requirement has bee waived by the Public Works Director, see attached email. LL 09/08/2023 A side sewer sampling connection and a new sewer cleanout cap is required to be installed on the commercial sanitary side sewer service in accordance with City policy ENG 21-03.  See City Standard Detail 04.03.04.
Miscellaneous Condition Resolved Prior to Occupancy
Engineering Division
The sampling tee requirement has bee waived by the Public Works Director, see attached email. LL 09/08/2023 The installation of the required sewer sampling tee and cleanout cap must be competed and a final approval granted prior to occupancy.
Engineering Commercial Standard Conditions Resolved Standard Conditions
Engineering Division
Development Engineering standard commercial conditions: - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Miscellaneous Condition Resolved Prior to Issuance
Traffic Division
N/A
Backflow Protection Device - Commercial RPBA Resolved Prior to Completion
Development & Permitting Services
An approved reduced pressure backflow assembly (RPBA) device is required to be installed on the commercial water service per City Standard Detail 03.04.02. For more information, visit https://www.cityofpuyallup.org/1131/Backflow-Prevention-Cross-Connection. Upon approval of the installation by the city inspector, the backflow device shall be tested by a Washington State certified backflow assembly tester, and the test report results shall be submitted to the City prior to occupancy of the building.

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20240431 Closed Commercial - Tenant Improvement/Remodel

Documents & Images

Date Uploaded File Type Name
02/07/2023 Receipt Receipt for transaction:2023-000182
03/23/2023 Receipt Receipt for transaction:2023-000480
12/28/2023 Plans CONSTRUCTION PLAN SET - (Stamped)
12/28/2023 Plans MECHANICAL PLANS (Stamped)
12/28/2023 Plans Cross Control Manual (Stamped)
12/28/2023 Report installation-guide-pdf-20230206201631 (Stamped)
12/28/2023 Form ENERGY CODE WORKSHEET (Stamped)
12/28/2023 Form Plumbing worksheet (Stamped)
01/03/2024 Receipt Receipt for transaction:2024-000012
01/04/2024 Permit Permit - Detailed
01/04/2024 Letter Permit Job Card
05/16/2024 Report Inspection Report (Frame Inspection)
05/22/2024 Report Inspection Report (Frame Inspection)
05/29/2024 Report Inspection Report (Energy (Insulation) Inspection)
05/30/2024 Report Inspection Report (Comment Building Div Inspection)
06/05/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/08/2024 Report Inspection Report (Comment Building Div Inspection)
07/09/2024 RPBA 212 S MERIDIAN PUYALLUP WA 98371 RPBA
07/09/2024 Report Inspection Report (Comment Engineering Div Inspection)
07/11/2024 Report Inspection Report (Engineering Final Inspection)
07/13/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
07/16/2024 Report Inspection Report (Building Final Inspection)
07/24/2024 Receipt Receipt for transaction:2024-001532
12/06/2024 Letter Permit Expiration Notice
01/17/2025 Other Certificate of Occupancy


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.