CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20231772


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20231772
Commercial - Tenant Improvement/Remodel
Closed
MULTICARE HEALTH SYSTEM
Alteration/Remodel
Remodel of portion of emergency department to create spaces for treating lower acuity patients in open bays by removing some walls and installing wall mounted hand-wash sinks. Additionally will convert open room to become two separate rooms for holding patients requiring seclusion with enclosed workroom for staff to observe seclusion rooms. HVAC will be modified to serve the new spaces. Some electrical updates will also occur. - GOOD SAM HOSPITAL - ED
12/22/2023
05/06/2024
03/23/2025

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 04/17/2024 04/15/2024
Engineering Traffic Review Approved 04/17/2024 04/09/2024
Planning Review Approved 04/17/2024 04/04/2024
Fire Review Approved 04/17/2024 04/04/2024
Engineering Review Approved 04/17/2024 04/04/2024
Building Review Failed 04/03/2024 04/02/2024
Engineering Traffic Review Approved 04/03/2024 03/28/2024
Fire Review Approved 04/03/2024 03/26/2024
Engineering Review Approved 04/03/2024 03/14/2024
Planning Review Approved 04/03/2024 03/07/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 05/06/2024
Mechanical Duct Work Fee $24.00 $24.00 Paid 05/06/2024
Building Permit Fee $6,294.95 $6,294.95 Paid 05/06/2024
Mechanical Permit Fee $40.00 $40.00 Paid 05/06/2024
Plumbing Permit Fee $40.00 $40.00 Paid 05/06/2024
Plumbing Fixtures Fee $117.00 $117.00 Paid 05/06/2024
Building Plan Review Fee $4,091.72 $4,091.72 Paid 03/06/2024
Mechanical Plan Review Fee $41.60 $41.60 Paid 03/06/2024
Plumbing Plan Review Fee $102.05 $102.05 Paid 03/06/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 05/06/2024
Resubmittal Fee $180.00 $180.00 Paid 04/02/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 06/18/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 06/18/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 08/06/2024
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 08/06/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Not Ready 5/8/2024 5/8/2024 05/08/2024
Shannon King ((253) 840-6684)
Comment Building Div Inspection Not Ready 5/14/2024 5/14/2024 05/14/2024
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Partial Pass 6/3/2024 6/3/2024 06/03/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
06/03/2024
1.supply and return ducts approved for insulation

Plumbing Rough In Inspection Partial Pass 6/11/2024 6/11/2024 06/11/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
06/11/2024
inspection date 6/11/2024 1.DWV approved at 7 1/2 pounds air 2.supply approved at 80 psi 3. provide run test at DWV tie ins at time of next inspection

Frame Inspection Failed 6/11/2024 6/11/2024 06/11/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
06/11/2024
inspection date 6/11/2024 1.provide electrical cover approval 2.complete all fasteners at framing per city approved plans 3. complete putty packs at electrical boxes in rated wall 4.complete nail plates at plumbing 5. provide detail for head of wall

Exhaust/Vent Fans Inspection Partial Pass 6/11/2024 6/11/2024 06/11/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
06/11/2024
inspection date 6/11/2024 1. exhaust terminations at soffits approved

Energy (Insulation) Inspection Partial Pass 6/12/2024 6/12/2024 06/12/2024
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 6/13/2024 6/13/2024 06/13/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
06/13/2024
complete drywall at 1 hour wall from soffit to top of wall and storage room.

Plumbing Rough In Inspection Partial Pass 6/20/2024 6/20/2024 06/20/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
06/20/2024
inspection date 6/11/2024 1.DWV approved at 7 1/2 pounds air 2.supply approved at 80 psi 3. provide run test at DWV tie ins at time of next inspection

Other/Miscellaneous
Carried Forward
06/20/2024
date of inspection 6/20/2024 1.run test on DWV tie in at level A approved

Building Final Inspection Not Ready 7/5/2024 7/5/2024 07/05/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
07/05/2024
cancelled by russell

Mechanical Final Inspection Not Ready 7/5/2024 7/5/2024 07/05/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
07/05/2024
cancelled by Russell

Fire Final Inspection Not Ready 7/5/2024 7/5/2024 07/05/2024
Ray Cockerham ((253) 841-5585)
Building Final Inspection Partial Pass 7/8/2024 7/8/2024 07/08/2024
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Not Ready 7/16/2024 7/16/2024 07/16/2024
Shannon King ((253) 840-6684)
Ceiling Grid/T-Bar Inspection Not Ready 7/16/2024 7/16/2024 07/16/2024
Shannon King ((253) 840-6684)
Plumbing Final Inspection Not Ready 7/16/2024 7/16/2024 07/16/2024
Shannon King ((253) 840-6684)
Mechanical Final Inspection Not Ready 7/16/2024 7/16/2024 07/16/2024
Shannon King ((253) 840-6684)
Fire Final Inspection Partial Pass 7/19/2024 7/22/2024 07/22/2024
David Drake ((253) 864-4171)
Building Final Inspection Failed 7/22/2024 7/22/2024 07/22/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
07/22/2024
1 ; provide department of health final prior to building final approval. 2 ; provide balance report prior to mechanical final.

Mechanical Final Inspection Failed 7/22/2024 7/22/2024 07/22/2024
Shannon King ((253) 840-6684)
Plumbing Final Inspection Failed 7/22/2024 7/22/2024 07/22/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
07/22/2024
see Building final inspection dated 7/22/2024

Frame Inspection Partial Pass 7/26/2024 7/26/2024 07/26/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
07/26/2024
inspection date 6/11/2024 1.provide electrical cover approval 2.complete all fasteners at framing per city approved plans 3. complete putty packs at electrical boxes in rated wall 4.complete nail plates at plumbing 5. provide detail for head of wall

Other/Miscellaneous
Outstanding
07/26/2024
ok to top down phase 2 wall between 180.7b and c

Plumbing Rough In Inspection Partial Pass 7/26/2024 7/26/2024 07/26/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
07/26/2024
inspection date 6/11/2024 1.DWV approved at 7 1/2 pounds air 2.supply approved at 80 psi 3. provide run test at DWV tie ins at time of next inspection

Other/Miscellaneous
Carried Forward
07/26/2024
date of inspection 6/20/2024 1.run test on DWV tie in at level A approved

Other/Miscellaneous
Carried Forward
07/26/2024
sink at 1807 supply and drain ok

Mechanical Rough In Inspection Partial Pass 7/31/2024 7/31/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/01/2024
1.supply and return ducts approved for insulation

Other/Miscellaneous
Carried Forward
08/01/2024
phase two 1.duct ok to insulate area 180.7 rooms B and C

Wallboard / Drywall Inspection Partial Pass 7/31/2024 7/31/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/01/2024
complete drywall at 1 hour wall from soffit to top of wall and storage room.

Other/Miscellaneous
Carried Forward
08/01/2024
phase 2 1. top out in area 180.7 rooms B and C approved

Building Final Inspection Partial Pass 7/31/2024 7/31/2024 08/01/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
08/01/2024
1 ; provide department of health final prior to building final approval. 2 ; provide balance report prior to mechanical final.

Other/Miscellaneous
Carried Forward
08/01/2024
phase 1 ok to occupy

Firewall/Firestop Inspection Not Ready 8/6/2024 8/6/2024 08/07/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/07/2024
1.provide special inspection report for fire stopping at time of next inspection

Frame Inspection Failed 8/6/2024 8/6/2024 08/07/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/07/2024
inspection date 6/11/2024 1.provide electrical cover approval 2.complete all fasteners at framing per city approved plans 3. complete putty packs at electrical boxes in rated wall 4.complete nail plates at plumbing 5. provide detail for head of wall

Other/Miscellaneous
Carried Forward
08/07/2024
phase 2 1. complete fasteners at framing 2.complete framing at head outs

Wallboard / Drywall Inspection Partial Pass 8/7/2024 8/7/2024 08/08/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/08/2024
complete drywall at 1 hour wall from soffit to top of wall and storage room.

Other/Miscellaneous
Carried Forward
08/08/2024
phase 2 1. top out in area 180.7 rooms B and C approved

Other/Miscellaneous
Carried Forward
08/08/2024
date of inspection 8/7/2024 2nd phase 1. rooms M180.7B and M180.7C framing and fire stopping above hard lids approved for cover walls in this area also approved for cover

Wallboard / Drywall Inspection Partial Pass 8/9/2024 8/9/2024 08/09/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/09/2024
complete drywall at 1 hour wall from soffit to top of wall and storage room.

Other/Miscellaneous
Carried Forward
08/09/2024
phase 2 1. top out in area 180.7 rooms B and C approved

Other/Miscellaneous
Carried Forward
08/09/2024
date of inspection 8/7/2024 2nd phase 1. rooms M180.7B and M180.7C framing and fire stopping above hard lids approved for cover walls in this area also approved for cover

Other/Miscellaneous
Carried Forward
08/09/2024
date of inspection 8/8/2024 1.drywall approved in rooms M180.7B and M180.7C and surrounding area 2.phase 2

Mechanical Rough In Inspection Partial Pass 8/26/2024 8/26/2024 08/27/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/27/2024
1.supply and return ducts approved for insulation

Other/Miscellaneous
Carried Forward
08/27/2024
phase two 1.duct ok to insulate area 180.7 rooms B and C

Other/Miscellaneous
Carried Forward
08/27/2024
phase 2 ceiling grid cover inspection for area 180.7 approved for cover

Emergency Radio Test Review Inspection VOID 09/20/2024
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 09/20/2024
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 09/20/2024
David Drake ((253) 864-4171)
Mechanical Final Inspection Failed 9/20/2024 9/20/2024 09/20/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
09/20/2024
nobody onsite no contact in the morning.

Plumbing Final Inspection Failed 9/20/2024 9/20/2024 09/20/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
09/20/2024
see Building final inspection dated 7/22/2024

Other/Miscellaneous
Carried Forward
09/20/2024
nobody onsite no contact in the morning.

Building Final Inspection Failed 9/20/2024 9/20/2024 09/20/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
09/20/2024
phase 1 ok to occupy

Other/Miscellaneous
Carried Forward
09/20/2024
nobody onsite no contact in the morning.

Erosion And Sediment Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Comment Engineering Div Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Footing/Setback Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Foundation/Rebar Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Underfloor Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Slab/Insulation Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Block Wall Rebar Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Shear Wall Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Refrigeration Line Test Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Gas Test Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Comment Building Div Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Planning Final Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Engineering Final Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Energy (Insulation) Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Exhaust/Vent Fans Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
06/11/2024
inspection date 6/11/2024 1. exhaust terminations at soffits approved

Mechanical Rough In Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/27/2024
1.supply and return ducts approved for insulation

Other/Miscellaneous
Outstanding
08/27/2024
phase two 1.duct ok to insulate area 180.7 rooms B and C

Other/Miscellaneous
Outstanding
08/27/2024
phase 2 ceiling grid cover inspection for area 180.7 approved for cover

Wallboard / Drywall Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/09/2024
complete drywall at 1 hour wall from soffit to top of wall and storage room.

Other/Miscellaneous
Outstanding
08/09/2024
phase 2 1. top out in area 180.7 rooms B and C approved

Other/Miscellaneous
Outstanding
08/09/2024
date of inspection 8/7/2024 2nd phase 1. rooms M180.7B and M180.7C framing and fire stopping above hard lids approved for cover walls in this area also approved for cover

Other/Miscellaneous
Outstanding
08/09/2024
date of inspection 8/8/2024 1.drywall approved in rooms M180.7B and M180.7C and surrounding area 2.phase 2

Frame Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
08/07/2024
inspection date 6/11/2024 1.provide electrical cover approval 2.complete all fasteners at framing per city approved plans 3. complete putty packs at electrical boxes in rated wall 4.complete nail plates at plumbing 5. provide detail for head of wall

Other/Miscellaneous
Outstanding
08/07/2024
phase 2 1. complete fasteners at framing 2.complete framing at head outs

Plumbing Rough In Inspection VOID 09/24/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
07/26/2024
inspection date 6/11/2024 1.DWV approved at 7 1/2 pounds air 2.supply approved at 80 psi 3. provide run test at DWV tie ins at time of next inspection

Other/Miscellaneous
Outstanding
07/26/2024
date of inspection 6/20/2024 1.run test on DWV tie in at level A approved

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
: • Comply with 2018 IFC and 2018 IBC • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • Separate permits required for Fire Alarm and Fire Sprinkler • RTU’S will be required to be tested for shut down • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRFS20240363 Issued Fire Sprinklers

Documents & Images

Date Uploaded File Type Name
03/06/2024 Receipt Receipt for transaction:2024-000426
04/02/2024 Form Building Permit Application 2023_202305181229557439 (Flattened)
04/02/2024 Form CORRECTION RESPONSE LETTER
04/02/2024 Letter Permit Review Correction Letter
04/02/2024 Receipt Receipt for transaction:2024-000643
04/16/2024 Form 1772 PLUMB FXTRE WRKSHEET (Stamped)
04/16/2024 Plans CONSTRUCTION PLAN SET - RESUB (Stamped)
04/16/2024 Other DOHapproval letter (Stamped)
05/06/2024 Permit Permit - Detailed
05/06/2024 Letter Permit Job Card
05/06/2024 Receipt Receipt for transaction: 2024-000928
05/14/2024 Report Inspection Report (Comment Building Div Inspection)
06/03/2024 Report Inspection Report (Mechanical Rough In Inspection)
06/11/2024 Report Inspection Report (Exhaust/Vent Fans Inspection)
06/11/2024 Report Inspection Report (Frame Inspection)
06/11/2024 Report Inspection Report (Plumbing Rough In Inspection)
06/12/2024 Report Inspection Report (Energy (Insulation) Inspection)
06/13/2024 Report Inspection Report (Wallboard / Drywall Inspection)
06/18/2024 Receipt Receipt for transaction:2024-001302
06/20/2024 Report Inspection Report (Plumbing Rough In Inspection)
07/08/2024 Report Inspection Report (Building Final Inspection)
07/16/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
07/16/2024 Report Inspection Report (Firewall/Firestop Inspection)
07/16/2024 Report Inspection Report (Mechanical Final Inspection)
07/16/2024 Report Inspection Report (Plumbing Final Inspection)
07/17/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
07/22/2024 Report Inspection Report (Building Final Inspection)
07/22/2024 Report Inspection Report (Mechanical Final Inspection)
07/22/2024 Report Inspection Report (Plumbing Final Inspection)
08/01/2024 Report Inspection Report (Building Final Inspection)
08/01/2024 Report Inspection Report (Mechanical Rough In Inspection)
08/01/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/06/2024 Receipt Receipt for transaction:2024-001630
08/07/2024 Report Inspection Report (Firewall/Firestop Inspection)
08/07/2024 Report Inspection Report (Frame Inspection)
08/08/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/09/2024 Report Inspection Report (Wallboard / Drywall Inspection)
08/27/2024 Report Inspection Report (Firewall/Firestop Inspection)
08/27/2024 Report Inspection Report (Mechanical Rough In Inspection)
09/24/2024 Report Inspection Report (Building Final Inspection)
09/24/2024 Report Inspection Report (Mechanical Final Inspection)
09/24/2024 Report Inspection Report (Plumbing Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.