CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20240464


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20240464
Commercial - Tenant Improvement/Remodel
Closed
SOUND PROPERTIES LLC
Alteration/Remodel
Interior remodel of existing Tractor Supply store space and add interior pet wash area to that store also - NO new s.f. being added - TRACTOR SUPPLY CO PUYALLUP
03/21/2024
05/21/2024
01/11/2025
07/15/2024

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 06/05/2024 05/21/2024
Engineering Traffic Review Approved 06/05/2024 05/21/2024
Planning Review Approved 06/05/2024 05/21/2024
Building Review Approved 06/05/2024 05/21/2024
Engineering Review Approved 06/05/2024 05/21/2024
Building Review Failed 05/02/2024 05/02/2024
Fire Review Approved 05/02/2024 04/29/2024
Engineering Traffic Review Approved 05/02/2024 04/08/2024
Engineering Review Approved 05/02/2024 04/08/2024
Planning Review Approved 05/02/2024 04/08/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 05/21/2024
Building Permit Fee $1,273.75 $1,273.75 Paid 05/21/2024
Plumbing Fixtures Fee $26.00 $26.00 Paid 05/21/2024
Plumbing Permit Fee $40.00 $40.00 Paid 05/21/2024
Building Plan Review Fee $827.94 $827.94 Paid 03/26/2024
Plumbing Plan Review Fee $42.90 $42.90 Paid 03/26/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 05/21/2024
Sewer System Development ChargeFee - Tenant Improvment/Addition $2,596.20 $2,596.20 Paid 05/21/2024
Water System Development ChargeFee - Tenant Improvment/Addition $1,423.60 $1,423.60 Paid 05/21/2024
Resubmittal Fee $180.00 $180.00 Paid 05/20/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Not Ready 6/7/2024 6/7/2024 06/07/2024
Shannon King ((253) 840-6684)
Underfloor Inspection Partial Pass 6/10/2024 6/10/2024 06/10/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
06/10/2024
1. under slab plumbing approved per city approved plans

Slab/Insulation Inspection Passed 6/12/2024 6/12/2024 06/12/2024
Kevin Spruell ((253) 841-5590)
Plumbing Rough In Inspection Not Ready 6/20/2024 6/20/2024 06/20/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
07/15/2024
1. complete plumbing as discussed with contractor

Frame Inspection Not Ready 6/20/2024 6/20/2024 06/20/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
07/15/2024
1. complete framing as discussed with contractor

Plumbing Rough In Inspection Partial Pass 6/25/2024 6/25/2024 06/25/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
06/25/2024
1. complete plumbing as discussed with contractor

Other/Miscellaneous
Carried Forward
06/25/2024
date of inspection 6/25/2024 1.DWV from pump to ladies rest room to include underground tie in approved 2.DWV and supply approved above slab

Frame Inspection Partial Pass 6/25/2024 6/25/2024 06/25/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
06/25/2024
1. complete framing as discussed with contractor

Other/Miscellaneous
Carried Forward
06/25/2024
date of inspection 6/25/2024 1.framing approved to include all CMU fixes

Comment Engineering Div Inspection Passed 7/1/2024 7/1/2024 07/01/2024
Michael Rosenau ((253) 344-6753)
Roof Sheathing Inspection Not Ready 7/1/2024 7/1/2024 07/01/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
07/15/2024
called in in error

Wallboard / Drywall Inspection Passed 7/1/2024 7/1/2024 07/01/2024
Kevin Spruell ((253) 841-5590)
Fire Final Inspection Passed 7/9/2024 7/9/2024 07/09/2024
David Drake ((253) 864-4171)
Engineering Final Inspection Passed 07/09/2024
Michael Rosenau ((253) 344-6753)
Erosion And Sediment Inspection VOID 07/09/2024
Michael Rosenau ((253) 344-6753)
Building Final Inspection Not Ready 7/9/2024 7/9/2024 07/09/2024
Kevin Spruell ((253) 841-5590)
Plumbing Final Inspection Failed 7/9/2024 7/9/2024 07/09/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
07/15/2024
1. provide test on gas pipe as discussed with contractor 2.provide upc approved hair drains

Exit Lighting Test Inspection VOID 07/10/2024
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 07/10/2024
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 07/10/2024
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 07/10/2024
David Drake ((253) 864-4171)
Plumbing Final Inspection Partial Pass 7/12/2024 7/12/2024 07/13/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/13/2024
1. provide test on gas pipe as discussed with contractor 2.provide upc approved hair drains

Other/Miscellaneous
Carried Forward
07/13/2024
date of inspection 7/12/2024 1. gas test approved at 60 psi

Building Final Inspection Passed 7/15/2024 7/15/2024 07/15/2024
Kevin Spruell ((253) 841-5590)
Footing/Setback Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Foundation/Rebar Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Block Wall Rebar Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Shear Wall Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Firewall/Firestop Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Energy (Insulation) Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Combination Frame And Rough In Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Ceiling Grid/T-Bar Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Re-Roof Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Hydronic Piping Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Refrigeration Line Test Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Exhaust Hood Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Light Test For Grease Duct Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Exhaust/Vent Fans Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Medical Gas Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Planning Final Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Comment Building Div Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Underfloor Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
06/10/2024
1. under slab plumbing approved per city approved plans

Plumbing Rough In Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
06/25/2024
date of inspection 6/25/2024 1.DWV from pump to ladies rest room to include underground tie in approved 2.DWV and supply approved above slab

Frame Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
06/25/2024
date of inspection 6/25/2024 1.framing approved to include all CMU fixes

Roof Sheathing Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/01/2024
called in in error

Plumbing Final Inspection VOID 07/15/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/13/2024
1. provide test on gas pipe as discussed with contractor 2.provide upc approved hair drains

Other/Miscellaneous
Outstanding
07/13/2024
date of inspection 7/12/2024 1. gas test approved at 60 psi

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2021 IFC and 2021 IBC • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • A separate permit may be required if fire alarm or sprinkler system is altered • RTU’S will be required to be tested for shut down • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRMH20241062 Permit(s) Issued Mechanical - COMMERCIAL ONLY

Documents & Images

Date Uploaded File Type Name
03/26/2024 Receipt Receipt for transaction: 2024-000591
05/20/2024 Receipt Receipt for transaction:2024-001043
05/21/2024 Other INSTALLATION INSTRUCTIONS (Stamped)
05/21/2024 Plans CONSTRUCTION PLAN SET (Stamped)
05/21/2024 Report STRUCTURAL CALCS (Stamped)
05/21/2024 Other PLUMBING FIXTURE WRKSHEET (Stamped)
05/21/2024 Letter Permit - Detailed
05/21/2024 Receipt Receipt for transaction:2024-001059
06/03/2024 Letter Permit Job Card
06/07/2024 Report Inspection Report (Comment Building Div Inspection)
06/10/2024 Report Inspection Report (Underfloor Inspection)
06/12/2024 Report Inspection Report (Slab/Insulation Inspection)
06/20/2024 Report Inspection Report (Plumbing Rough In Inspection)
06/20/2024 Report Inspection Report (Frame Inspection)
06/25/2024 Report Inspection Report (Plumbing Rough In Inspection)
06/25/2024 Report Inspection Report (Frame Inspection)
07/01/2024 Report Inspection Report (Comment Engineering Div Inspection)
07/01/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/09/2024 Report Inspection Report (Building Final Inspection)
07/09/2024 Report Inspection Report (Plumbing Final Inspection)
07/13/2024 Report Inspection Report (Plumbing Final Inspection)
07/15/2024 Report Inspection Report (Building Final Inspection)
07/18/2024 Report 20240464 BACKFLOW RESULTS