CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20241902


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20241902
Commercial - Tenant Improvement/Remodel
Closed
LMC PUYALLUP LLC
Alteration/Remodel
1. NEW FIXTURE, FURNITURE, EQUIPMENT AND GRAPHICS INTERIOR PARTITIONS AND DOORS FINISHES IN ALL AREAS CEILING IN ALL AREAS LIGHTING IN ALL AREAS PLUMBING FIXTURES ELECTRICAL SYSTEM MECHANICAL SYSTEM FIRE SAFETY EQUIPMENT EGRESS - T MOBILE - 4227 S MERIDIAN, Unit: E, PUYALLUP, WA 98373 * REVISION (1) - 3/20/2025 - FIELD CONDITION THAT REQUIRES 2 RTU'S TO BE RELOCATED. * REVISION (2) - 5/16/2025 - BASED ON SITE CONDITIONS (SPACE LIMITATIONS WITH HVAC DUCTWORK) THE ROOF FRAMING PLAN, DETAILS, AND CALCS HAVE BEEN UPDATED.
12/11/2024
01/29/2025
12/28/2025
07/01/2025

Locations

Property
0419106015

4227 S MERIDIAN, Unit: E, PUYALLUP, WA 98373

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 06/02/2025 05/19/2025
Building Review Approved 04/03/2025 03/25/2025
Engineering Review Approved 01/13/2025 01/10/2025
Planning Review Approved 01/13/2025 01/09/2025
Fire Review Approved 01/13/2025 01/06/2025
Building Review Approved 01/13/2025 01/02/2025
Engineering Traffic Review VOID 01/13/2025 12/18/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 01/28/2025
AC Unit Fee $39.10 $39.10 Paid 01/28/2025
Air Handling Unit (Up to 10,000 cfm) Fee $14.10 $14.10 Paid 01/28/2025
Exhaust Vent Fan (Bath) Fee $28.20 $28.20 Paid 01/28/2025
Gas Piping (Mechanical) Fee $6.30 $6.30 Paid 12/11/2024
Mechanical Duct Work Fee $24.00 $24.00 Paid 01/28/2025
Ventilation System (apart from Heating/AC) Fee $14.10 $14.10 Paid 01/28/2025
Building Permit Fee $2,225.75 $2,225.75 Paid 01/28/2025
Mechanical Permit Fee $40.00 $40.00 Paid 01/28/2025
Drinking Fountain, Water Cooler, Ice Machine Fee $40.25 $40.25 Paid 01/28/2025
Plumbing Permit Fee $40.00 $40.00 Paid 01/28/2025
Water Heater Fee $13.00 $13.00 Paid 01/28/2025
Building Plan Review Fee $1,446.74 $1,446.74 Paid 12/11/2024
Mechanical Plan Review Fee $107.77 $107.77 Paid 12/11/2024
Plumbing Plan Review Fee $60.61 $60.61 Paid 12/11/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 01/28/2025
Sewer System Development ChargeFee - Tenant Improvment/Addition $865.40 $865.40 Paid 01/28/2025
Resubmittal Fee $180.00 $180.00 Paid 03/20/2025
Resubmittal Fee $180.00 $180.00 Paid 05/19/2025
Inspection Fee - Outside Of Business Hours $540.00 $540.00 Paid 06/06/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Not Ready 2/12/2025 2/12/2025 02/12/2025
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 2/19/2025 2/19/2025 02/19/2025
Ray Cockerham ((253) 841-5585)
Plumbing Rough In Inspection Partial Pass 2/21/2025 2/21/2025 02/21/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
02/21/2025
below slab plumbing approved.

Wallboard / Drywall Inspection Partial Pass 2/24/2025 2/24/2025 02/24/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
02/24/2025
1:approved all but plumbing walls and security room, will need architects attachment detail for concrete board on lid

Slab/Insulation Inspection Passed 2/25/2025 2/25/2025 02/25/2025
Shannon King ((253) 840-6684)
Plumbing Rough In Inspection Passed 2/28/2025 2/28/2025 02/28/2025
Shannon King ((253) 840-6684)
Frame Inspection Not Ready 3/4/2025 3/4/2025 03/04/2025
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 3/6/2025 3/6/2025 03/06/2025
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 3/7/2025 3/7/2025 03/07/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
03/07/2025
bathroom walls approved

Mechanical Rough In Inspection Not Ready 3/17/2025 3/17/2025 03/17/2025
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 3/27/2025 3/27/2025 03/27/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
03/27/2025
public, private restrooms and security rm hard lids ok

Mechanical Rough In Inspection Partial Pass 3/27/2025 3/27/2025 03/27/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
03/27/2025
ductwork at hardlids approved, bathrooms and security rm.

Wallboard / Drywall Inspection Partial Pass 4/3/2025 4/3/2025 04/03/2025
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
04/03/2025
bathroom ceiling drywall approved

Wallboard / Drywall Inspection Passed 4/4/2025 4/4/2025 04/04/2025
Monty Johnson ((253) 770-3326)
Planning Final Inspection VOID 04/25/2025
Jillian Hulse-Lew ((253) 770-3330)
Frame Inspection Not Ready 5/12/2025 5/12/2025 05/12/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/12/2025
1 ; provide city approved plans on-site at time of inspection. not ready

Mechanical Rough In Inspection Partial Pass 5/12/2025 5/12/2025 05/12/2025
Shannon King ((253) 840-6684)
Engineering Final Inspection Not Ready 5/12/2025 5/12/2025 05/12/2025
Jeff Hill ((253) 204-5633)
Corrections:


Other/Miscellaneous
Resolved
05/14/2025
reconnect the roof drain over the ADA ramp

Engineering Final Inspection Passed 5/14/2025 5/14/2025 05/14/2025
Michael Rosenau ((253) 344-6753)
Corrections:


Other/Miscellaneous
Resolved
05/14/2025
reconnect the roof drain over the ADA ramp

Comment Engineering Div Inspection Passed 05/14/2025
Michael Rosenau ((253) 344-6753)
Frame Inspection Not Ready 5/20/2025 5/20/2025 05/20/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/20/2025
1 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. not ready

Ceiling Grid/T-Bar Inspection Not Ready 5/20/2025 5/20/2025 05/20/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
05/20/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Ceiling Grid/T-Bar Inspection Failed 5/21/2025 05/21/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Carried Forward
05/21/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Other/Miscellaneous
Carried Forward
05/21/2025
SEE 5/20 comments 1) Cloud installations; plans provided clear details regarding the all thread and the channel around the all thread below the unistrut framing. Review with engineer all thread bracing above the unistrut to the roof deck. 2) okay to place differs and grills; inspection required 3) Complete perimeter wire main room above exit sign. See framing inspection 5/21 for beams

Frame Inspection Partial Pass 5/21/2025 5/21/2025 05/21/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
05/21/2025
1 ; provide city approved plans on-site at time of inspection. not ready

Other/Miscellaneous
Carried Forward
05/21/2025
Inspection of beams per plan, bracing and truss splices. Approved to proceed.

Ceiling Grid/T-Bar Inspection Failed 5/21/2025 5/21/2025 05/21/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Carried Forward
05/21/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Other/Miscellaneous
Carried Forward
05/21/2025
SEE 5/20 comments 1) Cloud installations; plans provided clear details regarding the all thread and the channel around the all thread below the unistrut framing. Review with engineer all thread bracing above the unistrut to the roof deck. 2) okay to place differs and grills; inspection required 3) Complete perimeter wire main room above exit sign. See framing inspection 5/21 for beams

Frame Inspection Passed 5/28/2025 5/28/2025 05/28/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
05/28/2025
Inspection of beams per plan, bracing and truss splices. Approved to proceed.

Exit Lighting Test Inspection Passed 6/4/2025 6/4/2025 06/04/2025
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 06/04/2025
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 06/04/2025
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 06/04/2025
David Drake ((253) 864-4171)
Plumbing Final Inspection Passed 6/4/2025 6/4/2025 06/04/2025
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Not Ready 6/5/2025 6/5/2025 06/05/2025
Shannon King ((253) 840-6684)
Frame Inspection Not Ready 6/6/2025 6/6/2025 06/06/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/06/2025
1 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. not ready

Frame Inspection Passed 6/7/2025 6/7/2025 06/08/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
06/08/2025
1 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. not ready

Mechanical Rough In Inspection Partial Pass 6/9/2025 6/9/2025 06/09/2025
Shannon King ((253) 840-6684)
Fire Final Inspection Passed 6/10/2025 6/10/2025 06/10/2025
Ray Cockerham ((253) 841-5585)
Ceiling Grid/T-Bar Inspection Not Ready 6/10/2025 6/10/2025 06/10/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/10/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Other/Miscellaneous
Carried Forward
06/10/2025
SEE 5/20 comments 1) Cloud installations; plans provided clear details regarding the all thread and the channel around the all thread below the unistrut framing. Review with engineer all thread bracing above the unistrut to the roof deck. 2) okay to place differs and grills; inspection required 3) Complete perimeter wire main room above exit sign. See framing inspection 5/21 for beams

Ceiling Grid/T-Bar Inspection Not Ready 6/11/2025 6/11/2025 06/11/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
06/11/2025
1 ; complete mechanical rough-in of ducts and positive attachment of diffusers to main and cross tee at ceiling. 2 ; provide permit for gas piping and provide test prior to ceiling cover. 3 ; complete all ceiling grid requirements as per city approved plans as noted on last ceiling grid inspection.

Ceiling Grid/T-Bar Inspection Not Ready 6/12/2025 6/12/2025 06/12/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/12/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Other/Miscellaneous
Carried Forward
06/12/2025
SEE 5/20 comments 1) Cloud installations; plans provided clear details regarding the all thread and the channel around the all thread below the unistrut framing. Review with engineer all thread bracing above the unistrut to the roof deck. 2) okay to place differs and grills; inspection required 3) Complete perimeter wire main room above exit sign. See framing inspection 5/21 for beams

Other/Miscellaneous
Carried Forward
06/12/2025
1 ; complete all ceiling grid corrections from ceiling inspection dated 6-11-2025 not ready

Ceiling Grid/T-Bar Inspection Passed 6/13/2025 6/13/2025 06/13/2025
Monty Johnson ((253) 770-3326)
Gas Test Inspection Passed 6/17/2025 6/17/2025 06/17/2025
Monty Johnson ((253) 770-3326)
Mechanical Final Inspection Not Ready 6/20/2025 6/20/2025 06/21/2025
Ted Christie ((253) 507-0191)
Building Final Inspection Partial Pass 6/20/2025 6/20/2025 06/21/2025
Ted Christie ((253) 507-0191)
Mechanical Final Inspection Failed 6/24/2025 6/24/2025 06/24/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/24/2025
1 ; paint gas pipe at RTU"S on roof. 2 ; provide min. 10' from plumbing vent to air intake of RTU or extend plumbing vent 2' above air intake and brace vent to parapet of building. 3 ; provide balance report with min. OSA as required per city approved plans. 4 ; complete labeling of roof top equipment with suite number as discussed with contractor. 5 ; provide positive attachment or heat pump to roof as discussed with contractor. 6 ; provide ladder for roof top access at time of next inspection.

Building Final Inspection Failed 6/24/2025 6/24/2025 06/24/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Outstanding
07/01/2025
1 ; paint gas pipe at RTU"S on roof. 2 ; provide min. 10' from plumbing vent to air intake of RTU or extend plumbing vent 2' above air intake and brace vent to parapet of building. 3 ; provide balance report with min. OSA as required per city approved plans. 4 ; complete labeling of roof top equipment with suite number as discussed with contractor. 5 ; provide positive attachment or heat pump to roof as discussed with contractor. 6 ; provide ladder for roof top access at time of next inspection. 7 ; complete install of all ceiling tiles.

Fire Alarm Final Inspection Passed 6/23/2025 6/23/2025 06/25/2025
David Drake ((253) 864-4171)
Mechanical Final Inspection Failed 6/26/2025 6/26/2025 06/26/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/26/2025
1 ; paint gas pipe at RTU"S on roof. 2 ; provide min. 10' from plumbing vent to air intake of RTU or extend plumbing vent 2' above air intake and brace vent to parapet of building. 3 ; provide balance report with min. OSA as required per city approved plans. 4 ; complete labeling of roof top equipment with suite number as discussed with contractor. 5 ; provide positive attachment or heat pump to roof as discussed with contractor. 6 ; provide ladder for roof top access at time of next inspection.

Other/Miscellaneous
Carried Forward
06/26/2025
1 ; complete correction from last mechanical inspection. (items - 2,3,5,6,) 2 ; secure RTU'S to curb adapter as discussed with contractor.

Building Final Inspection Partial Pass 6/26/2025 6/26/2025 06/26/2025
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
06/26/2025
1 ; complete correction from last mechanical inspection. (items - 2,3,5,6,) 2 ; secure RTU'S to curb adapter as discussed with contractor. T.C.O. approved for 10 working days from 6-26-2025

Building Final Inspection Passed 7/1/2025 7/1/2025 07/01/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
07/01/2025
1 ; complete correction from last mechanical inspection. (items - 2,3,5,6,) 2 ; secure RTU'S to curb adapter as discussed with contractor. T.C.O. approved for 10 working days from 6-26-2025

Mechanical Final Inspection Passed 7/1/2025 7/1/2025 07/01/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
07/01/2025
1 ; paint gas pipe at RTU"S on roof. 2 ; provide min. 10' from plumbing vent to air intake of RTU or extend plumbing vent 2' above air intake and brace vent to parapet of building. 3 ; provide balance report with min. OSA as required per city approved plans. 4 ; complete labeling of roof top equipment with suite number as discussed with contractor. 5 ; provide positive attachment or heat pump to roof as discussed with contractor. 6 ; provide ladder for roof top access at time of next inspection.

Other/Miscellaneous
Resolved
07/01/2025
1 ; complete correction from last mechanical inspection. (items - 2,3,5,6,) 2 ; secure RTU'S to curb adapter as discussed with contractor.

Footing/Setback Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Foundation/Rebar Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Slab/Insulation Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Roof Sheathing Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Shear Wall Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Firewall/Firestop Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Energy (Insulation) Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Combination Frame And Rough In Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Hydronic Piping Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Carbon Monoxide Detectors Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Refrigeration Line Test Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Exhaust Hood Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Light Test For Grease Duct Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Exhaust/Vent Fans Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Medical Gas Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Comment Building Div Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Mechanical Rough In Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Ceiling Grid/T-Bar Inspection VOID 07/01/2025
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Outstanding
06/12/2025
1 ; provide electrical cover approval prior to ceiling grid inspection. 2 ; complete rough-in of all mechanical and install of diffusers. 3 ; provide complete set of city approved plans with all revisions for framing above suspended ceiling. (provide frame approval prior to ceiling grid approval) 4 ; complete all ceiling grid requirements as discussed with contractor. not ready .

Other/Miscellaneous
Outstanding
06/12/2025
SEE 5/20 comments 1) Cloud installations; plans provided clear details regarding the all thread and the channel around the all thread below the unistrut framing. Review with engineer all thread bracing above the unistrut to the roof deck. 2) okay to place differs and grills; inspection required 3) Complete perimeter wire main room above exit sign. See framing inspection 5/21 for beams

Other/Miscellaneous
Outstanding
06/12/2025
1 ; complete all ceiling grid corrections from ceiling inspection dated 6-11-2025 not ready

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2021 IFC and 2021 IBC • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • A separate permit may be required if fire alarm or sprinkler system is altered • RTU’S will be required to be tested for shut down with Fire Alarm • Fire extinguishers required per code to be installed at time of Fire Final • In existing buildings all required service and maintenance to be completed prior to inspection for the Fire Alarm, and Fire Sprinkler Systems. • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
Ready to Issue - Need Contractor Info Resolved Prior to Issuance
Development & Permitting Services
Must provide Contractor doing the work to be named on permit. Contractor must be registered with Washington State Labor and Industries AND have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
Ready to Issue - Need Business License Endorsement Resolved Prior to Issuance
Development & Permitting Services
Contractor needs to have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.

Related Permit & Planning Applications

Reference Number Status Type
PRMH20250755 Permit(s) Issued Mechanical - COMMERCIAL ONLY

Documents & Images

Date Uploaded File Type Name
12/11/2024 Receipt Receipt for transaction:2024-002565
01/13/2025 Plans CONSTRUCTION PLANS (Stamped)
01/13/2025 Form ENERGY CALCS (Stamped)
01/13/2025 Report STRUCT CALCS (Stamped)
01/13/2025 Form PLUMB FIXTURE WORKSHEET (Stamped)
01/28/2025 Receipt Receipt for transaction:2025-000177
01/29/2025 Permit Permit - Detailed
01/29/2025 Letter Permit Job Card
02/12/2025 Report Inspection Report (Comment Building Div Inspection)
02/19/2025 Report Inspection Report (Frame Inspection)
02/25/2025 Report Inspection Report (Slab/Insulation Inspection)
02/28/2025 Report Inspection Report (Plumbing Rough In Inspection)
03/04/2025 Report Inspection Report (Frame Inspection)
03/06/2025 Report Inspection Report (Frame Inspection)
03/17/2025 Report Inspection Report (Mechanical Rough In Inspection)
03/20/2025 Receipt Receipt for transaction:2025-000545
03/26/2025 Plans CONSTRUCTION PLAN SET, REVISED SHEETS ONLY - REV (1) (Stamped)
03/26/2025 Report STRUCTURAL CALCS - REV (1) (Stamped)
05/12/2025 Report Inspection Report (Frame Inspection)
05/12/2025 Report Inspection Report (Mechanical Rough In Inspection)
05/12/2025 Report Inspection Report (Engineering Final Inspection)
05/14/2025 Report Inspection Report (Engineering Final Inspection)
05/14/2025 Report Inspection Report (Engineering Final Inspection)
05/19/2025 Receipt Receipt for transaction:2025-000958
05/20/2025 Report LETTER FROM STRUCTURAL DESIGNER (Stamped)
05/20/2025 Report STRUCTURAL CALCS (Stamped)
05/20/2025 Plans CONSTRUCTION PLAN SET - REV (2) (Stamped)
05/20/2025 Report Inspection Report (Frame Inspection)
05/20/2025 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
05/28/2025 Report Inspection Report (Frame Inspection)
06/05/2025 Report Inspection Report (Mechanical Rough In Inspection)
06/05/2025 Report Inspection Report (Plumbing Final Inspection)
06/06/2025 Receipt Receipt for transaction:2025-001081
06/06/2025 Report Inspection Report (Frame Inspection)
06/08/2025 Report Inspection Report (Frame Inspection)
06/09/2025 Report Inspection Report (Mechanical Rough In Inspection)
06/10/2025 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
06/11/2025 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
06/12/2025 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
06/24/2025 Report Inspection Report (Mechanical Final Inspection)
06/24/2025 Report Inspection Report (Building Final Inspection)
06/26/2025 Report Inspection Report (Mechanical Final Inspection)
06/26/2025 Report Inspection Report (Building Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.