CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFA20230027


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFA20230027
Fire Alarms
Closed
MULTICARE HEALTH SYSTEM
Alteration/Remodel
Relocate & add smoke detectors, devices, speaker/strobes GSMOB 3rd FL/ WOMEN'S CLINIC TI
01/10/2023
02/07/2023
10/29/2023
05/02/2023

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
02/07/2023 revised GSMOB 3rd Fl FA (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 02/09/2023 02/07/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (Alteration) Fee $345.00 $345.00 Paid 01/10/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Piv And Tamper Inspection VOID 09/05/2023
Joyce Kennedy ((253) 841-5405)
Fire Alarm Cover Inspection VOID 09/05/2023
Joyce Kennedy ((253) 841-5405)
Fire Alarm Test Inspection VOID 09/05/2023
Joyce Kennedy ((253) 841-5405)

Conditions

Condition Status Department Category Expiration Date Due Date
New Fire Alarm System Conditions Open Standard Conditions
: • Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information. • Above ceiling detection is required. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72. • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. • Pre-test shall be conducted with a printout for inspector at time of inspection. • Labeling of all devices above and below ceiling required. • The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable. • In existing buildings all above ceiling detection is to remain. Do not remove. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

There are no related items for this development permit application.

Documents & Images

Date Uploaded File Type Name
01/10/2023 Receipt Receipt for transaction:2023-000042
02/07/2023 Form 3rd Floor Application (Flattened)
02/07/2023 Plans GSMOB 3rd Fl FA Submittals (Flattened)
02/07/2023 Permit Permit - Detailed
02/07/2023 Letter Permit Job Card
02/07/2023 Plans revised GSMOB 3rd Fl FA (Stamped)
05/02/2023 Report Inspection Report (Fire Alarm Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.