Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Alarm Final Inspection | Not Ready | 3/20/2023 | 3/20/2023 | 03/20/2023 |
David Drake ((253) 864-4171) | ||||
Fire Alarm Final Inspection | Not Ready | 3/29/2023 | 3/29/2023 | 03/29/2023 |
David Drake ((253) 864-4171) | ||||
Fire Alarm Final Inspection | Not Ready | 4/14/2023 | 4/17/2023 | 04/17/2023 |
David Drake ((253) 864-4171) | ||||
Piv And Tamper Inspection | VOID | 11/16/2023 | ||
Joyce Kennedy ((253) 841-5405) | ||||
Fire Alarm Cover Inspection | VOID | 11/16/2023 | ||
Joyce Kennedy ((253) 841-5405) |
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
New Fire Alarm System Conditions | Open | Standard Conditions | |||
:
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling.
• Provide plans and permit on site for inspection.
• Complete labor and industries inspections prior to requesting city inspection.
• If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information.
• Exterior fire bell required outside fire sprinkler room.
• Above ceiling detection is required.
• Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof.
• Total coverage is required, subject to field inspection. Comply with NFPA 72.
• Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified.
• Pre-test shall be conducted with a printout for inspector at time of inspection.
• Labeling of all devices above and below ceiling required.
• Fire sprinkler tamper valves and PIV will be required to be tested at inspection. Fire sprinkler contractor to be onsite.
• RTU’S and smoke dampeners will be required to be tested during inspection.
• The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable.
• In existing buildings all above ceiling detection is to remain. Do not remove.
• Due to unforeseeable construction design, all device locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
There are no related items for this development permit application.
Date Uploaded | File Type | Name |
---|---|---|
02/09/2023 | Plans | 7707P-88 Battery Calculations |
02/09/2023 | Receipt | Receipt for transaction:2023-000204 |
02/10/2023 | Letter | Incomplete Application Notice |
02/16/2023 | Plans | AES 7707 Data Cut Sheet (Stamped) |
02/16/2023 | Form | Multi Care Good Sam FA permit Appliation (Flattened) |
02/16/2023 | Plans | Multicare_-_Good_Samaritan_Hospital-- Dally Tower Building - SITE MAP (Stamped) |
03/14/2023 | Letter | Permit - Detailed |
03/14/2023 | Receipt | Receipt for transaction:2023-000413 |
04/17/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
04/17/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
04/17/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
06/26/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
06/26/2023 | Report | Inspection Report (Fire Alarm Test Inspection) |