CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFA20250286


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFA20250286
Fire Alarms
Permit(s) Issued
MULTICARE HEALTH SYSTEM
Alteration/Remodel
Modify existing fire alarm system for tenant improvements. Good Samaritan Hospital 401 15th Ave SE Puyallup WA 98372. Tenant improvements for Doctors Sleeping Rooms on Level 1. Install (13) new devices and (1) new NAC Panel. This is a joint venture between Johnson Controls Fire Protection (JOHNSCP831PR) and Precision Electric Group Inc (PRECIEG969PH).
02/24/2025
04/02/2025
09/29/2025

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
04/02/2025 PLAN SET (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 04/01/2025 04/01/2025

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (Alteration) Fee $230.00 $230.00 Paid 02/24/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Piv And Tamper Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Cover Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Final Inspection Pending
David Drake ((253) 864-4171)

Conditions

Condition Status Category
New Fire Alarm System Conditions Open Standard Conditions
Fire Prevention
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • Above ceiling detection is required. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72. • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. • Pre-test shall be conducted with a printout for inspector at time of inspection. • Labeling of all devices above and below ceiling required. • RTU’S and smoke dampeners will be required to be tested during inspection. RTU’S of 2000cfm or higher are required to be monitored and will require shutdown. • The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable. • In existing buildings all above ceiling detection is to remain. Do not remove. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

There are no related items for this development permit application.

Documents & Images

Date Uploaded File Type Name
02/24/2025 Other UL CERTIFICATE
02/24/2025 Receipt Receipt for transaction:2025-000385
02/25/2025 Letter Incomplete Application Notice
03/04/2025 Form APPLICATION
04/02/2025 Plans MULTICARE GOOD SAM JCI-FA SUBMITTAL -20250221 (Flattened)
04/02/2025 Plans PLAN SET (Stamped)
04/02/2025 Permit Permit - Detailed
04/02/2025 Letter Permit Job Card


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.