CITY OF PUYALLUP PERMITTING PORTAL
Development Permit Application Status
PRFS20220824
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Suppression System (other than Sprinklers) Fee | $230.00 | $230.00 | Paid | 05/17/2022 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $230.00 | $230.00 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Suppression System Test Inspection | Failed | 6/21/2022 | 6/21/2022 | 06/21/2022 |
Ray Cockerham ((253) 841-5585) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
06/21/2022
1) Test Electrical shunt
2) Seal sidewall penetration at heat shield- Per manufactures spec
3) Check into the fire alarm connection.
|
||||
Suppression System Final Inspection | Failed | 6/21/2022 | 6/21/2022 | 06/21/2022 |
Ray Cockerham ((253) 841-5585) | ||||
Corrections:
Other/Miscellaneous
Resolved
06/21/2022
See comments under test inspection
|
||||
Fire Sprinkler Cover Inspection | VOID | 6/21/2022 | 6/21/2022 | 06/21/2022 |
Ray Cockerham ((253) 841-5585) |
Condition | Status | Category |
---|---|---|
Fire Sprinkler System (New) Conditions | Open | Standard Conditions |
• Comply with 2018 IFC and IBC
• Provide plans and permit on site for inspection.
• Provide k-fire extinguishers according to IFC 904.11.5.
• Hook to fire alarm system or provide audio or visual indication of system discharge. IFC 904.3.4
• Provide manual activation in path of egress no closer than 10’ nor no more than 20’ from hood. IFC 904.11.1
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Call morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
Reference Number | Status | Type |
---|---|---|
B-21-0544 | Closed | Commercial - Tenant Improvement/Remodel |
PRFS20220161 | Permit(s) Issued | Fire Sprinklers |
PRSG20220511 | Closed | Sign/Awning |
PRMH20220512 | Permit(s) Issued | Mechanical - COMMERCIAL ONLY |
PRFS20220608 | Closed | Fire Sprinklers |
PRFA20220997 | Canceled | Fire Alarms |
Date Uploaded | File Type | Name |
---|---|---|
05/17/2022 | Receipt | Receipt for transaction:2022-000915 |
05/19/2022 | Form | Permit application0 (Flattened) |
05/19/2022 | Plans | TANDOORI_GRILL_Fire_System (Stamped) |
05/19/2022 | Plans | C_Captive Air TANK Calcs (Stamped) |
05/19/2022 | Plans | C_Captive Air TANK Cut Sheets (Stamped) |
05/19/2022 | Plans | Fire System 1 Drawing (7) (Stamped) |
05/19/2022 | Permit | Permit - Detailed |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView