CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFS20220824


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS20220824
Fire Sprinklers
Closed
New
Install Captive Aire TANK system into kitchen hood
05/17/2022
05/19/2022
02/18/2023
08/22/2022

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 06/06/2022 05/18/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Suppression System (other than Sprinklers) Fee $230.00 $230.00 Paid 05/17/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Suppression System Test Inspection Failed 6/21/2022 6/21/2022 06/21/2022
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Carried Forward
06/21/2022
1) Test Electrical shunt 2) Seal sidewall penetration at heat shield- Per manufactures spec 3) Check into the fire alarm connection.

Suppression System Final Inspection Failed 6/21/2022 6/21/2022 06/21/2022
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
06/21/2022
See comments under test inspection

Fire Sprinkler Cover Inspection VOID 6/21/2022 6/21/2022 06/21/2022
Ray Cockerham ((253) 841-5585)

Conditions

Condition Status Department Category Expiration Date Due Date
Fire Sprinkler System (New) Conditions Open Standard Conditions
: • Comply with 2018 IFC and IBC • Provide plans and permit on site for inspection. • Provide k-fire extinguishers according to IFC 904.11.5. • Hook to fire alarm system or provide audio or visual indication of system discharge. IFC 904.3.4 • Provide manual activation in path of egress no closer than 10’ nor no more than 20’ from hood. IFC 904.11.1 Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Call morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
B-21-0544 Closed Commercial - Tenant Improvement/Remodel
PRFS20220161 Permit(s) Issued Fire Sprinklers
PRSG20220511 Closed Sign/Awning
PRMH20220512 Permit(s) Issued Mechanical - COMMERCIAL ONLY
PRFS20220608 Closed Fire Sprinklers
PRFA20220997 Canceled Fire Alarms

Documents & Images

Date Uploaded File Type Name
05/17/2022 Receipt Receipt for transaction:2022-000915
05/19/2022 Plans C_Captive Air TANK Calcs (Stamped)
05/19/2022 Plans C_Captive Air TANK Cut Sheets (Stamped)
05/19/2022 Plans Fire System 1 Drawing (7) (Stamped)
05/19/2022 Permit Permit - Detailed
05/19/2022 Form Permit application0 (Flattened)
05/19/2022 Plans TANDOORI_GRILL_Fire_System (Stamped)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.