PRCTI20220811


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20220811
Commercial - Tenant Improvement/Remodel
Closed
CAFARO NORTHWEST PARTNERSHIP
Alteration/Remodel
Macy's SCOPE OF WORK CONSISTS OF INTERIOR ALTERATIONS LIMITED TO DEMOLITION OF NON-STRUCTURAL ELEMENTS, CONSTRUCTION OF NON-LOADBEARING PARTITIONS,MODIFICATIONS TO AFFECTED CEILINGS, AND INSTALLATION OF SHELVING LESS THAN 5'9" AND MILLWORK. NO CHANGE OF USE IS PROPOSED. NO CHANGES TO BUILDING ENVELOPE. BLDG ONLY - 8/24/2022 - MISCELLANEOUS REVISIONS TO PARTITIONS, CEILINGS AND FINISHES
05/13/2022
07/01/2022
04/19/2023

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 10/03/2022 10/03/2022
Fire Review Approved 10/03/2022 10/03/2022
Fire Review Approved 09/08/2022 09/14/2022
Building Review Failed 09/08/2022 09/07/2022
Building Review Approved 06/27/2022 06/28/2022
Planning Review Approved 06/27/2022 06/27/2022
Fire Review Approved 06/27/2022 06/26/2022
Engineering Traffic Review Approved 06/27/2022 06/23/2022
Engineering Review Approved 06/27/2022 06/23/2022
Building Review Failed 06/13/2022 06/13/2022
Engineering Review Approved 06/13/2022 06/09/2022
Engineering Traffic Review Approved 06/13/2022 06/09/2022
Fire Review Approved 06/13/2022 06/07/2022
Planning Review Approved 06/13/2022 06/01/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 07/01/2022
Mechanical Duct Work Fee $24.00 $24.00 Paid 07/01/2022
Building Permit Fee $5,608.75 $5,608.75 Paid 07/01/2022
Mechanical Permit Fee $40.00 $40.00 Paid 07/01/2022
Building Plan Review Fee $3,645.69 $3,645.69 Paid 05/24/2022
Mechanical Plan Review Fee $41.60 $41.60 Paid 05/24/2022
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 07/01/2022
Resubmittal Fee $130.00 $130.00 Paid 06/15/2022
Resubmittal Fee $130.00 $130.00 Paid 08/30/2022
Resubmittal Fee $130.00 $130.00 Paid 09/27/2022
Building Re-Inspection Fee $130.00 $130.00 Paid 10/14/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Frame Inspection Failed 7/27/2022 7/27/2022 07/27/2022
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
07/27/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Frame Inspection Not Ready 8/3/2022 8/3/2022 08/03/2022
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
08/03/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Frame Inspection Failed 8/15/2022 8/15/2022 08/15/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
08/15/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
08/15/2022
1:uncover columns at ext wall rocked without frame approval 2:provide electrical inspection. 3:provide fire approval for soffits prior to frame approval 4:will talk to other inspectors about wall framing covered without frame approval. 5:complete all mono coat and removal of abandoned equipment and framing.

Frame Inspection Partial Pass 8/17/2022 8/17/2022 08/17/2022
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
08/17/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
08/17/2022
1:remove rock from sw wall for insulation / foil insp 2:provide architects ok or fix on loads from new hard lids added to existing hard lids 3: ok to rock interior walls at own risk pending plan review of revisions

Frame Inspection Not Ready 8/22/2022 8/22/2022 08/22/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
08/22/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
08/22/2022
1 : inspection of of framing at exterior wall at s. e. corner only. ( complete vapor barrier at exterior wall prior to inspection ) not ready

Slab/Insulation Inspection Partial Pass 8/23/2022 8/23/2022 08/23/2022
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 8/23/2022 8/23/2022 08/23/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
08/23/2022
1. Kid section OK to tape 2.all other areas rescrew per conversation with contractor

Wallboard / Drywall Inspection Partial Pass 8/24/2022 8/24/2022 08/24/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
08/24/2022
1. Kid section OK to tape 2.all other areas rescrew per conversation with contractor

Frame Inspection Failed 9/14/2022 9/14/2022 09/14/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
09/14/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
09/14/2022
1 : inspection of of framing at exterior wall at s. e. corner only. ( complete vapor barrier at exterior wall prior to inspection ) not ready

Other/Miscellaneous
Carried Forward
09/14/2022
1. provide attachment detail for this area from the architect 2. provide electrical cover approval prior to next inspection 3.not ready

Ceiling Grid/T-Bar Inspection Not Ready 9/22/2022 9/22/2022 09/22/2022
Kevin Spruell ((253) 841-5590)
Frame Inspection Partial Pass 9/23/2022 9/23/2022 09/23/2022
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
09/23/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
09/23/2022
1 : inspection of of framing at exterior wall at s. e. corner only. ( complete vapor barrier at exterior wall prior to inspection ) not ready

Other/Miscellaneous
Carried Forward
09/23/2022
1. provide attachment detail for this area from the architect 2. provide electrical cover approval prior to next inspection 3.not ready

Ceiling Grid/T-Bar Inspection Not Ready 9/26/2022 9/26/2022 09/26/2022
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Partial Pass 9/26/2022 9/26/2022 09/26/2022
Shannon King ((253) 840-6684)
Erosion And Sediment Inspection VOID 09/29/2022
Jeff Hill ((253) 204-5633)
Cover Inspection/Thrust Blocks Inspection VOID 9/29/2022 09/29/2022
Jeff Hill ((253) 204-5633)
Ceiling Grid/T-Bar Inspection Failed 9/30/2022 9/30/2022 09/30/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
09/30/2022
1. complete all perimeter tie wires as discussed with contractor 2. complete positive connection of diffusers as discussed with contractor

Ceiling Grid/T-Bar Inspection Failed 10/3/2022 10/3/2022 10/03/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/03/2022
1. complete all perimeter tie wires as discussed with contractor 2. complete positive connection of diffusers as discussed with contractor

Other/Miscellaneous
Carried Forward
10/03/2022
1. complete all ceiling grid requirements as discussed with contractor 2. provide splice connection detail sheet at main bar at the time of next inspection

Ceiling Grid/T-Bar Inspection Not Ready 10/4/2022 10/4/2022 10/04/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/04/2022
1. complete all perimeter tie wires as discussed with contractor 2. complete positive connection of diffusers as discussed with contractor

Other/Miscellaneous
Carried Forward
10/04/2022
1. complete all ceiling grid requirements as discussed with contractor 2. provide splice connection detail sheet at main bar at the time of next inspection

Other/Miscellaneous
Carried Forward
10/04/2022
1. complete all ceiling requirements as discussed with contractor

Ceiling Grid/T-Bar Inspection Partial Pass 10/5/2022 10/5/2022 10/05/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/05/2022
1. complete all perimeter tie wires as discussed with contractor 2. complete positive connection of diffusers as discussed with contractor

Other/Miscellaneous
Carried Forward
10/05/2022
1. complete all ceiling grid requirements as discussed with contractor 2. provide splice connection detail sheet at main bar at the time of next inspection

Other/Miscellaneous
Carried Forward
10/05/2022
1. complete all ceiling requirements as discussed with contractor

Mechanical Final Inspection Not Ready 10/5/2022 10/5/2022 10/05/2022
Shannon King ((253) 840-6684)
Frame Inspection Not Ready 10/5/2022 10/5/2022 10/05/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/05/2022
1.remove flooring from under wall plates so it will bear on concrete 2.complete framing on door opening 3.complete all framing above mechanical equipment 4.complete all fasteners at studs to wall plates 5.verify that electrical J/Box in concrete are abandoned where new wall plates are placed 6. Provide architectural plans for all walls removed and demo 7. Remove all abandoned ducting, framing, electrical conduit thru out space

Other/Miscellaneous
Carried Forward
10/05/2022
1 : inspection of of framing at exterior wall at s. e. corner only. ( complete vapor barrier at exterior wall prior to inspection ) not ready

Other/Miscellaneous
Carried Forward
10/05/2022
1. provide attachment detail for this area from the architect 2. provide electrical cover approval prior to next inspection 3.not ready

Hydrostatic Test 200Lbs 2Hrs VOID 10/11/2022
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 10/11/2022
David Drake ((253) 864-4171)
Building Final Inspection Not Ready 10/11/2022 10/11/2022 10/11/2022
Shannon King ((253) 840-6684)
Fire Final Inspection Failed 10/11/2022 10/11/2022 10/11/2022
David Drake ((253) 864-4171)
Other/Miscellaneous
Carried Forward
10/11/2022
1. Fire Sprinkler system not Ready. Multiple heads installed incorrectly in tiles. Safety cap still installed. Missing trim rings. Paint on Sprinkler head. Paint on concealed sprinkler trim cap. 2. Exit Signs do not show correct Exit path. Exit paths shall be free of stocking materials. Exit Light test not completed. Isles to painted on floor per approved plans. 3. Fire extinguishers shall be installed every 75' of travel and visible from pathways. 4. Install all ceiling tiles. 5. Install all drywall to collect smoke and heat.

Mechanical Final Inspection Not Ready 10/11/2022 10/11/2022 10/11/2022
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/11/2022
1. complete duct wrap as discussed with contractor 2. provide final balance report at time of next inspection

Fire Final Inspection Failed with Fee 10/13/2022 10/13/2022 10/13/2022
David Drake ((253) 864-4171)
Other/Miscellaneous
Carried Forward
10/13/2022
1. Fire Sprinkler system not Ready. Multiple heads installed incorrectly in tiles. Safety cap still installed. Missing trim rings. Paint on Sprinkler head. Paint on concealed sprinkler trim cap. 2. Exit Signs do not show correct Exit path. Exit paths shall be free of stocking materials. Exit Light test not completed. Isles to painted on floor per approved plans. 3. Fire extinguishers shall be installed every 75' of travel and visible from pathways. 4. Install all ceiling tiles. 5. Install all drywall to collect smoke and heat.

Other/Miscellaneous
Carried Forward
10/13/2022
Pay 130$ reinspection fee prior to next inspection. Not Ready

Comment Engineering Div Inspection VOID 10/14/2022
Jeff Hill ((253) 204-5633)
Fire Final Inspection Partial Pass 10/18/2022 10/18/2022 10/18/2022
David Drake ((253) 864-4171)
Other/Miscellaneous
Resolved
10/18/2022
1. Fire Sprinkler system not Ready. Multiple heads installed incorrectly in tiles. Safety cap still installed. Missing trim rings. Paint on Sprinkler head. Paint on concealed sprinkler trim cap. 2. Exit Signs do not show correct Exit path. Exit paths shall be free of stocking materials. Exit Light test not completed. Isles to painted on floor per approved plans. 3. Fire extinguishers shall be installed every 75' of travel and visible from pathways. 4. Install all ceiling tiles. 5. Install all drywall to collect smoke and heat.

Other/Miscellaneous
Resolved
10/18/2022
Pay 130$ reinspection fee prior to next inspection. Not Ready

Comment Building Div Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Footing/Setback Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Foundation/Rebar Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Underfloor Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Block Wall Rebar Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Shear Wall Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Firewall/Firestop Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Energy (Insulation) Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Re-Roof Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Refrigeration Line Test Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Exhaust/Vent Fans Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Fire Or Smoke Damper Inspection VOID 10/11/2022 10/21/2022
Kevin Spruell ((253) 841-5590)
Engineering Final Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Planning Final Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Slab/Insulation Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)
Building Final Inspection VOID 10/13/2022 10/21/2022
Kevin Spruell ((253) 841-5590)
Mechanical Final Inspection VOID 10/13/2022 10/21/2022
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Outstanding
10/11/2022
1. complete duct wrap as discussed with contractor 2. provide final balance report at time of next inspection

Fire Final Inspection VOID 10/21/2022
Kevin Spruell ((253) 841-5590)

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
: Fire Alarm Conditions The system will only be considered existing provided, the original panel remains in same location, the original panel is not rewired, and if the original panel can be replaced like for like if required. If there is an existing Remote annunciator on the exterior of the building, it is required to be moved inside the vestibule. The Fire Alarm System is required to be monitored throughout construction. The System can be put into test for up to 8hrs a day. Anything longer than 8hrs will require Fire Code Officials approval and result in Fire Watch. RTU’S will be required to be tested for shut down with fire alarm. All maintenance and inspections are required to be completed prior to any inspections. L&I Final required prior to Fire Final. Fire Sprinkler Conditions The Fire Sprinkler System is required to be functional and monitored throughout construction. The System can be put into test for up to 8hrs a day. Anything longer than 8hrs will require Fire Code Officials approval and result in Fire Watch. All maintenance and inspections are required to be completed prior to any inspections. All tampers will be tested at Fire Sprinkler Final. Building Conditions Comply with 2018 IFC and 2018 IBC. Separate permits required for fire alarm and fire sprinkler systems. Exit lighting test required contractor to provide light meter. Fire extinguishers required per code. A Knox box is required at the front entry on the exterior of the building. PIV must have a Knox lock or approved lock with an extra key provided in Knox box. All above items to be completed prior to fire final. Fire final required before building final. All FACP and Riser Room signs are required to be installed and legible. Replace if necessary. All Fire Lane No Parking signs shall be updated or replaced as needed. Fire Lane stripping shall be updated as needed. Address required Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Miscellaneous Condition Open Development & Permitting Services
:

Related Permit & Planning Applications

Reference Number Status Type
PRFS20221262 Closed Fire Sprinklers

Documents & Images

Date Uploaded File Type Name
06/13/2022 Other Macys Puyallup - Project Manual1 (Flattened)
06/13/2022 Other Macys Puyallup - WATER AVAILABILITY1 (Flattened)
06/29/2022 Plans Macys Puyallup - PERMIT_r1_combined - 2021-06-17 (Stamped)
06/13/2022 Form Macys Puyallup - Building Permit App1 (Flattened)
06/13/2022 Form Macys Puyallup - Cafaro 62-985 Prlim Interior Review Ltr1 (Flattened)
05/24/2022 Receipt Receipt for transaction:2022-000956
06/13/2022 Letter Permit Review Comment Notice
06/15/2022 Receipt Receipt for transaction:2022-001123
06/29/2022 Other PRCTI20220811 - Revisions to Existing Residential or Commercial Applications0 (Flattened)
06/29/2022 Other ltr_PRCTI20220811_response - 2022-06-18 (Flattened)
07/01/2022 Letter Permit - Detailed
07/01/2022 Receipt Receipt for transaction:2022-001248
07/05/2022 Letter Permit Job Card
07/27/2022 Report Inspection Report (Frame Inspection)
08/03/2022 Report Inspection Report (Frame Inspection)
08/22/2022 Report Inspection Report (Frame Inspection)
08/23/2022 Report Inspection Report (Slab/Insulation Inspection)
08/23/2022 Report Inspection Report (Wallboard / Drywall Inspection)
10/05/2022 Plans Macys Puyallup - plan_rev_combined - 2021-09-21_flat2 (Stamped)
08/24/2022 Report Inspection Report (Wallboard / Drywall Inspection)
08/30/2022 Receipt Receipt for transaction:2022-001696
09/14/2022 Report Inspection Report (Frame Inspection)
09/16/2022 Letter Permit Review Comment Notice
09/22/2022 Other ltr_PRCTI20220811_response - 2022-09-21
09/22/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
09/23/2022 Report Inspection Report (Frame Inspection)
09/26/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
09/26/2022 Report Inspection Report (Wallboard / Drywall Inspection)
09/27/2022 Receipt Receipt for transaction:2022-001908
09/30/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
10/03/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
10/04/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
10/05/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
10/05/2022 Report Inspection Report (Mechanical Final Inspection)
10/05/2022 Report Inspection Report (Frame Inspection)
10/11/2022 Report Inspection Report (Frame Inspection)
10/11/2022 Report Inspection Report (Building Final Inspection)
10/11/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
10/11/2022 Report Inspection Report (Mechanical Final Inspection)
10/12/2022 Report Inspection Report (Wallboard / Drywall Inspection)
10/14/2022 Receipt Receipt for transaction:2022-002057
10/21/2022 Report Inspection Report (Building Final Inspection)