CITY OF PUYALLUP PERMITTING PORTAL
Development Permit Application Status
PRFS20221262
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Automatic Fire Sprinkler System Alteration Fee | $345.00 | $345.00 | Paid | 08/17/2022 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $345.00 | $345.00 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Sprinkler Cover Inspection | Partial Pass | 9/13/2022 | 9/13/2022 | 09/13/2022 |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Cover Inspection | Not Ready | 10/3/2022 | 10/3/2022 | 10/03/2022 |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Dry System Trip Test | VOID | 10/11/2022 | ||
David Drake ((253) 864-4171) | ||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 10/11/2022 | ||
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Final Inspection | Failed | 10/11/2022 | 10/11/2022 | |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler
Carried Forward
10/11/2022
1. Fire Sprinklers installed incorrectly in ceiling tiles.
2. Safety cap still installed by escalator.
3. Missing trims by escalator.
4. Painted sprinkler head by escalator.
5. Painted concealed sprinkler head by escalator.
6. Sprinkler head in drywall ceiling SW corner of building by roof top door pushed up.
7. Rewalk project for trim rings that are installed incorrectly.
8. GC will point out the issues to be fixed.
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Fire Sprinkler System (New) Conditions | Open | Standard Conditions | |||
:
1- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION.
2- COVER AND FINAL INSPECTIONS ARE REQUIRED.
3- FIRE WATCH IS REQUIRED WHEN SPRINKLER SYSTEM IS OUT OF SERVICE IN EXSISTING BUILDINGS.
4- CONTRACTOR REQUIRED AT ALL INSPECTIONS.
5- HYDRO TEST WILL BE REQUIRED ON ALL NEW AND EXISTING BUILDINGS. APPOINTMENT REQUIRED.
6- HYDRO TEST, TWO INSPECTIONS WILL BE REQUIRED 2HRS APART. CALL TO SCHEDULE TIMES.
7- FIRE PUMPS WILL BE REQUIRED TO BE TESTED AND WITNESSED BY INSPECTOR.
CONTRACTOR MUST BE PRESENT AT INSPECTIONS.
Note: Separate areas with no above ceiling fire protection from areas with upright. Must be able to collect heat; Separation is subject to architect of records design. Fire Prevention
|
Reference Number | Status | Type |
---|---|---|
PRCTI20220811 | Closed | Commercial - Tenant Improvement/Remodel |
Date Uploaded | File Type | Name |
---|---|---|
03/06/2023 | Letter | Permit Expiration Notice |
08/16/2022 | Letter | Incomplete Application Notice |
08/17/2022 | Receipt | Receipt for transaction:2022-001612 |
08/23/2022 | Form | Application-Comm FIre Sprinker_Macy's TI_08172022_v2 (Flattened) |
08/23/2022 | Plans | MaterialDataSheets_FireSprinklerTI_Macy'sTI_2ndFlr_08152022_v3 (Flattened) |
08/23/2022 | Permit | Permit - Detailed |
08/23/2022 | Plans | Plans_FireSprinklerTI_Macy'sTI_2ndFlr_08152022_v1 (Stamped) |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.