CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFS20221262


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS20221262
Fire Sprinklers
Closed
CAFARO NORTHWEST PARTNERSHIP
Alteration/Remodel
Modify existing wet pipe sprinkler system to accommodate for new walls and ceilings. No change to hydraulic calculations. (BLDG PRCTI20220811)
08/16/2022
08/23/2022
01/22/2024
07/26/2023

Locations

Property
6021590070

Property
6021590070

Address
3500 S MERIDIAN, Unit: 985, PUYALLUP, WA 98373

3500 S Meridian St, 2nd Flr Area A, Puyallup WA 98373

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 09/07/2022 08/22/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Automatic Fire Sprinkler System Alteration Fee $345.00 $345.00 Paid 08/17/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Sprinkler Cover Inspection Partial Pass 9/13/2022 9/13/2022 09/13/2022
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Not Ready 10/3/2022 10/3/2022 10/03/2022
David Drake ((253) 864-4171)
Fire Sprinkler Dry System Trip Test VOID 10/11/2022
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 10/11/2022
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Failed 10/11/2022 10/11/2022
David Drake ((253) 864-4171)
Fire Sprinkler
Carried Forward
10/11/2022
1. Fire Sprinklers installed incorrectly in ceiling tiles. 2. Safety cap still installed by escalator. 3. Missing trims by escalator. 4. Painted sprinkler head by escalator. 5. Painted concealed sprinkler head by escalator. 6. Sprinkler head in drywall ceiling SW corner of building by roof top door pushed up. 7. Rewalk project for trim rings that are installed incorrectly. 8. GC will point out the issues to be fixed.

Conditions

Condition Status Department Category Expiration Date Due Date
Fire Sprinkler System (New) Conditions Open Standard Conditions
: 1- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION. 2- COVER AND FINAL INSPECTIONS ARE REQUIRED. 3- FIRE WATCH IS REQUIRED WHEN SPRINKLER SYSTEM IS OUT OF SERVICE IN EXSISTING BUILDINGS. 4- CONTRACTOR REQUIRED AT ALL INSPECTIONS. 5- HYDRO TEST WILL BE REQUIRED ON ALL NEW AND EXISTING BUILDINGS. APPOINTMENT REQUIRED. 6- HYDRO TEST, TWO INSPECTIONS WILL BE REQUIRED 2HRS APART. CALL TO SCHEDULE TIMES. 7- FIRE PUMPS WILL BE REQUIRED TO BE TESTED AND WITNESSED BY INSPECTOR. CONTRACTOR MUST BE PRESENT AT INSPECTIONS. Note: Separate areas with no above ceiling fire protection from areas with upright. Must be able to collect heat; Separation is subject to architect of records design. Fire Prevention

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20220811 Closed Commercial - Tenant Improvement/Remodel

Documents & Images


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.