CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20221400


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20221400
Commercial - Tenant Improvement/Remodel
Closed
LMC PUYALLUP LLC
Alteration/Remodel
H & R BLOCK: Interior TI: includes demo of interior partitions/doors, relocation of select ceiling fixtures; To include new interior partitions/doors, and outlets: Adding a second restroom. (1 Men's and 1.Women's both accessible)
09/13/2022
12/05/2022
07/12/2023
12/30/2023

Locations

Property
0419106015

Address
4227 S MERIDIAN, Unit: C, PUYALLUP, WA 98373

4227
South Meridian , Puyallup WA 89373

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 11/20/2022 11/16/2022
Building Review Approved 11/20/2022 11/16/2022
Planning Review Approved 11/20/2022 11/16/2022
Engineering Review Approved 11/20/2022 11/14/2022
Building Review Failed 11/12/2022 11/08/2022
Fire Review Approved 11/12/2022 11/03/2022
Engineering Review Approved 11/12/2022 11/03/2022
Planning Review Approved 11/12/2022 11/02/2022
Fire Review Approved 10/16/2022 10/17/2022
Building Review Failed 10/16/2022 10/12/2022
Planning Review Approved 10/16/2022 09/28/2022
Planning Review Approved 10/16/2022 09/28/2022
Engineering Review Approved 10/16/2022 09/28/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 11/17/2022
Building Permit Fee $593.25 $593.25 Paid 11/17/2022
Building Plan Review Fee $385.61 $385.61 Paid 09/26/2022
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 11/17/2022
Exhaust Vent Fan (Bath) Fee $14.10 $14.10 Paid 11/17/2022
Mechanical Permit Fee $40.00 $40.00 Paid 11/17/2022
Plumbing Fixtures Fee $26.00 $26.00 Paid 11/17/2022
Plumbing Permit Fee $40.00 $40.00 Paid 11/17/2022
Mechanical Plan Review Fee $35.17 $35.17 Paid 09/26/2022
Plumbing Plan Review Fee $42.90 $42.90 Paid 09/26/2022
Sewer System Development ChargeFee - Tenant Improvment/Addition $2,367.78 $2,367.78 Paid 11/17/2022
Resubmittal Fee $130.00 $130.00 Paid 11/01/2022
Resubmittal Fee $130.00 $130.00 Paid 11/10/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Frame Inspection Not Ready 12/6/2022 12/6/2022 12/06/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/06/2022
1 ; complete all rough -in of plumbing ,mechanical, and electrical cover approval prior to frame inspection, not ready

Plumbing Rough In Inspection Failed 12/8/2022 12/8/2022 12/08/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/08/2022
1. provide test on supply as discussed with contractor 2.provide test on DWV as discussed with contractor

Combination Frame And Rough In Inspection Failed 12/8/2022 12/8/2022 12/08/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
12/08/2022
1 ; remove screws from top track to ceiling grid as discussed with contractor. 2 ; seal penetration in top plates at wood construction at plumbing penetrations.

Plumbing Rough In Inspection Partial Pass 12/9/2022 12/9/2022 12/09/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
12/09/2022
1. provide test on supply as discussed with contractor 2.provide test on DWV as discussed with contractor

Other/Miscellaneous
Carried Forward
12/09/2022
1 ; completer plumbing vent to exterior of building prior to ceiling cover inspection. 2 ; approved below slab and in wall at restroom.

Foundation/Rebar Inspection Partial Pass 12/12/2022 12/12/2022 12/12/2022
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 12/12/2022 12/12/2022 12/12/2022
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
12/12/2022
1 ; complete all rough -in of plumbing ,mechanical, and electrical cover approval prior to frame inspection, not ready

Other/Miscellaneous
Carried Forward
12/12/2022
1 ; complete plumbing vent to exterior of building prior to ceiling cover inspection. ( d.w.v. tested above wall with 10' head test)

Wallboard / Drywall Inspection Passed 12/16/2022 12/16/2022 12/16/2022
Kevin Spruell ((253) 841-5590)
Ceiling Grid/T-Bar Inspection Not Ready 12/20/2022 12/20/2022 12/20/2022
Shannon King ((253) 840-6684)
Exhaust Hood Inspection Passed 12/29/2022 12/29/2022 12/29/2022
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
12/29/2022
fart fans ok

Ceiling Grid/T-Bar Inspection Failed 12/29/2022 12/29/2022 12/29/2022
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/29/2022
complete rivets, complete pods

Exhaust/Vent Fans Inspection Passed 12/30/2022 12/30/2022 12/30/2022
Monty Johnson ((253) 770-3326)
Plumbing Final Inspection Not Ready 12/30/2022 12/30/2022 12/30/2022
Monty Johnson ((253) 770-3326)
Mechanical Final Inspection Not Ready 12/30/2022 12/30/2022 12/30/2022
Monty Johnson ((253) 770-3326)
Ceiling Grid/T-Bar Inspection Passed 12/30/2022 12/30/2022 12/30/2022
Monty Johnson ((253) 770-3326)
Planning Final Inspection VOID 1/3/2023 01/03/2023
Chris Beale ((253) 841-5418)
Building Final Inspection Passed 1/5/2023 1/5/2023 01/05/2023
Monty Johnson ((253) 770-3326)
Fire Final Inspection Passed 1/5/2023 1/5/2023 01/05/2023
David Drake ((253) 864-4171)
Exit Lighting Test Inspection Passed 1/5/2023 01/05/2023
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 1/5/2023 01/05/2023
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 01/05/2023
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 01/05/2023
David Drake ((253) 864-4171)
Comment Engineering Div Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Slab/Insulation Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Roof Sheathing Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Shear Wall Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Firewall/Firestop Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Energy (Insulation) Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Hydronic Piping Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Refrigeration Line Test Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Light Test For Grease Duct Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Medical Gas Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Cover Inspection/Thrust Blocks Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Engineering Final Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Combination Frame And Rough In Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
12/08/2022
1 ; remove screws from top track to ceiling grid as discussed with contractor. 2 ; seal penetration in top plates at wood construction at plumbing penetrations.

Plumbing Rough In Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
12/09/2022
1 ; completer plumbing vent to exterior of building prior to ceiling cover inspection. 2 ; approved below slab and in wall at restroom.

Foundation/Rebar Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Frame Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
12/12/2022
1 ; complete plumbing vent to exterior of building prior to ceiling cover inspection. ( d.w.v. tested above wall with 10' head test)

Comment Building Div Inspection VOID 01/05/2023
Monty Johnson ((253) 770-3326)

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2018 IFC and 2018 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required contractor to provide light meter • A separate permit may be required if fire alarm or sprinkler system is altered • RTU’S will be required to be tested for shut down. • Fire extinguishers required per code • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Engineering Commercial Standard Conditions Open Standard Conditions
Development & Permitting Services
Development Engineering standard commercial conditions: ** If a sewer sampling tee is not currently installed at this site the installation of one will be required prior to occupancy . - A separate utility permit must be obtained prior to the installation of a sewer sampling tee ** - A commercial development must have installed a side sewer sampling tee installed in conformance to city standard section 04.03 – side sewer. - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Side Sewer Sample Tee Open Prior to Occupancy
Engineering Division
A side sewer sampling connection is required to be installed on the commercial sanitary side sewer service in accordance with City policy ENG 21-03.  If a sewer sampling tee is not currently installed at this site the installation of one will be required prior to occupancy. See sewer sampling connection City Standard Detail 04.03.04, attached in CityView.
Miscellaneous Condition Resolved Prior to Issuance
Development & Permitting Services
PROVIDE CONTRACTOR INFORMATION AND VERIFY BUSINESS LICENSE PRIOR TO ISSUANCE -EM REC'D 12.5.22, RESOLVED CONDITION AND ISSUED PERMIT. ~ JJ

Related Permit & Planning Applications

Reference Number Status Type
PRSG20221797 Closed Sign/Awning

Documents & Images

Date Uploaded File Type Name
09/26/2022 Form Fruitland Water Availability
09/26/2022 Receipt Receipt for transaction:2022-001897
09/28/2022 Plans Sewer Sampling Tee 04.03.04
10/17/2022 Form Plumbing fixture worksheet_Puyallup2 (Flattened)
11/01/2022 Receipt Receipt for transaction:2022-002183
11/10/2022 Receipt Receipt for transaction:2022-002245
11/16/2022 Plans Construction Plan Set (Stamped)
11/17/2022 Receipt Receipt for transaction:2022-002295
12/05/2022 Letter Permit Job Card
12/05/2022 Permit Permit - Detailed
12/06/2022 Report Inspection Report (Frame Inspection)
12/08/2022 Report Inspection Report (Plumbing Rough In Inspection)
12/08/2022 Report Inspection Report (Combination Frame And Rough In Inspection)
12/09/2022 Report Inspection Report (Plumbing Rough In Inspection)
12/12/2022 Report Inspection Report (Frame Inspection)
12/12/2022 Report Inspection Report (Foundation/Rebar Inspection)
12/16/2022 Report Inspection Report (Wallboard / Drywall Inspection)
12/20/2022 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
01/05/2023 Report Inspection Report (Building Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.