CITY OF PUYALLUP PERMITTING PORTAL
Development Permit Application Status
PRFA20220621
| Paid Fees | Amount | Paid | Owing | Date Paid |
|---|---|---|---|---|
| Fire Alarm Systems (Alteration) Fee | $345.00 | $345.00 | Paid | 04/07/2022 |
| Resubmittal/Revision Fee | $130.00 | $130.00 | Paid | 04/28/2022 |
| Resubmittal/Revision Fee | $130.00 | $130.00 | Paid | 08/30/2022 |
| Outstanding Fees | Amount | Paid | Owing | Date Paid |
| No outstanding fees. | ||||
| Totals: | $605.00 | $605.00 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
| Inspection | Outcome | Requested | Scheduled | Date Inspected |
|---|---|---|---|---|
| Piv And Tamper Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Fire Alarm Test Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Fire Alarm Cover Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
|
Corrections:
Other/Miscellaneous
Outstanding
07/27/2022
1) Review location of smoke detection above ceiling; detectors are currently located at the base of the deep web truss, many locations. NFPA 72 17.7.3.2.4.2 Provide insulation level, calculations or relocate to appropriate distance from the roof.
2) Total coverage NFPA 72 17.5.3.1 ; Add devices at the ceiling in the vacant space, Others as applicable. See note below regarding the enclosed stair at the west.
NFPA 72 2016 Explanatory excerpt "Revised 17.5.3.1 to eliminate reference to closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes; expanded the associated annex to address general consideration for shafts with regard to the “total coverage” detection approach. These types of spaces are unique for different buildings and are subject to special detection requirements — they should not be subject to requirements for total coverage."
3) Remote annunciator; Location may have been decided; unable to locate on the plans. Need to coordinate with Knox box location. Need follow-up on this issue
|
||||
| Fire Alarm Final Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
|
Corrections:
Other/Miscellaneous
Outstanding
12/28/2022
1) fire alarm complete; less elevator recall -
2) Second floor complete for shell only.
3) Post annunciator map near remote annunciator legible scale
4) Approved for stocking furniture; verified with building inspector today
NOTE: HVAC 606.2.1 Return air systems. exception 2 - provided by the GC.
|
||||
| Fire Alarm Cover Inspection | Failed | 7/27/2022 | 7/27/2022 | 07/27/2022 |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Other/Miscellaneous
Outstanding
07/27/2022
1) Review location of smoke detection above ceiling; detectors are currently located at the base of the deep web truss, many locations. NFPA 72 17.7.3.2.4.2 Provide insulation level, calculations or relocate to appropriate distance from the roof.
2) Total coverage NFPA 72 17.5.3.1 ; Add devices at the ceiling in the vacant space, Others as applicable. See note below regarding the enclosed stair at the west.
NFPA 72 2016 Explanatory excerpt "Revised 17.5.3.1 to eliminate reference to closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes; expanded the associated annex to address general consideration for shafts with regard to the “total coverage” detection approach. These types of spaces are unique for different buildings and are subject to special detection requirements — they should not be subject to requirements for total coverage."
3) Remote annunciator; Location may have been decided; unable to locate on the plans. Need to coordinate with Knox box location. Need follow-up on this issue
4) Electrical was scheduled for today; not complete at time of inspection.
5) Approved plans not available on site for inspection; please provide approved plans on site.
|
||||
| Fire Alarm Final Inspection | Not Ready | 12/20/2022 | 12/22/2022 | 12/22/2022 |
| David Drake ((253) 864-4171) | ||||
|
Corrections:
Fire Alarm
Carried Forward
12/27/2022
1. Complete permit conditions prior to next inspection.
2. Above ceiling smoke detection required above bathrooms.
3. Move smoke detector in mechanical room to top of joist.
4. Not ready
|
||||
| Fire Alarm Final Inspection | Partial Pass | 12/27/2022 | 12/27/2022 | |
| Ray Cockerham ((253) 841-5585) | ||||
|
Corrections:
Fire Alarm
Resolved
12/27/2022
1. Complete permit conditions prior to next inspection.
2. Above ceiling smoke detection required above bathrooms.
3. Move smoke detector in mechanical room to top of joist.
4. Not ready
|
||||
|
Other/Miscellaneous
Carried Forward
12/28/2022
1) fire alarm complete; less elevator recall -
2) Second floor complete for shell only.
3) Post annunciator map near remote annunciator legible scale
4) Approved for stocking furniture; verified with building inspector today
NOTE: HVAC 606.2.1 Return air systems. exception 2 - provided by the GC.
|
||||
| Condition | Status | Category |
|---|---|---|
| New Fire Alarm System Conditions | Open | Standard Conditions |
|
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. Inspections are Monday - Thursday, no friday inspections
• Provide plans and permit on site for inspection.
• Complete labor and industries inspections prior to requesting city inspection.
• A remote annunciator located at the main entrance is required. If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information.
• Exterior fire bell required outside fire sprinkler room.
• Above ceiling detection is required.
• Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof.
• Total coverage is required, subject to field inspection. Comply with NFPA 72, 2016
• Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified.
• A pre-test shall be conducted and a printout of the location of the device, point number and descriptor shall be furnished to the inspector at final. Labeling of all devices above and below ceiling required.
• Fire sprinkler tamper valves and PIV will be required to be tested at inspection. Fire sprinkler contractor to be onsite.
• RTU’S and smoke dampeners will be required to be tested during inspection.
• The city of puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable.
• In existing buildings all above ceiling detection is to remain. Do not remove.
• Due to unforeseeable construction design, all device locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
||
| Date Uploaded | File Type | Name |
|---|---|---|
| 04/07/2022 | Receipt | Receipt for transaction:2022-000648 |
| 04/07/2022 | Letter | Incomplete Application Notice |
| 04/22/2022 | Letter | Permit Review Comment Notice |
| 04/22/2022 | Form | permit app0 (Flattened) |
| 04/28/2022 | Receipt | Receipt for transaction:2022-000786 |
| 04/28/2022 | Letter | Incomplete Application Notice |
| 05/12/2022 | Form | RESUBMITTAL FORM0 (Flattened) |
| 05/12/2022 | Form | Permit Review RESUBMITTAL0 (Flattened) |
| 05/12/2022 | Plans | FIRE ALARM SUBMITTALS (Stamped) |
| 05/12/2022 | Permit | Permit - Detailed |
| 05/12/2022 | Plans | CASCADE CHRISTIAN JR HIGH - FIRE - PHASE 2 & 3 - COMBINED SET - 2022-04-27 (Stamped) |
| 08/29/2022 | Plans | FIRE ALARM SUBMTTALS0 (Flattened) |
| 08/29/2022 | Form | REVISIONS FORM0 (Flattened) |
| 08/30/2022 | Receipt | Receipt for transaction:2022-001705 |
| 08/30/2022 | Plans | CASCADE CHRISTIAN JR HIGH - FIRE - COMBINED - 08-16-2022 (Flattened) (Stamped) |
| 05/11/2023 | Letter | Permit Expiration Notice |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.