Summary

PRFA20221409
Fire Alarms
Closed
AMB INSTITUTIONAL ALLIANCE FUND III LP
Alteration/Remodel
Remove beam detectors in Suite 103 Replace with 137 spot-type smoke detectors Install dedicated function fire alarm panel and interconnect with building system
09/14/2022
09/30/2022
10/18/2023
04/21/2023

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
09/30/2022 FA_Cut Sheets (Stamped)
09/30/2022 FA_Plans_Stamped (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 09/30/2022 09/29/2022
Fire Review Failed 10/06/2022 09/19/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (Alteration) Fee $230.00 $230.00 Paid 09/14/2022
Fire Alarm Systems (New) Fee $517.50 $517.50 Paid 09/14/2022
Resubmittal Fee $130.00 $130.00 Paid 09/20/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Piv And Tamper Inspection VOID 02/27/2023
David Drake ((253) 864-4171)
Fire Alarm Cover Inspection VOID 02/27/2023
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Failed 02/27/2023
David Drake ((253) 864-4171)
Corrections:


Fire Alarm
Carried Forward
02/27/2023
1. With all the pallets that have been moved into the warehouse causing inspection issues and timing, Patriot Fire will need to a 100% smoke test on all new devices installed. 2. Provide a central station report showing that all devices have been tested after todays date. Point number and description are required. 3. The FACP currently has troubles that will need to be addressed prior to receiving a final. 4. When items 1-3 are complete, a percentage will be tested in the field.

Fire Alarm Final Inspection Not Ready 2/27/2023 2/28/2023 02/28/2023
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Passed 04/21/2023
David Drake ((253) 864-4171)
Corrections:


Fire Alarm
Outstanding
02/27/2023
1. With all the pallets that have been moved into the warehouse causing inspection issues and timing, Patriot Fire will need to a 100% smoke test on all new devices installed. 2. Provide a central station report showing that all devices have been tested after todays date. Point number and description are required. 3. The FACP currently has troubles that will need to be addressed prior to receiving a final. 4. When items 1-3 are complete, a percentage will be tested in the field.

Fire Alarm Final Inspection Passed 04/21/2023
David Drake ((253) 864-4171)

Conditions

Condition Status Category
New Fire Alarm System Conditions Open Standard Conditions
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. Inspections are Monday - Thursday, no friday inspections • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • A remote annunciator located at the main entrance is required. If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information. • Exterior fire bell required outside fire sprinkler room. • Above ceiling detection is required. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72, 2016 • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. • A pre-test shall be conducted and a printout of the location of the device, point number and descriptor shall be furnished to the inspector at final. Labeling of all devices above and below ceiling required. • The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable. • In existing buildings all above ceiling detection is to remain. Do not remove. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20221019 Closed Commercial - Tenant Improvement/Remodel
PRCTI20230908 Closed Commercial - Tenant Improvement/Remodel

Documents & Images

Date Uploaded File Type Name
09/14/2022 Receipt Receipt for transaction:2022-001803
09/20/2022 Letter Permit Review Comment Notice
09/20/2022 Form FA_Application1 (Flattened)
09/20/2022 Receipt Receipt for transaction:2022-001857
09/30/2022 Plans FA_Plans_Stamped11 (Flattened)
09/30/2022 Plans FA_Plans_Stamped12 (Flattened)
09/30/2022 Form FA_Resubmit App0 (Flattened)
09/30/2022 Plans FA_Cut Sheets (Stamped)
09/30/2022 Plans FA_Plans_Stamped (Stamped)
09/30/2022 Permit Permit - Detailed
02/13/2023 Letter Permit Expiration Notice
04/21/2023 Report Inspection Report (Fire Alarm Final Inspection)