CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCTI20221019
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 07/20/2023 |
Building Permit Fee | $2,040.95 | $2,040.95 | Paid | 07/20/2023 |
Building Plan Review Fee | $1,326.62 | $1,326.62 | Paid | 06/28/2022 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 07/20/2023 |
Sewer System Development ChargeFee - Tenant Improvment/Addition | $10,201.20 | $10,201.20 | Paid | 07/20/2023 |
Water System Development ChargeFee - Tenant Improvment/Addition | $6,292.98 | $6,292.98 | Paid | 07/20/2023 |
Resubmittal Fee | $180.00 | $180.00 | Paid | 04/12/2023 |
Resubmittal Fee | $180.00 | $180.00 | Paid | 05/02/2023 |
Furnace (up to 100,000 BTU) Fee | $19.55 | $19.55 | Paid | 07/20/2023 |
Gas Piping (Mechanical) Fee | $6.30 | $6.30 | Paid | 07/20/2023 |
AC Unit Fee | $19.55 | $19.55 | Paid | 07/20/2023 |
Mechanical Duct Work Fee | $24.00 | $24.00 | Paid | 07/20/2023 |
Unclassified Appliance or Equipment Fee | $14.10 | $14.10 | Paid | 07/20/2023 |
Mechanical Permit Fee | $40.00 | $40.00 | Paid | 07/20/2023 |
Drinking Fountain, Water Cooler, Ice Machine Fee | $40.25 | $40.25 | Paid | 07/20/2023 |
Plumbing Permit Fee | $40.00 | $40.00 | Paid | 07/20/2023 |
Plumbing Fixtures Fee | $234.00 | $234.00 | Paid | 07/20/2023 |
Water Heater Fee | $13.00 | $13.00 | Paid | 07/20/2023 |
Mechanical Plan Review Fee | $80.28 | $80.28 | Paid | 07/20/2023 |
Plumbing Plan Review Fee | $212.71 | $212.71 | Paid | 07/20/2023 |
Building Inspection Fee | $180.00 | $180.00 | Paid | 02/28/2024 |
Building Re-Inspection Fee | $180.00 | $180.00 | Paid | 02/28/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $21,615.49 | $21,615.49 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Plumbing Rough In Inspection | Partial Pass | 8/8/2023 | 8/8/2023 | 08/08/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
08/08/2023
1. provide as-built from engineer of record for changes made on city approved plans for pipe sizes
2. plumbing test approved pending as-built approval (below slab)
|
||||
Foundation/Rebar Inspection | Passed w/ Conditions | 8/14/2023 | 8/14/2023 | 08/14/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Outstanding
08/14/2023
1. provide engineers as-built approval for all under slab plumbing
|
||||
Energy (Insulation) Inspection | Failed | 9/1/2023 | 9/1/2023 | 09/01/2023 |
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/01/2023
arrived on site 9:22 am talked to framer, he said no super on site and to check other building, unable to locate super .
|
||||
Energy (Insulation) Inspection | Not Ready | 9/5/2023 | 9/5/2023 | 09/05/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/05/2023
1. complete insulation as discussed with contractor
|
||||
Plumbing Rough In Inspection | Partial Pass | 9/15/2023 | 9/15/2023 | 09/15/2023 |
Shannon King ((253) 840-6684) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/15/2023
1. provide as-built from engineer of record for changes made on city approved plans for pipe sizes
2. plumbing test approved pending as-built approval (below slab)
|
||||
Frame Inspection | Not Ready | 9/18/2023 | 9/18/2023 | 09/19/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/19/2023
1.provide electrical cover approval at time of next inspection
2.not ready
|
||||
Frame Inspection | Not Ready | 9/26/2023 | 9/26/2023 | 09/26/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/26/2023
1.provide electrical cover approval at time of next inspection
2.not ready
|
||||
Other/Miscellaneous
Carried Forward
09/26/2023
1. cancelled by contractor
|
||||
Frame Inspection | Partial Pass | 9/27/2023 | 9/27/2023 | 09/27/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
09/27/2023
1. no framing, MECH, plumbing, electrical was installed at I/T room and janitors closet at time of inspection
2. provide clarification of bracing at 32" on center on demising wall on detail 16 A2.1 on city approved plans
3. ok to insulate
|
||||
Energy (Insulation) Inspection | Partial Pass | 10/5/2023 | 10/5/2023 | 10/05/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
10/05/2023
1. complete insulation as discussed with contractor
|
||||
Other/Miscellaneous
Carried Forward
10/05/2023
1. no hard lids in bathrooms
2.clarify insulation over bathrooms
3.no demising wall need clarification on blocking in wall as discussed with contractor
4.all other interior and exterior walls ok to cover
|
||||
Combination Frame And Rough In Inspection | Partial Pass | 10/5/2023 | 10/5/2023 | 10/05/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
10/05/2023
1.framing at roof modification for MECH approved
2.fasteners at curb to roof on roof for RTU approved
3. ok to roof
3.ok to insulate
|
||||
Energy (Insulation) Inspection | Partial Pass | 10/12/2023 | 10/12/2023 | 10/12/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
10/12/2023
1. no hard lids in bathrooms
2.clarify insulation over bathrooms
3.no demising wall need clarification on blocking in wall as discussed with contractor
4.all other interior and exterior walls ok to cover
|
||||
Other/Miscellaneous
Carried Forward
10/12/2023
1. rigid insulation at demising wall approved
2.insulation at roof where new mech comes thru roof approved
|
||||
Wallboard / Drywall Inspection | Partial Pass | 10/12/2023 | 10/12/2023 | 10/12/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
10/12/2023
1. all dry wall ok to tape except hard lids in bathrooms where covered without inspections
2. there was no drywall installed at demising wall at time of inspection
|
||||
Plumbing Rough In Inspection | Partial Pass | 10/20/2023 | 10/20/2023 | 10/20/2023 |
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
10/20/2023
1. provide as-built from engineer of record for changes made on city approved plans for pipe sizes
2. plumbing test approved pending as-built approval (below slab)
|
||||
Other/Miscellaneous
Carried Forward
10/20/2023
drinking fountain dwv and supply ok
|
||||
Mechanical Rough In Inspection | Partial Pass | 10/23/2023 | 10/23/2023 | 10/23/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Frame Inspection | Not Ready | 10/23/2023 | 10/23/2023 | 10/24/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
10/24/2023
1. no framing, MECH, plumbing, electrical was installed at I/T room and janitors closet at time of inspection
2. provide clarification of bracing at 32" on center on demising wall on detail 16 A2.1 on city approved plans
3. ok to insulate
|
||||
Other/Miscellaneous
Carried Forward
10/24/2023
1.THIS WAS A FRAMING INSPECTION OF I/T AND JANITOR CLOSET
2.provide fasteners at hard lid in to demising wall as discussed with contractor
3.provide electrical cover approval specific to this area
4. provide fire cover approval for this area prior to next inspection
5. provide access to drywall screws on demising wall as discussed with contractor
|
||||
Frame Inspection | Partial Pass | 11/2/2023 | 11/2/2023 | 11/02/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Outstanding
09/26/2023
1.provide electrical cover approval at time of next inspection
2.not ready
|
||||
Other/Miscellaneous
Outstanding
09/26/2023
1. cancelled by contractor
|
||||
Other/Miscellaneous
Outstanding
11/02/2023
1. framing at I/T closet and janitor closet approved ok to insulate
2. framing at hard lids over bathrooms approved
|
||||
Mechanical Rough In Inspection | Partial Pass | 11/3/2023 | 11/3/2023 | 11/03/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
11/03/2023
1. THIS WAS A INSULATION INSPECTION ONLY
2. insulation at I/T room and janitors closet approved
3. OK TO COVER
|
||||
Frame Inspection | Not Ready | 11/6/2023 | 11/6/2023 | 11/06/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
11/06/2023
1. no framing, MECH, plumbing, electrical was installed at I/T room and janitors closet at time of inspection
2. provide clarification of bracing at 32" on center on demising wall on detail 16 A2.1 on city approved plans
3. ok to insulate
|
||||
Other/Miscellaneous
Carried Forward
11/06/2023
1.THIS WAS A FRAMING INSPECTION OF I/T AND JANITOR CLOSET
2.provide fasteners at hard lid in to demising wall as discussed with contractor
3.provide electrical cover approval specific to this area
4. provide fire cover approval for this area prior to next inspection
5. provide access to drywall screws on demising wall as discussed with contractor
|
||||
Other/Miscellaneous
Carried Forward
11/06/2023
1.cancelled on site by contractor
|
||||
Ceiling Grid/T-Bar Inspection | Not Ready | 11/7/2023 | 11/7/2023 | 11/07/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
11/07/2023
1. complete all ceiling requirements as discussed with contractor
|
||||
Frame Inspection | Not Ready | 11/8/2023 | 11/8/2023 | 11/08/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Wallboard / Drywall Inspection | Partial Pass | 11/8/2023 | 11/8/2023 | 11/08/2023 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Resolved
11/08/2023
1. all dry wall ok to tape except hard lids in bathrooms where covered without inspections
2. there was no drywall installed at demising wall at time of inspection
|
||||
Mechanical Rough In Inspection | Passed | 11/9/2023 | 11/9/2023 | 11/09/2023 |
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
11/03/2023
1. THIS WAS A INSULATION INSPECTION ONLY
2. insulation at I/T room and janitors closet approved
3. OK TO COVER
|
||||
Fire Final Inspection | Not Ready | 12/21/2023 | 12/21/2023 | 12/21/2023 |
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
12/21/2023
Items discussed.
1. Fire Alarm, devices above ceiling, missing detection warehouse bathroom hallway, and all documentation.
2. Fire Sprinkler final requirements.
3. Emergency Lighting, tested the circuit, missing lighting throughout office space, warehouse half the lights works, half the bug eyes work.
4. All fire extinguishers have been removed, reinstall all through warehouse and office space.
|
||||
Building Final Inspection | Failed | 2/21/2024 | 2/21/2024 | 02/21/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
02/21/2024
1. provide fire, engineering,and planning final approval prior to next inspection
2.provide balance report
3. provide plumbing boot at drain at break room sink
4. insulate recirc lines at hot water tank in janitors closet
5.complete birc clips
6. complete perimeter wires
7.provide occupancy signage at front door
8.complete plumbing boots at sinks in mens and womens bathrooms
9. complete partitions at existing mens bathrooms per city approved plans
|
||||
Engineering Final Inspection | Passed | 2/23/2024 | 2/23/2024 | 02/23/2024 |
Jeff Hill ((253) 204-5633) | ||||
Erosion And Sediment Inspection | Passed | 02/23/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Comment Engineering Div Inspection | Passed | 02/23/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Cover Inspection/Thrust Blocks Inspection | Passed | 02/23/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Floodproof Certification Inspection | Passed | 02/23/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Elevation Verification Inspection | Passed | 02/23/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Fire Final Inspection | Failed with Fee | 2/27/2024 | 2/27/2024 | 02/27/2024 |
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
02/27/2024
Items discussed.
1. Fire Alarm, devices above ceiling, missing detection warehouse bathroom hallway, and all documentation.
2. Fire Sprinkler final requirements.
3. Emergency Lighting, tested the circuit, missing lighting throughout office space, warehouse half the lights works, half the bug eyes work.
4. All fire extinguishers have been removed, reinstall all through warehouse and office space.
|
||||
Fire Sprinkler
Carried Forward
02/27/2024
Install fire sprinkler on both heads in warehouse rooms. Pay reinspection fee prior to calling for fire final again.
|
||||
Planning Final Inspection | VOID | 2/23/2024 | 02/28/2024 | |
Chris Beale ((253) 841-5418) | ||||
Fire Final Inspection | Passed | 2/28/2024 | 02/28/2024 | |
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Resolved
02/28/2024
Items discussed.
1. Fire Alarm, devices above ceiling, missing detection warehouse bathroom hallway, and all documentation.
2. Fire Sprinkler final requirements.
3. Emergency Lighting, tested the circuit, missing lighting throughout office space, warehouse half the lights works, half the bug eyes work.
4. All fire extinguishers have been removed, reinstall all through warehouse and office space.
|
||||
Fire Sprinkler
Resolved
02/28/2024
Install fire sprinkler on both heads in warehouse rooms. Pay reinspection fee prior to calling for fire final again.
|
||||
Mechanical Final Inspection | Passed | 2/29/2024 | 2/29/2024 | 02/29/2024 |
Monty Johnson ((253) 770-3326) | ||||
Comment Building Div Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Footing/Setback Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Underfloor Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Slab/Insulation Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Block Wall Rebar Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Roof Sheathing Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Shear Wall Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Firewall/Firestop Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Exit Lighting Test Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Re-Roof Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Hydronic Piping Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Gas Test Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Carbon Monoxide Detectors Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Refrigeration Line Test Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Exhaust Hood Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Light Test For Grease Duct Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Exhaust/Vent Fans Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Medical Gas Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Fire Or Smoke Damper Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Emergency Radio Test Review Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Plumbing Final Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Combination Frame And Rough In Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
10/05/2023
1.framing at roof modification for MECH approved
2.fasteners at curb to roof on roof for RTU approved
3. ok to roof
3.ok to insulate
|
||||
Energy (Insulation) Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
10/12/2023
1. no hard lids in bathrooms
2.clarify insulation over bathrooms
3.no demising wall need clarification on blocking in wall as discussed with contractor
4.all other interior and exterior walls ok to cover
|
||||
Other/Miscellaneous
Outstanding
10/12/2023
1. rigid insulation at demising wall approved
2.insulation at roof where new mech comes thru roof approved
|
||||
Plumbing Rough In Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
10/20/2023
1. provide as-built from engineer of record for changes made on city approved plans for pipe sizes
2. plumbing test approved pending as-built approval (below slab)
|
||||
Frame Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
11/06/2023
1. no framing, MECH, plumbing, electrical was installed at I/T room and janitors closet at time of inspection
2. provide clarification of bracing at 32" on center on demising wall on detail 16 A2.1 on city approved plans
3. ok to insulate
|
||||
Other/Miscellaneous
Outstanding
11/06/2023
1.THIS WAS A FRAMING INSPECTION OF I/T AND JANITOR CLOSET
2.provide fasteners at hard lid in to demising wall as discussed with contractor
3.provide electrical cover approval specific to this area
4. provide fire cover approval for this area prior to next inspection
5. provide access to drywall screws on demising wall as discussed with contractor
|
||||
Other/Miscellaneous
Outstanding
11/06/2023
1.cancelled on site by contractor
|
||||
Ceiling Grid/T-Bar Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
11/07/2023
1. complete all ceiling requirements as discussed with contractor
|
||||
Frame Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Wallboard / Drywall Inspection | VOID | 02/29/2024 | ||
Monty Johnson ((253) 770-3326) | ||||
Building Final Inspection | VOID | 2/29/2024 | 2/29/2024 | 02/29/2024 |
Monty Johnson ((253) 770-3326) | ||||
Corrections:
Other/Miscellaneous
Outstanding
02/21/2024
1. provide fire, engineering,and planning final approval prior to next inspection
2.provide balance report
3. provide plumbing boot at drain at break room sink
4. insulate recirc lines at hot water tank in janitors closet
5.complete birc clips
6. complete perimeter wires
7.provide occupancy signage at front door
8.complete plumbing boots at sinks in mens and womens bathrooms
9. complete partitions at existing mens bathrooms per city approved plans
|
Condition | Status | Category |
---|---|---|
Building Permit Standard Conditions | Open | Standard Conditions |
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
||
Fire Review Conditions | Open | Standard Conditions |
1. INSTALL ADDRESS NUMBERS PER THE FOLLOWING DISTANCES:0-50FOOT SETBACK FROM STREET NUMBERS SHALL BE 6 INCHES IN HEIGHT; 51-100 FEET 12 INCHES IN HEIGHT. ALL NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND. ADDITIONAL NUMBERS MAY BE NEEDED AT DRIVEWAY ENTRANCE IF BUILDING NUMBERS ARE NOT VISIBLE FROM THE STREET. REAR DOORS OF SUITES OR UNITS SHALL ALSO BE LABELED WITH MINIMUM 4 INCH NUMBERS.
2. FIRE HYDRANTS REQUIRED FOR CONSTRUCTION AND FIRE DEPARTMENT ACCESS SHALL BE INSTALLED AND APPROVED BY THE FIRE CODE OFFICIAL PRIOR TO THE STORAGE OR INSTALLATION OF ANY COMBUSTIBLE FRAMING MATERIAL. ACCESS ROADWAY SURFACES SHALL BE DESIGNED TO CITY STANDARDS AND BE DESIGNED TO MAINTAIN THE IMPOSED LOADS OF A 80,000 POUND FIRE APPARATUS. ASPHALT TREATED BASE, ASPHALT OR CONCRETE PAVEMENT CAN BE USED TO PROVIDE THE REQUIRED ALL-WEATHER DRIVING SURFACE.
3. ANY REQUIRED FIRE LANE MARKINGS SHALL BE INSTALLED PRIOR TO FINAL INSPECTION AND PER CITY ORDINANCE.
4. KNOX BOXES, WHEN REQUIRED, SHALL BE INSTALLED USUALLY TO THE RIGHT OF THE MAIN FRONT DOOR AND NO HIGHER THAN 6 FEET OFF OF THE GROUND. ONLY HINGED KNOX BOXES SHALL BE USED. KNOX BOXES AND KEY SWITCHES CAN BE ORDERED ONLINE AT THE "KNOX COMPANY"
5. FIRE EXTINGUISHERS WILL BE REQUIRED PER CHAPTER 9 OF THE INTERNATIONAL FIRE CODE. GENERALLY, 1 FIRE EXTINGUISHER WITH A MINIMUM RATING OF 2A 10BC SHALL BE INSTALLED PER EVERY 3,000 SQUARE FEET OF FLOOR AREA. THE LOCATION OF THE FIRE EXTINGUISHERS SHALL BE NEAR THE EXIT DOORS AND TRAVEL DISTANCE TO AN EXTINGUISHER SHALL NOT EXCEED 75 FEET. ADDITIONAL SIGNAGE MAY BE NECESSARY TO INDICATE THE FIRE EXTINGUISHER LOCATION.
6. Fire alarm and Fire sprinkler require separate permits.
|
||
Miscellaneous Condition | Resolved | Prior to Issuance |
Engineering Division
A Utility Connection/Repair permit must be issued to install the required sewer sampling tee. Another TI application, PRCTI2023 310, is under review for this building with this same condition. Once the the utility permit is issued both can be released. LL
|
||
Miscellaneous Condition | Resolved | Prior to Occupancy |
Engineering Division
Occupancy will not be granted until the sewer sampling tee has been installed and a final inspection has been approved on the installation, see permit PRUSR20230614. LL 05/11/2023
Another TI application, PRCTI2023 310, is under review for this building with this same condition. Once the the sewer sampling tee has been installed and approved both can ask for a final engineering inspection. LL
|
||
Engineering Commercial Standard Conditions | Open | Standard Conditions |
Development & Permitting Services
Development Engineering standard commercial conditions:
- Occupancy will not be granted until all work associated with the required utility connection/repair permit to install the sewer sampling tee has been completed and approval has been provided.
-- A commercial development must have installed a side sewer sampling tee installed in conformance to city standard section 04.03 – side sewer.
- The record civil drawings indicate that a reduced pressure backflow assembly has been installed. However if one does not exist on the water service connections an approved backflow prevention assembly must be installed as directed by the Puyallup Municipal Code 14.02.220(3) and conforming to city standard section 03.04 - backflow installation. A reduced pressure backflow assembly (RPBA) is required as directed by the City of Puyallup,
- Due to the proximity of this property to a secondary water source (i.e. clarks creek, meeker ditch, etc.) the applicant shall install a reduced pressure backflow assembly per city standards.
- Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
|
Reference Number | Status | Type |
---|---|---|
PRFA20221409 | Closed | Fire Alarms |
PRCTI20230908 | Closed | Commercial - Tenant Improvement/Remodel |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.