CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20240469


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20240469
Commercial - Tenant Improvement/Remodel
Closed
AMB INSTITUTIONAL ALLIANCE FUND III LP
Alteration/Remodel
NON-STRUCTURAL INTERIOR TENANT IMPROVEMENT: WORK INCLUDES ADDING ROOF INSULATION TO EXISTING ROOF THROUGHOUT THE SUITE. - PROLOGIS Project is a resubmittal review.
03/21/2024
04/09/2024
03/16/2025
09/12/2024

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Building Review Approved 04/12/2024 04/09/2024
Fire Review Approved 04/12/2024 04/08/2024
Engineering Review Approved 04/12/2024 03/28/2024
Planning Review VOID 04/18/2024 03/27/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 04/09/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 04/09/2024
Outstanding Fees Amount Paid Owing Date Paid
Building Permit Fee $0.00 $0.00 Not payable Not Paid
Building Plan Review Fee $0.00 $0.00 Not payable Not Paid


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Not Ready 4/25/2024 4/25/2024 04/25/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. discussed old permit new permit and current scope of work

Energy (Insulation) Inspection Failed 6/4/2024 6/4/2024 06/04/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.complete vapor barrier as discussed with contractor

Comment Engineering Div Inspection Passed 6/7/2024 6/7/2024 06/07/2024
Jeff Hill ((253) 204-5633)
Energy (Insulation) Inspection Failed 6/10/2024 6/10/2024 06/10/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.complete vapor barrier as discussed with contractor

Other/Miscellaneous
Resolved
09/17/2024
1. complete vapor barrier as discussed with contractor 2. provide head of wall detail at north end of office space at time of next inspection

Energy (Insulation) Inspection Failed 6/12/2024 6/12/2024 06/12/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.complete vapor barrier as discussed with contractor

Other/Miscellaneous
Resolved
09/17/2024
1. complete vapor barrier as discussed with contractor 2. provide head of wall detail at north end of office space at time of next inspection

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 6/12/2024 1. complete corrections from previous inspection prior to scheduling next inspection

Energy (Insulation) Inspection Partial Pass 6/17/2024 6/17/2024 06/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
06/17/2024
1.complete vapor barrier as discussed with contractor

Other/Miscellaneous
Resolved
06/17/2024
1. complete vapor barrier as discussed with contractor 2. provide head of wall detail at north end of office space at time of next inspection

Other/Miscellaneous
Resolved
06/17/2024
date of inspection 6/12/2024 1. complete corrections from previous inspection prior to scheduling next inspection

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 6/17/2024 1.insulation and vapor barrier at roof approved

Frame Inspection Partial Pass 6/27/2024 6/27/2024 06/27/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.framing at fill ins approved pending electrical approval 2.ok to insulate as discussed with contractor

Wallboard / Drywall Inspection Partial Pass 6/27/2024 6/27/2024 06/27/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. drywall at fill in on inside approved

Energy (Insulation) Inspection Partial Pass 7/3/2024 7/3/2024 07/03/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
date of inspection 6/17/2024 1.insulation and vapor barrier at roof approved

Other/Miscellaneous
Resolved
09/17/2024
insulation in demising walls at three places ok

Shear Wall Inspection Partial Pass 7/9/2024 7/9/2024 07/10/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.plywood nailing and vapor barrier at east demising wall approved

Wallboard / Drywall Inspection Partial Pass 7/9/2024 7/9/2024 07/10/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. drywall at fill in on inside approved

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 7/9/2024 1. drywall fill ins in north demising wall exterior side approved

Shear Wall Inspection Partial Pass 7/16/2024 7/16/2024 07/16/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.plywood nailing and vapor barrier at east demising wall approved

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 7/16/2024 1.plywood strips at east dismissing wall approved ok to drywall

Exhaust/Vent Fans Inspection Passed 7/17/2024 7/17/2024 07/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/17/2024
1.duct sealing approved

Wallboard / Drywall Inspection Partial Pass 7/17/2024 7/17/2024 07/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. drywall at fill in on inside approved

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 7/9/2024 1. drywall fill ins in north demising wall exterior side approved

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 7/17/2024 1. drywall at east demising wall approved

Hydrostatic Test 200Lbs 2Hrs VOID 7/23/2024 7/23/2024 07/23/2024
David Drake ((253) 864-4171)
Ceiling Grid/T-Bar Inspection Not Ready 7/29/2024 7/29/2024 07/29/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1.provide engineering for pods on site at time of next inspection 2.complete pods in areas that exceed 1,000 sq ft 3. provide seismic separation joint in areas that exceed 2,500 sq ft 4. not a complete list

Ceiling Grid/T-Bar Inspection Failed 7/31/2024 08/01/2024
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
08/01/2024
1.provide engineering for pods on site at time of next inspection 2.complete pods in areas that exceed 1,000 sq ft 3. provide seismic separation joint in areas that exceed 2,500 sq ft 4. not a complete list

Other/Miscellaneous
Resolved
09/17/2024
7/31/2024 1.provide engineering for pods on site at time of next inspection (will submit from architect) 2.complete pods in areas that exceed 1,000 sq ft (contractor will create soffit/separation at kitchenette) 3. provide seismic separation joint in areas that exceed 2,500 sq ft (Completed) 4. not a complete list

Comment Building Div Inspection Passed w/ Conditions 7/31/2024 08/01/2024
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. discussed old permit new permit and current scope of work

Ceiling Grid/T-Bar Inspection Not Ready 8/5/2024 8/5/2024 08/07/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
08/07/2024
7/31/2024 1.provide engineering for pods on site at time of next inspection (will submit from architect) 2.complete pods in areas that exceed 1,000 sq ft (contractor will create soffit/separation at kitchenette) 3. provide seismic separation joint in areas that exceed 2,500 sq ft (Completed) 4. not a complete list

Ceiling Grid/T-Bar Inspection Partial Pass 8/8/2024 8/8/2024 08/08/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
7/31/2024 1.provide engineering for pods on site at time of next inspection (will submit from architect) 2.complete pods in areas that exceed 1,000 sq ft (contractor will create soffit/separation at kitchenette) 3. provide seismic separation joint in areas that exceed 2,500 sq ft (Completed) 4. not a complete list

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 8/8/2024 1.kitchen area approved for cover 2.main area complete pods per city approved plans ( fasteners and spacing as discussed with contractor ) 3. this is a complete list

Ceiling Grid/T-Bar Inspection Failed 8/16/2024 8/16/2024 08/16/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
7/31/2024 1.provide engineering for pods on site at time of next inspection (will submit from architect) 2.complete pods in areas that exceed 1,000 sq ft (contractor will create soffit/separation at kitchenette) 3. provide seismic separation joint in areas that exceed 2,500 sq ft (Completed) 4. not a complete list

Other/Miscellaneous
Resolved
09/17/2024
date of inspection 8/8/2024 1.kitchen area approved for cover 2.main area complete pods per city approved plans ( fasteners and spacing as discussed with contractor ) 3. this is a complete list

Other/Miscellaneous
Resolved
09/17/2024
8/16/24 1:install clips on diffusers correctly or provide screws 2:complete siezmic wires on lights 3:patch holes in demising walls

Ceiling Grid/T-Bar Inspection Passed 8/19/2024 8/19/2024 08/19/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
08/19/2024
7/31/2024 1.provide engineering for pods on site at time of next inspection (will submit from architect) 2.complete pods in areas that exceed 1,000 sq ft (contractor will create soffit/separation at kitchenette) 3. provide seismic separation joint in areas that exceed 2,500 sq ft (Completed) 4. not a complete list

Other/Miscellaneous
Resolved
08/19/2024
date of inspection 8/8/2024 1.kitchen area approved for cover 2.main area complete pods per city approved plans ( fasteners and spacing as discussed with contractor ) 3. this is a complete list

Other/Miscellaneous
Outstanding
08/19/2024
date of inspection 8/19/2024 1.ceiling cover approved per city approved documents 2. ok to cover

Exit Lighting Test Inspection Passed 9/4/2024 09/05/2024
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 09/05/2024
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 09/05/2024
David Drake ((253) 864-4171)
Fire Final Inspection Passed 9/4/2024 9/4/2024 09/05/2024
David Drake ((253) 864-4171)
Building Final Inspection Failed 9/5/2024 9/5/2024 09/05/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/17/2024
1. provide balance report as discussed with contractor 2.cap gas line on roof 3. fasten RTU to curb adapter on roof 4. provide fire final approval at time of next inspection 5. provide engineering final prior to next inspection

Building Final Inspection Passed 9/12/2024 9/12/2024 09/12/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
09/12/2024
1. provide balance report as discussed with contractor 2.cap gas line on roof 3. fasten RTU to curb adapter on roof 4. provide fire final approval at time of next inspection 5. provide engineering final prior to next inspection

Footing/Setback Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Foundation/Rebar Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Slab/Insulation Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Roof Sheathing Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Firewall/Firestop Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Combination Frame And Rough In Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Hydronic Piping Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Refrigeration Line Test Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Exhaust Hood Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Light Test For Grease Duct Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Medical Gas Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Cover Inspection/Thrust Blocks Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Engineering Final Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Frame Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
06/27/2024
1.framing at fill ins approved pending electrical approval 2.ok to insulate as discussed with contractor

Energy (Insulation) Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Shear Wall Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/16/2024
1.plywood nailing and vapor barrier at east demising wall approved

Other/Miscellaneous
Outstanding
07/16/2024
date of inspection 7/16/2024 1.plywood strips at east dismissing wall approved ok to drywall

Wallboard / Drywall Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
07/17/2024
1. drywall at fill in on inside approved

Other/Miscellaneous
Outstanding
07/17/2024
date of inspection 7/9/2024 1. drywall fill ins in north demising wall exterior side approved

Other/Miscellaneous
Outstanding
07/17/2024
date of inspection 7/17/2024 1. drywall at east demising wall approved

Comment Building Div Inspection VOID 09/17/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Outstanding
08/01/2024
1. discussed old permit new permit and current scope of work

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2021IFC and 2021 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • Separate permits required for Fire Alarm and Fire Sprinkler • RTU’S will be required to be tested for shut down • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20230310 Closed Commercial - Tenant Improvement/Remodel
PRUSR20230614 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRFS20230864 Expired Fire Sprinklers
PRFA20230883 Closed Fire Alarms
PRFA20231139 Closed Fire Alarms
PRFA20231193 Closed Fire Alarms
PRFS20240702 Permit(s) Issued Fire Sprinklers
PRCTI20250557 Closed Commercial - Tenant Improvement/Remodel
PRSG20250891 Closed Sign/Awning
PRCTI20251104 Ready for Issuance Commercial - Tenant Improvement/Remodel
PRCTI20251201 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRSG20251300 Permit(s) Issued Sign/Awning
PRFA20251359 In Plan Check Fire Alarms

Documents & Images

Date Uploaded File Type Name
04/09/2024 Form Building Permit Application 2023_Correction #2_Roof Insulation (Flattened)
04/09/2024 Plans CONSTRUCTION PLANS (Stamped)
04/09/2024 Form WSEC - ENVELOPE COMPLIANCE (Stamped)
04/09/2024 Letter Permit - Detailed
04/09/2024 Receipt Receipt for transaction:2024-000709
04/25/2024 Report Inspection Report (Comment Building Div Inspection)
06/04/2024 Report Inspection Report (Energy (Insulation) Inspection)
06/10/2024 Report Inspection Report (Energy (Insulation) Inspection)
06/12/2024 Report Inspection Report (Energy (Insulation) Inspection)
06/17/2024 Report Inspection Report (Energy (Insulation) Inspection)
06/27/2024 Report Inspection Report (Frame Inspection)
06/27/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/10/2024 Report Inspection Report (Shear Wall Inspection)
07/10/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/16/2024 Report Inspection Report (Shear Wall Inspection)
07/17/2024 Report Inspection Report (Exhaust/Vent Fans Inspection)
07/17/2024 Report Inspection Report (Wallboard / Drywall Inspection)
07/29/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
08/07/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
08/07/2024 Plans 240805 Prologis Puyallup 1 FIELD REVISION 22-0243-00
08/08/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
08/19/2024 Report Inspection Report (Ceiling Grid/T-Bar Inspection)
09/05/2024 Report Inspection Report (Building Final Inspection)
09/12/2024 Report Inspection Report (Building Final Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.