Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Alarm Final Inspection | Partial Pass | 1/8/2024 | 1/8/2024 | 01/10/2024 |
Ray Cockerham ((253) 841-5585) | ||||
Corrections:
Other/Miscellaneous
Resolved
01/07/2025
Testing in office space is complete suite 103.
1) Need updated map.
2) Review Certificate
3) Above ceiling system has been disabled.
|
||||
Fire Alarm Final Inspection | Passed | 1/7/2025 | 1/7/2025 | 01/07/2025 |
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Resolved
01/07/2025
Testing in office space is complete suite 103.
1) Need updated map.
2) Review Certificate
3) Above ceiling system has been disabled.
|
||||
Piv And Tamper Inspection | VOID | 01/07/2025 | ||
David Drake ((253) 864-4171) | ||||
Fire Alarm Cover Inspection | VOID | 01/07/2025 | ||
David Drake ((253) 864-4171) | ||||
Fire Alarm Test Inspection | VOID | 01/07/2025 | ||
David Drake ((253) 864-4171) |
Condition | Status | Category |
---|---|---|
New Fire Alarm System Conditions | Open | Standard Conditions |
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling.
• Provide plans and permit on site for inspection.
• Complete labor and industries inspections prior to requesting city inspection.
• If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information.
• Exterior fire bell required outside fire sprinkler room.
• Above ceiling detection is required.
• Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof.
• Total coverage is required, subject to field inspection. Comply with NFPA 72.
• Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified.
• Pre-test shall be conducted with a printout for inspector at time of inspection.
• Labeling of all devices above and below ceiling required.
• RTU’S and smoke dampeners will be required to be tested during inspection.
• The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable.
• In existing buildings all above ceiling detection is to remain. Do not remove.
• Due to unforeseeable construction design, all device locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
Reference Number | Status | Type |
---|---|---|
PRCTI20230310 | Closed | Commercial - Tenant Improvement/Remodel |
PRUSR20230614 | Closed | Utility Service Repair/PRIVATE PROPERTY ONLY |
PRFS20230864 | Expired | Fire Sprinklers |
PRFA20231139 | Closed | Fire Alarms |
PRFA20231193 | Closed | Fire Alarms |
PRCTI20240469 | Closed | Commercial - Tenant Improvement/Remodel |
PRFS20240702 | Permit(s) Issued | Fire Sprinklers |
PRCTI20250557 | Closed | Commercial - Tenant Improvement/Remodel |
PRSG20250891 | Closed | Sign/Awning |
PRCTI20251104 | Ready for Issuance | Commercial - Tenant Improvement/Remodel |
PRCTI20251201 | Permit(s) Issued | Commercial - Tenant Improvement/Remodel |
PRSG20251300 | Permit(s) Issued | Sign/Awning |
PRFA20251359 | In Plan Check | Fire Alarms |
Date Uploaded | File Type | Name |
---|---|---|
06/13/2023 | Form | Prologis Park 103 Fire Alarm Application |
06/13/2023 | Receipt | Receipt for transaction:2023-001108 |
07/11/2023 | Letter | Permit Review Correction Letter |
07/11/2023 | Form | prologis Park Suite 103 Resbmittal Letter |
07/20/2023 | Plans | (7-7-23) Prologis Puyallup Suite 103 FA Drawings (Stamped) |
07/20/2023 | Plans | Prologis Puyallup Suite 103 Fire Alarm Submittals (Stamped) |
07/20/2023 | Permit | Permit - Detailed |
12/05/2023 | Letter | Permit Expiration Notice |
06/06/2024 | Letter | Permit Expiration Notice |
12/06/2024 | Letter | Permit Expiration Notice |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView