PRFA20251732
Fire Alarms
Permit(s) Issued
EAST TOWN CROSSING LLC
New
New Fire Alarm system for Hot Works Studio. System will be monitored by 3rd party. - HOTWORX -- 727 SHAW RD, EAST TOWN CROSSING COMMERCIAL BLDG.
12/31/2025
02/20/2026
08/31/2026

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
02/20/2026 FIRE ALARM PLANS - RESUB (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 02/20/2026 02/20/2026
Fire Review Failed 01/27/2026 01/23/2026

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (New) Fee $402.50 $402.50 Paid 12/31/2025
Resubmittal/Revision Fee $180.00 $180.00 Paid 02/09/2026
Building Re-Inspection Fee $180.00 $180.00 Paid 03/05/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Alarm Cover Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Pending
David Drake ((253) 864-4171)
Piv And Tamper Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Final Inspection Pending 3/10/2026
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
03/03/2026
1. Complete Riser Room walls construction per approved plans. 2. Install Riser Room signage. 3. Install ladder and roof hatch system. No access to RTU's. 4. The Riser Room is a heated room. There is a significant amount of light coming through at the roof deck. This tells me the heat will not protect the Fire Sprinkler Riser or the FACP. 5. No fire alarm contractor onsite. 6. Pay reinspection’s prior to scheduling next Finals.

Piv And Tamper Inspection Failed 3/3/2026 03/03/2026
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Failed 3/3/2026 03/03/2026
David Drake ((253) 864-4171)
Fire Alarm Final Inspection Failed with Fee 3/3/2026 03/03/2026
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Carried Forward
03/03/2026
1. Complete Riser Room walls construction per approved plans. 2. Install Riser Room signage. 3. Install ladder and roof hatch system. No access to RTU's. 4. The Riser Room is a heated room. There is a significant amount of light coming through at the roof deck. This tells me the heat will not protect the Fire Sprinkler Riser or the FACP. 5. No fire alarm contractor onsite. 6. Pay reinspection’s prior to scheduling next Finals.

Conditions

Condition Status Category
New Fire Alarm System Conditions Open Standard Conditions
Fire Prevention
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. Inspections are Monday - Thursday, no friday inspections • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • A remote annunciator located at the main entrance is required. If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information. • Exterior fire bell required outside fire sprinkler room. • Above ceiling detection is required. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72, 2019 • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. • A pre-test shall be conducted and a printout of the location of the device, point number and descriptor shall be furnished to the inspector at final. Labeling of all devices above and below ceiling required. • Fire sprinkler tamper valves and PIV will be required to be tested at inspection. Fire sprinkler contractor to be onsite. • RTU’S and smoke dampeners will be required to be tested during inspection. • The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable. • In existing buildings all above ceiling detection is to remain. Do not remove. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Miscellaneous Condition Resolved Prior to Issuance
Development & Permitting Services
Pending Issuance of Permit no. PRCTI20251445 prior to issuance of PRFA20251732

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20251445 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFS20260109 Permit(s) Issued Fire Sprinklers

Documents & Images

Date Uploaded File Type Name
12/31/2025 Plans FIRE ALARM PLANS (DO NOT USE - NOT FLATTEN FOR REVIEW)
12/31/2025 Receipt Receipt for transaction:2025-002468
01/23/2026 Form HotWorx Studio - Fire Permit Application (Flattened)
02/09/2026 Plans FLOOR PLAN - RESUB ( NOT FLATTEN FOR REVIEW)
02/09/2026 Plans FIRE ALARM PLANS - RESUB (NOT FLATTEN FOR REVIEW)
02/20/2026 Plans FIRE ALARM PLANS - RESUB (Stamped)
02/20/2026 Permit Permit - Detailed