Review Type |
Outcome |
Est. Completion Date |
Completed |
Planning Review
|
Revisions Required
|
07/08/2022
|
07/14/2022
|
|
|
|
|
Engineering Review
|
Revisions Required
|
06/28/2022
|
07/11/2022
|
|
|
|
Other/Miscellaneous
GENERAL:
• Engineered plans must follow the latest regulations and standards set forth in the Puyallup Municipal Code (PMC), the City Standards for Public Works Engineering and Construction (design standards), and the current City adopted stormwater manual at the time of civil permit application [PMC 21.10.040].
• The comments provided below are intended to assist the applicant with incorporating City requirements into the project design documents, but should not be considered an exhaustive list of all necessary provisions from the PMC, design standards, or the Ecology stormwater manual.
• Comments regarding design and construction of new utilities and road improvements are provided for the applicant’s information and use. Unless specifically noted, construction of these infrastructure improvements is not a condition of landuse approval. However, infrastructure improvements must be approved and permitted prior to issuance of the first building permit associated with the project. [RCW 58.17.120 and 19.07.080]
|
|
Other/Miscellaneous
WATER:
• Refer to City Standards, Section 300 for Water System Requirements. [PMC 14.02.120]
• The domestic service line and fire system service line shall have separate, independent connections to the supply main. [PMC 14.02 & CS 302.3(4)]
• A new water main shall be extended to, and through, the site sufficient to provide the necessary flows for the proposed fire system. The minimum water pipe size shall be 8-inch diameter for dead-end mains and 6-inch diameter for circulating mains. [PMC 16.08.040, 14.20.010 & CS 301.2]
• The applicant shall be responsible for the operation and maintenance of the proposed water system located on private property.
• Any existing services that are to be abandoned at this site shall be disconnected at the main, the corp. stop removed, and the service plugged to city standards. [PMC 14.02.120(f)]
• The minimum distance between water lines and sewer lines shall be 10-feet horizontally and 18-inches vertically. If this criterion cannot be met, the applicant shall isolate the sewer and water lines by encasement, shielding, or other approved methods. [PMC 14.02.120(f) & CS 301.1(8)]
• The applicant shall be responsible to provide and install the water meters required to service the site. Domestic service water meters shall be located within the PUBLIC ROW, or in the case of a private road adjacent to the road section, in accordance with City Standards. [PMC 14.02.120(f) & CS 301.3]
• Water pipe and service connections shall be a minimum of 10-feet away from building foundations and/or roof lines.
• The applicant is required to provide backflow protection on the domestic line(s) in accordance with City Standards. The minimum level of protection would be a double check valve assembly (DCVA). However, the City requires a reduced pressure backflow assembly (RPBA) for any use considered to be a high-hazard as outlined in WAC 246-290-490 Table 9. Depending on the end-user of the individual tenant space(s), the applicant may want to install an RPBA at this time, in lieu of a DCVA, to avoid the potential expense of upgrading the backflow device in the future. [PMC 14.02.220(3) & CS 302.2]
• If an irrigation system is also proposed, a DCVA is required on that line as well. [PMC 14.02.220(3) & CS 302]
• Available fire flow for the project site must be determined by hydraulic modeling conducted by the City’s consultant. The cost of this analysis is $600 and shall be paid by the applicant.
• Fire hydrants and other appurtenances such as DDCVA and PIV shall be placed as directed by the Puyallup Fire Code Official. Fire hydrants shall be placed so that there is a minimum of 50-feet of separation from hydrants to any building walls. [PMC 16.08.080 & CS 301.2, 302.3]
• Maximum hydrant run is 20-feet. Hydrant runs that exceed this distance shall be served by a mainline with the hydrant feed line set at right angles to the supply main.
• The fire sprinkler double detector check valve assembly (DDCVA) may be located either inside, or outside, of the building. [CS 302.3, CS 303]
• At the time of Civil permit application, the fire sprinkler supply line shall be designed, and shown on the plan, into the building to the point of connection to the interior building riser. Provide plan and elevation detail(s) where the riser enters the building with dimensions, clearances, and joint restraint in accordance with NFPA 24. [CS 302.3, CS 303]
• The Fire Department Connection (FDC) shall be located no closer than 10-feet and no further than 15-feet from a fire hydrant. (NOTE: If the project is utilizing a fire booster pump, the FDC must connect to the sprinkler system on the discharge side of the pump in accordance with NFPA regulations.) A post indicator valve (PIV) shall be provided for the fire sprinkler system in advance of the DDCVA. [CS 302.3]
• A water system development charge (SDC) will be assessed based on the number of plumbing fixture units as defined in the Uniform Plumbing Code. Current SDC’s as of this writing are $4,260.00 for the first 15 fixture units and an additional charge of $285.42 for each fixture unit in excess of the base 15 plumbing fixture units. [PMC 14.02.040]
• Water connection fees and systems development charges are due at the time of building permit issuance and do not vest until time of permit issuance. [PMC 14.02.040, 14.10.030]
• To obtain credit towards System Development Fees for any existing fixture units, the applicant shall provide the City evidence of the existing plumbing fixtures prior to demolition or removal. A written breakdown of the removed fixture types, quantities, and associated fixture units shall accompany the building permit application and be subject to review and approval by the City. [PMC 14.02.040]
|
|
Other/Miscellaneous
SANITARY SEWER:
• Refer to City Standards, Section 400 for Sewer System Requirements. [PMC 17.42]
• The applicant shall connect into the existing public system located within 15th St SE. If a proposed connection is to occur elsewhere, the applicant shall confirm that the system is located within an easement to the City of Puyallup. [PMC 14.08.070]
• As of this writing, there are no known sewer constrictions in this system within ¼-mile of the proposed project.
• A separate and independent side sewer will be required from the public main to the project site. Side sewers shall be 6-inch minimum diameter with a 0.02 foot per foot slope. Side sewers shall have a cleanout at the property line, at the building, and every 100 feet between the two points. [PMC 14.08.110 & CS 401(6)]
• If the proposed side sewer is greater than 6-inches, a sanitary sewer manhole shall be provided at the property line.
• Prior to reuse of the existing side sewer, the City Collections Division must conduct a visual inspection of the side sewer to determine whether it can be used again. Existing laterals must meet current standard to be used again. The applicant shall be responsible to expose the line as necessary for the City inspection. The City reserves the right to request video inspection of the side sewer to assist in its determination.
• Sewer main pipe and service connections shall be a minimum of 10-feet away from building foundations and/or roof lines.
• Grease Interceptors are required for all commercial facilities involved in food preparation. If food preparation facilities are proposed now, or in the future, the applicant shall install an external grease interceptor in accordance with the current edition of the Uniform Plumbing Code adopted by the City of Puyallup, Puyallup Municipal Code, and City standard details. [PMC 14.06.031(3) & CS 401(5), 402.3]
• The construction of a trash enclosure will require the enclosure pad to be elevated to prevent stormwater run-on. If a sewer area drain is proposed for any trash enclosure, then the entire enclosure shall be covered to prevent stormwater run-on and inflow into the sewer system.
• A sanitary sewer system development charge (SDC) will be assessed based on the number of plumbing fixture units as defined in the Uniform Plumbing Code. Current SDC’s as of this writing are $5,890.00 for the first 15 plumbing fixture units and an additional charge of $394.63 for each fixture unit in excess of the base 15 plumbing fixture units. [PMC 14.10.010, 14.10.030]
• Sewer connection fees and systems development charges are due at the time of building permit issuance and do not vest until time of permit issuance. [PMC 14.10.010, 14.10.030]
• To obtain credit towards System Development Fees for any existing fixture units, the applicant shall provide the City evidence of the existing plumbing fixtures prior to demolition or removal. A written breakdown of the removed fixture types, quantities, and associated fixture units shall accompany the building permit application and be subject to review and approval by the City. [PMC 14.10.010]
|
|
Other/Miscellaneous
STORMWATER/ EROSION CONTROL:
• Stormwater design shall be in accordance with PMC Chapter 21.10 and the 2019 Department of Ecology (Ecology) Stormwater Management Manual for Western Washington (aka “Ecology Manual”) as adopted by the City Council at the time of project application.
• Refer to City Standards, Section 200 for Stormwater System Requirements. [PMC 17.42]
• The applicant shall complete the stormwater flowchart, Figure 3.1, contained in Ecology’s Phase II Municipal Stormwater Permit, Appendix I. The completed flowchart shall be submitted with the preliminary stormwater site plan and highlight the Minimum Requirements (MR) triggered by the project thresholds. The link below may be used to obtain the flowchart:
Western Washington PH II Stormwater Permit
• NOTE: Areas of disturbance within the public ROW must be included in the project area as part of the stormwater thresholds and calculations.
• The applicant is responsible for submitting a preliminary stormwater management site plan which meets the design requirements provided by PMC Section 21.10 and Ecology Manual. The preliminary stormwater site plan (PSSP) shall be submitted with the landuse application to ensure that adequate stormwater facilities are anticipated prior to development of the property. The preliminary stormwater site plan shall reasonably estimate the quantity of stormwater runoff and the application of On-site Stormwater Management BMPs for the proposed development.
• The written technical report shall clearly delineate any offsite basins tributary to the project site and include the following information: [PMC 21.10.060]
- the quantity of the offsite runoff;
- the location(s) where the offsite runoff enters the project site;
- how the offsite runoff will be routed through the project site.
- the location of proposed retention/detention facilities
- and, the location of proposed treatment facilities
• Each section of the TIR/SSP shall be individually indexed and tabbed with each permit application and every re-submittal prior to review by the City. [PMC 21.10.060]
• If the applicant proposes a direct discharge connection to the Puyallup River, the associated conveyance system shall be designed in accordance with the requirements of PMC 21.10.04 and the Ecology Manual, Volume I, Appendix I-E. Specifically:
- The project site must be drained by a conveyance system that is comprised entirely of manmade elements and extends to the ordinary high water mark of the Puyallup River;
- The conveyance system between the project site and the Puyallup River shall have adequate conveyance capacity to convey discharges from the proposed (post-development) project, in addition to the discharges associated with the existing basin tributary to the outfall;
- All such flows shall remain within all catch basin or manhole rims for a continuous model simulation associated with the September 17, 1969, storm event assuming no backflow influence from the Puyallup River and shall provide greater than one cfs remaining capacity of the system.
- The discharge will not cause, or aggravate, downstream flooding problems
- The discharge does not reduce natural flows to other streams or wetlands
• Public right-of-way runoff shall be detained and treated independently from proposed private stormwater facilities. This shall be accomplished by enlarging the private facilities to account for bypass runoff; providing separate publicly maintained storm facilities within a tract or dedicated right-of-way; or, other methods as approved by the City Engineer. [PMC 21.10.190(3)]
• Development and redevelopment projects are required to employ, wherever feasible, Low Impact Development (LID) Best Management Practices (BMPs) to meet the design criteria set forth in PMC 21.10.190, the Ecology Manual Volume I, Minimum Requirement 5; Volume III, Chapter 3; and Volume V, Chapter 5.
• If infiltration facilities/BMPs are anticipated, the number of infiltration tests shall be based on the area contributing to the proposed facility/BMP, e.g., one test for every 5,000 sq. ft of permeable pavement, or one test for each bioretention cell.
• Preliminary feasibility/infeasibility testing for infiltration facilities/BMPs shall be in accordance with the site analysis requirements of the Ecology Manual, Volume I, Chapter 3, specifically:
- Groundwater evaluation, either instantaneous (MR1-5), or continuous monitoring (MR1-9), during the wet weather months (December 21 through April 1).
- Hydraulic conductivity testing:
i. If the development meets the threshold to require implementation of Minimum Requirement #7 (flow control); or, if the site soils are consolidated; or, if the property is encumbered by a critical area, then Small Scale Pilot Infiltration Testing (PIT) during the wet weather months (December 21 through April 1) is required.
ii. If the development does not meet the threshold to require implementation of Minimum Requirement #7; or, is not encumbered by a critical area; and is located on soils unconsolidated by glacial advance, grain size analyses may be substituted for the Small Scale PIT test at the discretion of the review engineer.
- Testing to determine the hydraulic restriction layer.
- Mounding analysis may be required in accordance with Ecology Volume III Section 3.3.8.
• Upon submission of the geotechnical infiltration testing, appropriate long-term correction factors shall be noted for any areas utilizing infiltration into the underlying native soils in accordance with the Ecology Manual, Volume III, Chapter 3. Provide the long-term infiltration rate calculation in the stormwater report.
• At the time of civil permit application, the applicant is responsible for submitting a permanent storm water management plan which meets the design requirements provided by PMC Section 21.10. [PMC 21.10.190, 21.10.060]
- When using WWHM for analysis, provide the following WWHM project files with the civil permit application:
- Binary project file (WHM file extension)
- ASCII project file (WH2 file extension)
- WDM file (WDM file extension)
- WWHM report text (Word file)
• For offsite basin inflow: At time of civil application, document compliance with 2019 Ecology Manual, Vol III, Sec III-2.4 (2014 Manual, Vol. III, Appendix III-B, Section 6) for the Offsite Basin inflow.
• Overflow facilities shall be provided for any proposed detention/retention (R/D) facilities in accordance with the City Standards. This includes a downstream analysis a minimum of ¼ mile downstream from the site.
• Any above-ground stormwater facility shall be screened from public right-of-way and adjacent property per the underlying zoning perimeter buffer requirements in the PMC.
• Stormwater R/D facilities shall be a minimum of 20-feet from any public right-of-way, tract, vegetative buffer, and/or property line measured from the toe of the exterior slope/embankment of the facility. [PMC 21.10 & DOE Manual, Vol. V, Pg 10-39 and Pg 10-9]
• A minimum of 5-feet clearance shall be provided from the toe of the exterior slope/embankment to any tract, property line, fence, or any required vegetative buffer. [PMC 21.10 & CS 206]
• Water quality treatment of stormwater shall be in accordance with the Ecology Manual, Volume 1, Minimum Requirement 6; and Volume 5, Runoff Treatment.
• If the use of an above-ground combined treatment-storage facility is proposed for flow control and water quality treatment, the geometric characteristics of the facility design shall be in accordance with the Ecology Manual, and the following criteria:
- A licensed professional geotechnical engineer shall determine the maximum seasonal high groundwater elevation at the location of the combined facility.
- The applicant shall clearly indicate the static water surface elevation for the top of the wetpool/bottom of the storage volume.
- The maximum seasonal high groundwater elevation shall be below the static water surface elevation of the wetpool.
• If the applicant proposes to use bioretention cells for water quality treatment, the following notes shall be added to the civil design plans:
- “At the completion of the bioretention cells construction, the engineer-of-record shall provide a written statement to the City of Puyallup that the bioretention cells were built per the approved design.”
- “The bioretention soil media (BSM) supplier shall certify in writing that the bioretention soil media meets the guidelines for Ecology-approved BSM including mineral aggregate gradation, compost guidelines, and mix standards as specified in the 2012 Low Impact Development Technical Guidance Manual for Puget Sound. And, if so verified, no laboratory infiltration testing, cation exchange, or organic content testing is required.”
• Overflow facilities shall be provided at the low points of any proposed permeable pavement areas to allow safe discharge to the downstream public storm system.
• Trench dams shall be provided at the property line for utilities located below infiltrative facilities including, but not limited to, permeable pavements and bioretention facilities. Reference City Standard Detail 06.01.10.
• At the time of civil permit application, all pipe reaches shall be summarized in a Conveyance Table containing the following minimum information and included in the TIR:
Pipe Reach Name Design Flow (cfs)
Structure Tributary Area Pipe-Full Flow (cfs)
Pipe Diameter (in) Water Depth at Design Flow (in)
Pipe Length (ft) Critical Depth (in)
Pipe Slope (%) Velocity at Design Flow (fps)
Manning’s Coefficient (n) Velocity at Pipe-Full Flow (fps)
Percent full at Design Flow (%)
HGL for each Pipe Reach (elev)
• If discharging to the 15th St SE conveyance system, there is an existing wetland approximately 1,100 feet downstream just north of East Main. The applicant shall provide a hydrologic analysis which ensures the wetland’s hydrologic conditions, hydrophytic vegetation, and substrate characteristics are maintained. See Ecology Manual Volume I, Minimum Requirement 8.
• If discharging to the existing private system near the central portion of the project, the applicant shall ensure there are adequate easement rights between the project site and the proposed discharge location (either the public ROW or the existing Puyallup River outfall, depending on whether direct discharge to the river is an option.)
• At the time of civil permit application, the applicant shall provide a conveyance capacity analysis of the existing storm conveyance system between the project site and the existing outfall to ensure adequate capacity assuming existing conditions for any contributing offsite areas, and developed conditions for the project site. The analysis shall include any upstream basin flows tributary to the pipe outfall.
• All storm drains shall be signed as follows:
a) Publicly maintained stormwater catch basins shall be signed using glue-down markers supplied by the City and installed by the project proponent.
b) Privately maintained stormwater catch basins shall be signed with pre-cut 90ml torch down heavy-duty, intersection-grade preformed thermoplastic pavement marking material. It shall read either “Only Rain Down the Drain" or “No Dumping, Drains to Stream”. Alternatively, the glue-down markers may be purchased from the City for a nominal fee.
• All private storm drainage facilities shall be covered by a maintenance agreement provided by the City and recorded with Pierce County. Under this agreement, if the owner fails to properly maintain the facilities, the City, after giving the owner notice, may perform necessary maintenance at the owner’s expense.
• A Stormwater Systems Development fee will be assessed for each new equivalent service unit (ESU) in accordance with PMC Chapter 14.26. Each ESU is equal to 2,800 square feet of ‘hard’ surface. The current SDC as of this writing is $3,560.00 per ESU.
• Stormwater Systems Development fees are due at the time of site development permit or in the case where no site development permit is required, at the time of building permit issuance for the individual lot(s); and the fees do not vest until the time of site development permit issuance, or at the time of building permit issuance in the case where a site development permit is not required.
• A Construction Stormwater General Permit shall be obtained from the Department of Ecology if any land disturbing activities such as clearing, grading, excavating and/or demolition will disturb one or more acres of land, or are part of larger common plan of development or sale that will ultimately disturb one or more acres of land. The link below may be used to obtain information to apply for this permit:
Construction Stormwater General Permit
|
|
Other/Miscellaneous
STREET:
• Frontage improvements shall be completed along the entire property frontage and include curb, gutter, sidewalk, roadway base, pavement, street lighting, and drainage. Dedication of right-of-way may be required to provide for adequate roadway section. Frontage improvements shall meet current City Standards unless otherwise waived by the City Engineer. [PMC 11.08.120, 11.08.130, 19.12.050(1)]
• Existing public utilities that are in conflict with proposed frontage improvements shall be relocated as necessary to meet all applicable City, State, and Federal requirements.
• Existing private utilities (gas, telcom, cable, etc…) that are in conflict with City maintained right-of-way and utilities shall be relocated outside of the travelled road section, i.e., behind the curb under the sidewalk area.
• Upon civil permit application, the following items shall be provided:
- Road plans shall include a plan and profile view of the roadway indicating both the centerline and flow line elevations. [PMC 17.42 & CS 2.2]
- A separate street lighting and channelization plan shall be provided in accordance with City Standards.
- Commercial and Multi-family projects shall provide an autoturn analysis for the largest anticipated vehicle that would access the site. Curb radii and entrance dimensions shall be increased as necessary to allow vehicles to access the site without encroaching into adjacent lanes of traffic.
- Root barriers in accordance with City Standard Detail 01.02.03 shall be installed for all street trees within ten (10) feet of the public ROW.
- Wheel chair ramps, accessible routes, etc. shall be constructed in accordance with City Standards and current ADA regulations. If there is a conflict between the City Standards and ADA regulations, the ADA regulations shall take precedence over the City’s requirements. [PMC 17.42]
- Any surface area proposed for parking, drive aisle, or outdoor storage shall be paved with asphalt or concrete. [PMC 20.30.045(3), 20.35.035(3), 20.44.045(2)]
• Any curb, gutter, sidewalk, or other existing improvements which currently do not meet City Standards, or are damaged during construction, shall be replaced. [PMC 11.08.020]
• Upon review of the required, submitted traffic report, additional off-site improvements may be required as directed by the Traffic Engineering Department. [PMC 17.42]
|
|
Other/Miscellaneous
GRADING:
• A Grading Plan conforming to all requirements of PMC Section 21.14.120 will be required for this project. The Plan shall be prepared by a Civil Engineer licensed in the State of Washington. [PMC 21.14.070]
• A geotechnical report conforming to all requirements PMC Sections 21.14.150 and 21.14.160 will be required for this project. The Report shall be prepared by a Civil Engineer or Engineering Geologist licensed in the State of Washington. Prior to final acceptance of this project, the author of the Report shall provide certification to the City the project was constructed in accordance with the recommendations contained in the report.
• Cross sections will be required at various points along the property lines in accordance with City Standards Section 502 and 503 to ensure no impact from storm water damming or runoff. [PMC 17.42 & CS 502.1]
• At the time of civil permit application, the following notes shall be added to the first sheet of the TESCP:
-“At any time during construction it is determined by the City that mud and debris are being tracked onto public streets with insufficient cleanup, all work shall cease on the project until this condition is corrected. The contractor and/or the owner shall immediately take all steps necessary to prevent future tracking of mud and debris into the public ROW, which may include the installation of a wheel wash facility on-site.”
-“Contractor shall designate a Washington Department of Ecology certified erosion and sediment control leadperson, and shall comply with the Stormwater Pollution Prevention Plan (SWPPP) prepared for this project.”
-“Sediment-laden runoff shall not be allowed to discharge beyond the construction limits in accordance with the Project’s NPDES General Stormwater Permit.”
• RCW 19.122 requires all owners of underground facilities to notify pipeline companies of scheduled excavations through the one-number locator service if proposed excavation is within 100 feet. Notification must occur in a window of not less than 2 business days but not more than 10 business days before beginning the excavation. If a transmission pipeline company is notified that excavation work will occur near a pipeline, a representative of the company must consult with the excavator on-site prior to excavation.
|
|
Other/Miscellaneous
MISC:
• All proposed improvements shall be designed and constructed to current City Standards. [PMC 14.08.040, 14.08.120, 17.42]
• Civil engineering drawings cannot be accepted until Planning Department requirements have been satisfied, including but not limited to, SEPA, Preliminary Site Plan approval, CUP, and/or Hearing Examiner conditions.
• Civil engineering drawings will be required for this project prior to issuance of the first building permit. Included within the civil design package shall be a utility plan overlaid with the proposed landscaping design to ensure that potential conflicts between the two designs have been addressed.
- At the time of civil application, submit electronic files in PDF format, through the City’s Permit Portal. Contact the Permit staff via email at PermitCenter@ci.puyallup.wa.us for the initial project submittal.
• Civil engineering plan review fee is $470.00 (plus an additional per hour rate of $130.00 in excess of 5 hours). The Civil permit shall be $300.00 and the inspection fee shall be 3% of the total cost of the project as calculated on the Engineering Division Cost Estimate form. [City of Puyallup Resolution No. 2098]
• Benchmark and monumentation to City of Puyallup datum (NAVD 88) will be required as a part of this project / plat.
• Engineering plans submitted for review and approval shall comply with City Standards Section 1.0 and Section 2.0, particularly:
- Engineering plans submitted for review and approval shall be based on 24 x 36-inch sheets.
- The scale for design plans shall be indicated directly below the north arrow and shall be only 1”=20’ or 1”=30’. The north arrow shall point up or to the right on the plans.
- Engineering plan sheets shall be numbered sequentially in this manner: Sheet 1 of 20, Sheet 2 of 20, etc. ending in Sheet 20 of 20.
• All applicable City Standard Notes and Standard Details shall be included on the construction plans for this project. A copy of the City Standards can be found on the City’s web site under City Engineering, Development Engineering.
• Prior to Acceptance/Occupancy, Record Drawings shall be provided for review and approval by the City. The fee for this review is $200.00. Record Drawings shall be provided as follows:
- In accordance with City Standards Manual Section 2.3.
- Electronic version of the record drawings in the following formats:
1. AutoCAD Map 2007 or newer in State Plane South Projection
2. PDF
|
|
|
Engineering Traffic Review
|
Revisions Required
|
06/28/2022
|
07/06/2022
|
|
|
|
Other/Miscellaneous
Traffic scoping worksheet will be required. City policy requires the project trips to be estimated using the Institute of Transportation Engineers’ (ITE) Trip Generation, 11th Edition. In general, trip generation regression equations shall be used when the R2 value is 0.70 or greater. For single-family units and offices smaller than 30,000 SF, use ITE’s Trip Generation, average rate. The project trips shall be rounded to the nearest tenth.
Vehicle trip credits would be allowed for previous cold storage land use.
Trip generation assumptions need to demonstrate worst-case scenario land use to accurately capture possible traffic impacts particularly if no end user or use is specified and there is no known mechanism to constrain land uses. For warehouse projects with no end user or uses, the City of Puyallup has been using the ITE land use code 155, high cube fulfillment center, for the purposes of assessment of traffic impacts for warehouse development projects.
-Further discussion needed with City on how traffic impact fees would be paid.
Once the traffic scoping worksheet is reviewed, a written response would be sent to the applicant’s traffic engineer outlining the scope of the project’s Traffic Access and Impact Study (TAIS).
The City has adopted a City-Wide Traffic Impact Fee of $4,500 per PM peak hour trip and shall be paid prior to building permit issuance.
Park impact fee was established by Ordinance 3142 dated July 3, 2017 and shall be charged $0.87 per building sqft and shall be paid prior to building permit issuance.
Per Puyallup Municipal Code Section 11.08.135, the applicant/owner would be expected to construct half-street improvements including curb, gutter, planter strip, sidewalk, roadway base, pavement, and street lighting. The extent of paving would be determined based on current condition. Any existing improvements which are damaged now or during construction, or which do not meet current City Standards, shall be replaced. Based on the materials submitted, the applicant would be expected to construct half-street improvements on the following streets:
-15th St SE is classified as a Minor Arterial and shall consist of curb, gutter, 8’ sidewalks, 10ft planter strip, and streetlights. The improvements shall be from street centerline. Assuming a symmetrical cross section, additional right-of-way (ROW) on 15th St SE may need to be dedicated to the city.
15th St SE along the site is designated as a Minor Arterial. City standards (Section 101.10.1) require minimum spacing of 300 feet from the intersection & driveways measured between closest edges of the driveway.
-Per City standards, commercial driveways must be aligned with intersections/driveways across the street.
-Existing driveway near BNSF at-grade crossing will be removed or possibly used for EV access (feasibility needed)
Access restrictions may be necessary if City Standards are not met.
Coordination with BNSF needed regarding the commercial spur
-Consistency with their future plans, Siding capacity, etc.
-Possible safety upgrades at traffic signal (advanced preemption).
During preliminary site plan review a sight distance analysis may be required ensure drive locations meet City standards.
This commercial/industrial development shall provide an AutoTurn analysis for the largest anticipated vehicle that would access the site (WB-67, fire apparatus). Curb radii and entrance dimensions shall be increased as necessary to allow vehicles to access the site without encroaching into adjacent lanes of traffic.
City standard commercial driveway shall be required along frontage. Minimum commercial driveway width is 30ft with 35ft radius.
|
|
|
External Agency Review
|
No Comments
|
06/28/2022
|
07/06/2022
|
|
|
|
|
Building Review
|
Revisions Required
|
06/28/2022
|
07/05/2022
|
|
|
|
Other/Miscellaneous
Response to question #8
The Building department views BNSF railroad as private property. The building code provides clear definition of Yard or open space (507.2) so the City would not considered the railroad ROW to utilize as part of calculation of meeting the required 60 ft. yard unlimited building area. If BNSF agreed to either of the proposed site plan we could consider documentation from them to view it to meet the 2018 IBC.
General comments:
• A separate demolition permit will be required for the demo of the existing structures currently on the site and will require documentation from the Puget Sound Clean Air agency at the time of submittal for the Demo permit.
• Building plans will need to be complete with all building, mechanical, plumbing, energy code items and accessibility requirements that apply to project.
• If applicable, truss specs will also be required with the truss engineers’ stamps and a layout that matches the submitted plans at the time of submittal.
• Electric Vehicle Charging Infrastructure are required in place for charging stations per IBC section 429 Washington State amendments for occupancy B and will need to be shown on the plans.
• Plans will need to be per the applicable codes 2018 adopted February 1, 2021 for all permits.
• All electrical is permitted by the Washington State Department L & I.
• Accessible parking and access to the public way will be required. For all accessible requirements the City adopted the 2018 IBC / WAC 51-50 and the ICC A117.1-2009 standard. One electric vehicle charging infrastructure is required.
• Depending on what type of use is proposed or potential manufacturing it may require approval from Department of Health prior to release of building permit.
• Please reach out to me if I can answer any other questions in relationship to Building code items for this project. No other Building items at this time.
|
|
|
Fire Review
|
Revisions Required
|
06/28/2022
|
06/24/2022
|
|
|
|
Other/Miscellaneous
Codes
• http://www.cityofpuyallup.org/325/Permit-Support-Services
• IFC 2018 Edition and the referenced standards shall be utilized: subject to state adoption.
Notes
2018 IFC and referenced standards are current at the time of this meeting. Based on City of Puyallup Municipal Codes fire sprinkler and fire alarm systems shall be required.
Fire Sprinklers and Hydrants:
The fire sprinkler system shall be designed and install per NFPA 13
A Water Availability/ Fire flow Letter shall be required.
Based on the type of construction and the size of the largest structure and including a 75% reduction for having a fire sprinkler system, the fire flow requirement is per IFC and IFC Appendix B.
Fire Hydrants shall be at least 50’ from the structure and the FDC supporting the fire sprinkler system shall be no closer than 10’ and no greater than 15’ from the hydrant.
Structures requiring more than 2500 GPM require the fire mains to be looped.
Fire hydrants are required by the Code, and each shall be a minimum of 50’ away from the building. Hydrants will be addressed at “Civils”.
Fire Alarm: The City of Puyallup Municipal Code requires the fire alarm system to be designed and installed to “Total Coverage” per NFPA 72.
A UL Certificate shall be required for the fire alarm system.
Fire Access: The fire access road (lane) shall be a minimum of 20’, 26’ in front of hydrants and 26’ if the building is over 30’ in height. An aerial fire apparatus access road may be required.
Building or facilities exceeding 30’ or 3 stories in height shall have at least 2 means of fire apparatus for each structure.
The entrances shall meet ladder truck fire apparatus truck turning radiuses and approval of the angle of inclination.
Maximum road grade shall be 10%
Comply with 2018 IFC section 510 Emergency Responder Radio Coverage.
Knox box required, provide compatibly with Central Pierce Fire and Rescue.
Questions 13 from McKenzie: Provide auto turn information for evaluation with the preliminary site plan.
Railroad spur revisions were presented in the meeting. Applicants will need to follow up with the city for fire access clarification. An email has been sent to CPFR to review operational concerns related to the railroad spur revisions.
|
|
|