CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

F-21-0083


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

F-21-0083
Fire Alarms
Closed
PUYALLUP SCH DIST #3
Replacement
(408) FIRE ALARMS ~ FERRUCCI JHS
07/07/2021
11/10/2021
04/22/2023
10/24/2022

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 08/16/2021

Fees

Paid Fees Amount Paid Owing Date Paid
Legacy Fee $727.50 $727.50 Paid 09/07/2021
No
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Alarm Final Inspection Partial Pass 3/9/2022 03/10/2022
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Partial Pass 3/9/2022 03/10/2022
David Drake ((253) 864-4171)
Corrections:


Fire Alarm
Outstanding
03/10/2022
Test

Fire Alarm Test Inspection Failed 09/04/2022
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Carried Forward
09/04/2022
Fire Alarm 3rd floor Strobes at stair lobby not working Room 118 no strobe Exterior horn/strobe at portables not working Low Voltage approval from LnI M2-67 Not functioning

Fire Alarm Test Inspection Partial Pass 9/20/2022 09/21/2022
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Carried Forward
09/21/2022
Fire Alarm 3rd floor Strobes at stair lobby not working Room 118 no strobe Exterior horn/strobe at portables not working Low Voltage approval from LnI M2-67 Not functioning

Other/Miscellaneous
Carried Forward
09/21/2022
1. Complete change of address on devices above ceiling 3 noted during inspection. 2. Monitoring of Emergency Radio system required, testing to be completed prior to Final.

Fire Alarm Cover Inspection VOID 10/24/2022
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Passed 9/28/2022 10/24/2022
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
09/21/2022
Fire Alarm 3rd floor Strobes at stair lobby not working Room 118 no strobe Exterior horn/strobe at portables not working Low Voltage approval from LnI M2-67 Not functioning

Other/Miscellaneous
Outstanding
09/21/2022
1. Complete change of address on devices above ceiling 3 noted during inspection. 2. Monitoring of Emergency Radio system required, testing to be completed prior to Final.

Fire Alarm Final Inspection Passed 9/28/2022 10/24/2022
David Drake ((253) 864-4171)

Conditions

Condition Status Category
New Fire Alarm System Conditions Resolved Standard Conditions
1- APPOINTMENT REQUIRED FOR ALL INSPECTIONS 2- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION. 3- COMPLETE LABOR AND INDUSTRIES INSPECTIONS PRIOR TO REQUESTING CITY INSPECTION. 4- REMOTE ANNUNICATOR MUST BE LOCATED INSIDE THE BUILDING. 5- EXTERIOR FIRE BELL REQUIRED OUTSIDE FIRE SPRINKLER ROOM. 6- DEVICE MAPS REQUIRED AT THE ANNUNCIATOR AND FIRE ALARM PANEL PRIOR TO CALLING IN FINAL. THE ANNUNCIATOR MAP WILL NEED TO BE WEATHER PROOF. 7- TOTAL COVERAGE IS REQURED; SUBJECT TO FIELD INSPECTION. COMPLY WITH NFPA 72, 2013 8- FIRE ALARM SYSTEM SHALL BE PLACARDED PER NFPA 72. THE UL CERTIFICATE SHALL BE POSTED AT TIME OF FINAL INSPECTION. THE SYSTEM WILL NEED TO BE UL CERTIFIED. 9- A PRE-TEST SHALL BE CONDUCTED AND A PRINT OUT OF THE LOCATION OF THE DEVICE, POINT NUMBER AND DESCRIPTOR SHALL BE FURNISHED TO THE INSPECTOR AT FINAL. 10- FIRE SPRINKLER TAMPER VALVES AND PIV WILL BE REQUIRED TO BE TESTED AT INSPECTION. FIRE SPRINKLER CONTRACTOR TO BE ONSITE. 11- THE CITY OF PUYALLUP ALLOWS ONE FACP PER BUILDING. THE PANEL WILL NEED TO BE LARGE ENOUGH TO HANDLE MULTIPLE TENTANTS IF APPLICABLE. INSPECTION REQUEST CODES: 5302 FIRE ALARM TEST INSPECTION 5303 FIRE ALARM FINAL INSPECTION SCHEDULE YOUR INSPECTION BY PHONE OR ONLINE THROUGH THE CITY OF PUYALLUP ONLINE PERMIT SYSTEM. THEN CALL MORNING OF INSPECTION BETWEEN 7AM - 8AM TO SET UP A TIME. CONTRACTOR MUST BE PRESENT. HTTPS://SECURE.CITYOFPUYALLUP.ORG/ INSPECTION LINE 1-877-232-6456 (USE MUTE TO AVOID BACKGROUND NOISE) DAVID DRAKE AT 253-864-4171 OR RAY COCKERHAM AT 253-841-5585

Related Permit & Planning Applications

Reference Number Status Type
E-20-0612 Permit(s) Issued Civil Construction Permit
B-20-0993 Permit(s) Issued Commercial - Addition
PRFS20221060 Closed Fire Sprinklers
PRSG20230064 Closed Sign/Awning
PRPF20230822 Expired Pre-Fabricated Building

Documents & Images

Date Uploaded File Type Name
08/09/2022 Letter Permit Expiration Notice


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.