| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Fire Review
|
Approved
|
12/19/2025
|
12/15/2025
|
|
|
|
|
Planning Review
|
Approved
|
12/19/2025
|
12/10/2025
|
|
|
|
|
Design Review
|
VOID
|
12/19/2025
|
12/10/2025
|
|
|
|
|
Engineering Traffic Review
|
Approved
|
12/19/2025
|
12/09/2025
|
|
|
|
|
Engineering Review
|
Approved
|
12/19/2025
|
12/09/2025
|
|
|
|
|
Engineering Review
|
Approved
|
11/18/2025
|
11/17/2025
|
|
|
|
|
Fire Review
|
Approved
|
11/18/2025
|
11/14/2025
|
|
|
|
|
Building Review
|
Failed
|
11/18/2025
|
11/12/2025
|
|
|
|
|
|
See Document Markup
Accessibility falls under the 2017 Washington State Accessibility Code (ICC A117.1-2017 Standard)
|
|
|
See Document Markup
Please include the dimensions showing the minimum and maximum heights and clearances for the grab bars, per Section 609 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
Please note on the plans fixtures and accessories are new and which are existing.
|
|
|
See Document Markup
Please provide a WSEC compliant Lighting Summary Worksheet for the new lighting.
|
|
|
See Document Markup
Verify if fireblocking is required at the concealed space per section 718.2 of the 2021 Washington State Building Code. Existing conditions and layout will determine whether fireblocking is required.
|
|
|
See Document Markup
Verify if fireblocking is required at the concealed space per section 718.2 of the 2021 Washington State Building Code. Existing conditions and layout will determine whether fireblocking is required.
|
|
|
See Document Markup
The height of sales and service counters that are for public use cannot exceed 36" per section 904 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
Exposed pipes under lavatories must be insulated or otherwise configured to protect against contact per section 606.6 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
Fireblocking required to separate vertical wall space from ceiling space.
|
|
|
See Document Markup
Fireblocking required to separate vertical wall space from ceiling space.
|
|
|
See Document Markup
The height of sales and service counters that are for public use cannot exceed 36" per section 904 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
The height of work and dining surfaces cannot exceed 34" per section 902.4 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
The height of sales and service counters that are for public use cannot exceed 36" per section 904 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
The height of work and dining surfaces cannot exceed 34" per section 902.4 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
The height of sales and service counters that are for public use cannot exceed 36" per section 904 of the 2017 Washington State Accessibility Code.
|
|
|
See Document Markup
The height of work and dining surfaces cannot exceed 34" per section 902.4 of the 2017 Washington State Accessibility Code.
|
|
Engineering Traffic Review
|
Approved
|
11/18/2025
|
10/30/2025
|
|
|
|
|
Planning Review
|
Approved
|
11/18/2025
|
10/29/2025
|
|
|
|
|
Design Review
|
VOID
|
11/18/2025
|
10/29/2025
|
|
|
|
|
Building Review
|
Pending
|
12/19/2025
|
|
|
|
|