Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Alarm Final Inspection | Failed | 6/15/2022 | 6/17/2022 | 06/17/2022 |
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Carried Forward
06/17/2022
1) Post floor plan at annunciator (provide N arrow, provide riser location, provide room areas that match the device addresses)
2) mount detailed device map near FACP
3) Label Door to FACP
4) Add devices on cloud at bowling lanes; test devices and provide Central Station report for review.
5) Need to load Knox keys with CPFR
Notes: LnI sticker posted on panel, UL Certification posted at Panel, Testing complete.
Tested tampers at vault, PIV, riser and flow circuits at risers
|
||||
Fire Alarm Cover Inspection | VOID | 6/15/2022 | 6/17/2022 | 06/17/2022 |
Ray Cockerham ((253) 841-5585) | ||||
Fire Alarm Final Inspection | Failed | 6/28/2022 | 06/28/2022 | |
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Outstanding
06/17/2022
1) Post floor plan at annunciator (provide N arrow, provide riser location, provide room areas that match the device addresses)
2) mount detailed device map near FACP
3) Label Door to FACP
4) Add devices on cloud at bowling lanes; test devices and provide Central Station report for review. TEST HOOD with Central Station.
5) Need to load Knox keys with CPFR
Notes: LnI sticker posted on panel, UL Certification posted at Panel, Testing complete.
Tested tampers at vault, PIV, riser and flow circuits at risers
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
New Fire Alarm System Conditions | Open | Standard Conditions | |||
:
1- Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. Inspections are Monday - Thursday, no friday inspections
2- Provide plans and permit on site for inspection.
3- Complete labor and industries inspections prior to requesting city inspection.
4- A remote annunciator located at the main entrance is required. If there is an existing annunciator on the exterior of the building it will need to be moved inside the main entrance. Please contact fire inspector for further information.
5- Exterior fire bell required outside fire sprinkler room.
6- Above ceiling detection is required.
7- Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof.
8- Total coverage is required, subject to field inspection. Comply with NFPA 72, 2013
9- Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified.
10- A pre-test shall be conducted and a printout of the location of the device, point number and descriptor shall be furnished to the inspector at final. Labeling of all devices above and below ceiling required.
11- Fire sprinkler tamper valves and PIV will be required to be tested at inspection. Fire sprinkler contractor to be onsite.
12- RTU’S and smoke dampeners will be required to be tested during inspection.
13- The city of puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable.
14- In existing buildings all above ceiling detection is to remain. Do not remove.
15- Due to unforeseeable construction design, all device locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
There are no related items for this development permit application.
Date Uploaded | File Type | Name |
---|---|---|
03/09/2022 | Receipt | Receipt for transaction:2022-000449 |
03/23/2022 | Permit | Permit - Detailed |
03/23/2022 | Letter | Permit Job Card |
03/23/2022 | Form | Puyallup Fire Alarm Permit Application for Round One TI Buildout (Flattened) |
03/23/2022 | Plans | Round One T_I_ FA-05 (Flattened) |
03/23/2022 | Plans | Round One T_I__Full Set (Stamped) |
03/23/2022 | Plans | Round One TI Buildout Equipment Submittal (Flattened) |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView