Summary

PRFA20220979
Fire Alarms
Closed
LARSON FAMILY PARTNERSHIP
New
Install new potter afc-1000 addressable fire alarm panel in group b occupancy in remodeled building and in existing maintenance bay building. Install initiation and notification to Puyallup and state fire code requirements. Provide fire alarm visual and audible notification on exterior of building and throughout building space within scope. Provide smoke detection and pull stations throughout. Building is sprinkled. Provide fire alarm central monitoring via Telco Lines.
06/17/2022
07/01/2022
12/25/2023
06/28/2023

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 07/07/2022 07/01/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (New) Fee $587.50 $587.50 Paid 06/17/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Alarm Final Inspection Failed 6/21/2023 (1:00 to 2:00) 6/21/2023 06/21/2023
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Outstanding
06/22/2023
1) Provide device graphic at annunciator. 2) Review code for separation from HVAC Email sent 6-22-2023 to E2 RE HVAC separation two options: a) add row of detection and shift devices for manufacturers clearance b) provide NICET designer acceptance of location within 3 feet of the supply diffuser. 3) As-built update for document box and email to City ddrake@puyallupwa.gov

Fire Alarm Cover Inspection VOID 06/28/2023
David Drake ((253) 864-4171)
Piv And Tamper Inspection VOID 06/28/2023
David Drake ((253) 864-4171)

Conditions

Condition Status Department Category Expiration Date Due Date
New Fire Alarm System Conditions Open Standard Conditions
: 1- APPOINTMENT REQUIRED FOR ALL INSPECTIONS 2- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION. 3- COMPLETE LABOR AND INDUSTRIES INSPECTIONS PRIOR TO REQUESTING CITY INSPECTION. 4- A REMOTE ANNUCIATOR LOCATED ON THE EXTERIOR OF THE MAIN ENTRANCE IN A WEATHER PROOF HOUSING REQUIRED. 5- EXTERIOR FIRE BELL REQUIRED OUTSIDE FIRE SPRINKLER ROOM. 6- DEVICE MAPS REQUIRED AT THE ANNUNCIATOR AND FIRE ALARM PANEL PRIOR TO CALLING IN FINAL. THE ANNUNCIATOR MAP WILL NEED TO BE WEATHERPROOF. 7- TOTAL COVERAGE IS REQURED; SUBJECT TO FIELD INSPECTION. COMPLY WITH NFPA 72, 2013 8- FIRE ALARM SYSTEM SHALL BE PLACARDED PER NFPA 72. THE UL CERTIFICATE SHALL BE POSTED AT TIME OF FINAL INSPECTION. THE SYSTEM WILL NEED TO BE UL CERTIFIED. 9- A PRE-TEST SHALL BE CONDUCTED AND A PRINT OUT OF THE LOCATION OF THE DEVICE, POINT NUMBER AND DESCRIPTOR SHALL BE FURNISHED TO THE INSPECTOR AT FINAL. 10- FIRE SPRINKLER TAMPER VALVES AND PIV WILL BE REQUIRED TO BE TESTED AT INSPECTION. FIRE SPRINKLER CONTRACTOR TO BE ONSITE. 11- THE CITY OF PUYALLUP ALLOWS ONE FACP PER BUILDING. THE PANEL WILL NEED TO BE LARGE ENOUGH TO HANDLE MULTIPLE TENTANTS IF APPLICABLE.

Related Permit & Planning Applications

Reference Number Status Type
PRCA20220091 Finaled Commercial - Addition
PRCCP20220092 Closed Civil Construction Permit
PRDE20220927 Closed Demolition
PRFS20221051 Closed Fire Sprinklers
PRSG20221792 Closed Sign/Awning