CITY OF PUYALLUP PERMITTING PORTAL
Development Permit Application Status
PRFA20220979
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Alarm Systems (New) Fee | $587.50 | $587.50 | Paid | 06/17/2022 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $587.50 | $587.50 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Alarm Final Inspection | Failed | 6/21/2023 (1:00 to 2:00) | 6/21/2023 | 06/21/2023 |
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Outstanding
06/22/2023
1) Provide device graphic at annunciator.
2) Review code for separation from HVAC
Email sent 6-22-2023 to E2 RE HVAC separation two options:
a) add row of detection and shift devices for manufacturers clearance
b) provide NICET designer acceptance of location within 3 feet of the supply diffuser.
3) As-built update for document box and email to City ddrake@puyallupwa.gov
|
||||
Fire Alarm Cover Inspection | VOID | 06/28/2023 | ||
David Drake ((253) 864-4171) | ||||
Piv And Tamper Inspection | VOID | 06/28/2023 | ||
David Drake ((253) 864-4171) |
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
New Fire Alarm System Conditions | Open | Standard Conditions | |||
:
1- APPOINTMENT REQUIRED FOR ALL INSPECTIONS
2- PROVIDE PLANS AND PERMIT ON SITE FOR INSPECTION.
3- COMPLETE LABOR AND INDUSTRIES INSPECTIONS PRIOR TO REQUESTING CITY INSPECTION.
4- A REMOTE ANNUCIATOR LOCATED ON THE EXTERIOR OF THE MAIN ENTRANCE IN A WEATHER PROOF HOUSING REQUIRED.
5- EXTERIOR FIRE BELL REQUIRED OUTSIDE FIRE SPRINKLER ROOM.
6- DEVICE MAPS REQUIRED AT THE ANNUNCIATOR AND FIRE ALARM PANEL PRIOR TO CALLING IN FINAL. THE ANNUNCIATOR MAP WILL NEED TO BE WEATHERPROOF.
7- TOTAL COVERAGE IS REQURED; SUBJECT TO FIELD INSPECTION. COMPLY WITH NFPA 72, 2013
8- FIRE ALARM SYSTEM SHALL BE PLACARDED PER NFPA 72. THE UL CERTIFICATE SHALL BE POSTED AT TIME OF FINAL INSPECTION. THE SYSTEM WILL NEED TO BE UL CERTIFIED.
9- A PRE-TEST SHALL BE CONDUCTED AND A PRINT OUT OF THE LOCATION OF THE DEVICE, POINT NUMBER AND DESCRIPTOR SHALL BE FURNISHED TO THE INSPECTOR AT FINAL.
10- FIRE SPRINKLER TAMPER VALVES AND PIV WILL BE REQUIRED TO BE TESTED AT INSPECTION. FIRE SPRINKLER CONTRACTOR TO BE ONSITE.
11- THE CITY OF PUYALLUP ALLOWS ONE FACP PER BUILDING. THE PANEL WILL NEED TO BE LARGE ENOUGH TO HANDLE MULTIPLE TENTANTS IF APPLICABLE.
|
Reference Number | Status | Type |
---|---|---|
PRCA20220091 | Finaled | Commercial - Addition |
PRCCP20220092 | Closed | Civil Construction Permit |
PRDE20220927 | Closed | Demolition |
PRFS20221051 | Closed | Fire Sprinklers |
PRSG20221792 | Closed | Sign/Awning |
Date Uploaded | File Type | Name |
---|---|---|
06/17/2022 | Receipt | Receipt for transaction:2022-001147 |
06/26/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
06/26/2023 | Report | Inspection Report (Fire Alarm Final Inspection) |
07/01/2022 | Plans | 1276C BatteryCalc_AFC-1000 (Stamped) |
07/01/2022 | Plans | 1276C Larson Jeep FAD submittal 6-17-22 (Stamped) |
07/01/2022 | Plans | 1276D Submittal 6_16_23 (Flattened) |
07/01/2022 | Form | City of Puyallup Building Permit Application0 (Flattened) |
07/01/2022 | Permit | Permit - Detailed |
07/01/2022 | Letter | Permit Job Card |
11/06/2022 | Letter | Permit Expiration Notice |