CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFA20230460


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFA20230460
Fire Alarms
Closed
MULTICARE HEALTH SYSTEM
Alteration/Remodel
Modify existing fire alarm system: Existing pre-action system panel and all components to be decommissioned and removed as depicted on demo plan sheet. Provide new 4007ES pre-action system panel and tie-in to existing simplex 4120 network. Provide new suppression releasing appliance and peripherals and addressable modules to monitor pre-action sprinkler points. Provide addressable modules to monitor the existing VESDA system serving the pre-action coverage area.
04/11/2023
05/15/2023
02/26/2024
08/30/2023

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 05/10/2023 05/15/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (Alteration) Fee $230.00 $230.00 Paid 04/11/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

There are no inspections for this development permit application, or you are not authorized to view them.

Conditions

Condition Status Department Category Expiration Date Due Date
New Fire Alarm System Conditions Open Standard Conditions
: • Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Fire alarm system shall be placarded per NFPA 72. • Pre-test shall be conducted with a printout for inspector at time of inspection. • Labeling of all devices above and below ceiling required. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

There are no related items for this development permit application.

Documents & Images

Date Uploaded File Type Name
04/11/2023 Form Fire Code Permit Application 0821_202108241006411506
04/11/2023 Plans Good Sam Hospital - MRI PreAction Rev48 - JCI FA Submittals - 2023-04-05
04/11/2023 Receipt Receipt for transaction:2023-000610
04/12/2023 Plans CALCS_Pages from Good Sam PCT - Rev48 - JCI FA Dwgs - 20230405
04/12/2023 Plans FLOOR PLANS_Pages from Good Sam PCT - Rev48 - JCI FA Dwgs - 20230405-2
05/15/2023 Plans Good Sam PCT - Rev48 - JCI FA Dwgs - 20230405 (Stamped)
05/15/2023 Permit Permit - Detailed
05/15/2023 Letter Permit Job Card