CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFA20240544


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFA20240544
Fire Alarms
Closed
STEP BY STEP FAMILY SUPPORT CENTER
Addition
Addition / modification to an existing fire alarm system. Install automatic / manual fire alarm detection and audible visual notification to the 2 detached greenhouses. These devices will be connected to the existing Farenhyt by Silent Knight addressable fire alarm system located in the adjacent Gateway Building. To include adding 10 smoke detectors, 4 pull stations and 6 horn strobes.
04/02/2024
04/08/2024
02/16/2025
08/20/2024

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
04/04/2024 FIRE ALARM PLANS (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 04/17/2024 04/04/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (Alteration) Fee $230.00 $230.00 Paid 04/02/2024
Fire Code Expedite Review Fee $540.00 $540.00 Paid 04/08/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Piv And Tamper Inspection VOID 04/25/2024
David Drake ((253) 864-4171)
Fire Alarm Cover Inspection VOID 04/25/2024
David Drake ((253) 864-4171)

Conditions

Condition Status Department Category Expiration Date Due Date
New Fire Alarm System Conditions Open Standard Conditions
: • Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • Per the agreement with CPFR and City of Puyallup Building Official, both Green Houses will require Fire Alarm monitoring during events using the agreed upon time frame with CPFR operational permit. • When the Green House is outside of the operational permit usage, the system will be required to be removed and then returned to service during any event under the operational permit period. • Comply with CPFR operational permit and inspection requests. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72. System design is based off agreement with CPFR. • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. A note should be added to the U.L. cert describing the requirements of this system for use. • Pre-test shall be conducted with a printout for inspector at time of inspection. • Labeling of all devices above and below ceiling required. • The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCA20220482 Closed Commercial - Addition

Documents & Images

Date Uploaded File Type Name
04/02/2024 Form APPLICATION FORM
04/02/2024 Letter Incomplete Application Notice
04/02/2024 Receipt Receipt for transaction:2024-000632
04/04/2024 Plans FIRE ALARM PLANS (Stamped)
04/08/2024 Letter Permit - Detailed
04/08/2024 Receipt Receipt for transaction:2024-000697


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.