Summary

PRFS20241876
Fire Sprinklers
Closed
WRI-URS SOUTH HILL LLC
Alteration/Remodel
Survey the existing fire sprinkler system and perform hydraulic calculations to see if existing system can provide Ordinary Hazard Group 2 (Merchantile) protection with the existing Fire Pump taken out of service.
12/06/2024
12/12/2024
08/02/2025
02/03/2025

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
12/12/2024 SPRINKLER PLANS (Stamped)
12/12/2024 SYSTEM CALCULATIONS (Stamped)
12/12/2024 CUT SHEETS (Stamped)
12/12/2024 FLOOR PLAN (Stamped)
Review Type Outcome Est. Completion Date Completed
Fire Review Approved 01/07/2025 12/11/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Building Division Fee (Hourly) $540.00 $540.00 Paid 12/12/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Sprinkler Cover Inspection Passed 12/13/2024 12/13/2024
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs Passed 12/13/2024 12/13/2024 12/13/2024
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Partial Pass 12/13/2024 12/16/2024 12/13/2024
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
12/16/2024
Building owner or representative has engineering corrects that will be required to be completed prior to Final. Storm clean up from Diesel.

Erosion And Sediment Inspection Failed 12/13/2024 12/13/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Carried Forward
12/13/2024
- Verify the floor drain out to storm or sewer. - Dilute, clean, and dry fire room floor. - Vac and jet ALL storm along the west and north side of the building and the outlet to the swale.

Erosion And Sediment Inspection Not Ready 12/16/2024 12/16/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Carried Forward
12/16/2024
- Verify the floor drain out to storm or sewer. - Dilute, clean, and dry fire room floor. - Vac and jet ALL storm along the west and north side of the building and the outlet to the swale.

Erosion And Sediment Inspection VOID 12/16/2024 12/16/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Outstanding
12/16/2024
- Verify the floor drain out to storm or sewer. - Dilute, clean, and dry fire room floor. - Vac and jet ALL storm along the west and north side of the building and the outlet to the swale.

Fire Sprinkler Dry System Trip Test VOID 12/16/2024
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Passed 1/30/2025 02/03/2025
David Drake ((253) 864-4171)

Conditions

Condition Status Category
Fire Sprinkler System (New) Conditions Open Standard Conditions
• Provide plans and permit on site for inspection. • Cover and final inspections are required. • Fire watch is required when sprinkler system is out of service in existing buildings. • Contractor required at all inspections. • Hydro test will be required with the new riser install. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment. • Fire pump will be required to be completely removed along with all related equipment. • Tool kit required at time of final. • NFPA placards required. • In existing buildings all upright fire sprinklers to remain, do not remove. • Fire Riser room will be required to be cleaned prior to inspection. • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20240669 Closed Commercial - Tenant Improvement/Remodel
PRFS20241520 Closed Fire Sprinklers
PRUSR20241577 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRFS20241638 Closed Fire Sprinklers
PRUSR20241718 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRFA20241727 Permit(s) Issued Fire Alarms
PRSG20241748 Closed Sign/Awning

Documents & Images

Date Uploaded File Type Name
12/06/2024 Form APPLICATION
12/12/2024 Plans SPRINKLER PLANS (Stamped)
12/12/2024 Plans SYSTEM CALCULATIONS (Stamped)
12/12/2024 Plans CUT SHEETS (Stamped)
12/12/2024 Plans FLOOR PLAN (Stamped)
12/12/2024 Letter Permit - Detailed
12/12/2024 Receipt Receipt for transaction:2024-002579
12/13/2024 Report Inspection Report (Erosion And Sediment Inspection)
12/16/2024 Report Inspection Report (Erosion And Sediment Inspection)