CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20240669


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20240669
Commercial - Tenant Improvement/Remodel
Closed
WRI-URS SOUTH HILL LLC
Alteration/Remodel
TENANT INTERIOR ALTERATION, EXISTING SPACE, NEW TENANT TO INCLUDE NEW WALLS, FINISHES, FIXTURES, AND PAINT- BOOT BARN
04/22/2024
09/11/2024
09/09/2025

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
06/21/2024 CONSTRUCTION PLAN SET (Stamped)
06/21/2024 WSEC (Stamped)
06/21/2024 PLUMBING FIXTURE WORKSHEET (Stamped)
06/21/2024 WA (Stamped)
Review Type Outcome Est. Completion Date Completed
Building Review Approved 06/21/2024 06/18/2024
Fire Review Approved 06/21/2024 06/13/2024
Engineering Traffic Review Approved 06/21/2024 06/11/2024
Planning Review Approved 06/21/2024 06/10/2024
Engineering Review Approved 06/21/2024 06/06/2024
Building Review Failed 05/24/2024 05/24/2024
Fire Review Approved 05/24/2024 05/22/2024
Engineering Review Approved 05/24/2024 05/13/2024
Engineering Traffic Review Approved 05/24/2024 05/01/2024
Planning Review Approved 05/24/2024 04/30/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 09/11/2024
Building Permit Fee $2,393.75 $2,393.75 Paid 09/11/2024
Mechanical Permit Fee $40.00 $40.00 Paid 09/11/2024
Plumbing Fixtures Fee $39.00 $39.00 Paid 09/11/2024
Plumbing Permit Fee $40.00 $40.00 Paid 09/11/2024
Building Plan Review Fee $1,555.94 $1,555.94 Paid 04/25/2024
Mechanical Plan Review Fee $26.00 $26.00 Paid 04/25/2024
Plumbing Plan Review Fee $51.35 $51.35 Paid 04/25/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 09/11/2024
Resubmittal Fee $180.00 $180.00 Paid 06/05/2024
Building Division Fee (Hourly) $540.00 $540.00 Paid 12/13/2024
Outstanding Fees Amount Paid Owing Date Paid
Sewer System Development ChargeFee - Tenant Improvment/Addition $0.00 $0.00 Not payable Not Paid


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Erosion And Sediment Inspection Partial Pass 10/8/2024 10/08/2024
Jason Little ((253) 244-0387)
Sidesewer Inspection Failed 10/8/2024 10/08/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Carried Forward
10/08/2024
Tie side sewer into main line upstream from the c/o and sample tee. Install a 6" sample tee upstream from the c/o. The c/o riser needs to be replaced. Install cap and adaptors for the risers. Install castings with lids that say sewer. The c/o and sample tee dimension may need to be adjusted to fit within excavation. Maintain separation for casting fitment.

Plumbing Rough In Inspection Partial Pass 10/14/2024 10/14/2024 10/14/2024
Shannon King ((253) 840-6684)
Slab/Insulation Inspection Partial Pass 10/15/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/15/2024
slab pour back approved

Plumbing Rough In Inspection Passed 10/15/2024 10/15/2024 10/15/2024
Monty Johnson ((253) 770-3326)
Frame Inspection Not Ready 10/28/2024 10/28/2024 10/28/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/28/2024
1:complete all bottom track anchors, top track anchors, bracing.

Frame Inspection Partial Pass 10/29/2024 10/29/2024 10/29/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/29/2024
frame at front and middle of store ok to include floating hard lid.

Plumbing Rough In Inspection Partial Pass 10/31/2024 10/31/2024 10/31/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/31/2024
test for back area approved, insulate water lines where needed (hot water) frame back area minus hard lids ok.

Frame Inspection Partial Pass 11/1/2024 11/1/2024 11/01/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
11/01/2024
1:FRAME APPROVED MINUS AREA UNDER AND NORTH OF 2ND RTU FROM THE EAST.

Wallboard / Drywall Inspection Partial Pass 11/5/2024 11/5/2024 11/05/2024
Shannon King ((253) 840-6684)
Frame Inspection Partial Pass 11/6/2024 11/6/2024 11/06/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
11/06/2024
deflection track corrections ok

Plumbing Rough In Inspection Not Ready 11/6/2024 11/6/2024 11/06/2024
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Not Ready 11/6/2024 11/6/2024 11/06/2024
Monty Johnson ((253) 770-3326)
Frame Inspection Passed 11/8/2024 11/8/2024 11/08/2024
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Passed 11/8/2024 11/8/2024 11/08/2024
Monty Johnson ((253) 770-3326)
Mechanical Rough In Inspection Passed 11/8/2024 11/8/2024 11/08/2024
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Passed 11/12/2024 11/12/2024 11/12/2024
Shannon King ((253) 840-6684)
Plumbing Final Inspection Not Ready 12/2/2024 12/2/2024 12/02/2024
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Resolved
12/10/2024
1 ; cancel per contractor at time of inspection. not ready

Plumbing Final Inspection Passed 12/10/2024 12/10/2024 12/10/2024
Ray Cockerham ((253) 841-5585)
Corrections:


Other/Miscellaneous
Resolved
12/10/2024
1 ; cancel per contractor at time of inspection. not ready

Building Final Inspection Failed 12/12/2024 12/12/2024 12/12/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/12/2024
1:provide fire, engineering and electrical final prior to building final 2:complete entrance facade and flatwork

Mechanical Final Inspection Failed 12/12/2024 12/12/2024 12/12/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/12/2024
provide balance report and electrical final.

Ceiling Grid/T-Bar Inspection Not Ready 12/12/2024 12/12/2024 12/12/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/12/2024
1:provide 3 turns on all wires and mech attach diffuser to grid as discussed.

Planning Final Inspection Passed 12/13/2024 12/13/2024
Chris Beale ((253) 841-5418)
Engineering Final Inspection Passed 12/13/2024 12/13/2024 12/13/2024
Jason Little ((253) 244-0387)
Erosion And Sediment Inspection Failed 12/13/2024 12/13/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Carried Forward
12/13/2024
- Dilute, clean, and dry fire room floor. - Vactor and jet ALL storm lines along the west and north side of the building to the outlet at the swale.

Comment Engineering Div Inspection VOID 12/13/2024
Jason Little ((253) 244-0387)
Erosion And Sediment Inspection VOID 12/13/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Outstanding
12/13/2024
- Dilute, clean, and dry fire room floor. - Vactor and jet ALL storm lines along the west and north side of the building to the outlet at the swale.

Sidesewer Inspection Passed 12/13/2024 12/13/2024
Jason Little ((253) 244-0387)
Corrections:


Other/Miscellaneous
Resolved
12/13/2024
Tie side sewer into main line upstream from the c/o and sample tee. Install a 6" sample tee upstream from the c/o. The c/o riser needs to be replaced. Install cap and adaptors for the risers. Install castings with lids that say sewer. The c/o and sample tee dimension may need to be adjusted to fit within excavation. Maintain separation for casting fitment.

Ceiling Grid/T-Bar Inspection Passed 12/16/2024 12/17/2024 12/17/2024
Monty Johnson ((253) 770-3326)
Building Final Inspection Not Ready 12/16/2024 12/17/2024 12/17/2024
Monty Johnson ((253) 770-3326)
Mechanical Final Inspection Failed 12/16/2024 12/17/2024 12/17/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/17/2024
provide balance report

Fire Final Inspection Not Ready 12/16/2024 12/17/2024
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
12/17/2024
Talked with Boot Barn management, Brian Bennett, and Façade contractor. Use the exterior rear door for stocking until life safety is met overhead at front entrance.

Fire Final Inspection Partial Pass 12/19/2024 12/19/2024 12/19/2024
David Drake ((253) 864-4171)
Corrections:


Fire Final
Carried Forward
12/19/2024
1. TCO will be approved for 30 days once Building approval is signed off. 2. Façade must be complete prior to Final. 3. Emergency lighting test required for exterior illumination. 4. Test main entrance EXIT sign as it did not work during the last test. 5. Complete sealing up of Fire Sprinkler Riser room. All penetrations, and venting for old fire pump. The current heating must be able to maintain the room at a minimum of 40 degrees. 6. Complete fire lane stripping no parking along with ped crossing. 7. Install horn strobe on front of building. 8. Shell space requires install of Beam detectors prior to shell approvals. Fire alarm permit was for both spaces. 9. Do not use front door until an approved plan is in motion.

Building Final Inspection Partial Pass 12/20/2024 12/20/2024 12/20/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
12/20/2024
30 day tco ok

Exit Lighting Test Inspection Passed 1/30/2025 02/03/2025
David Drake ((253) 864-4171)
Fire Or Smoke Damper Inspection VOID 02/03/2025
David Drake ((253) 864-4171)
Hydrostatic Test 200Lbs 2Hrs VOID 02/03/2025
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection VOID 02/03/2025
David Drake ((253) 864-4171)
Fire Final Inspection Passed 1/30/2025 02/03/2025
David Drake ((253) 864-4171)
Corrections:


Fire Final
Resolved
02/03/2025
1. TCO will be approved for 30 days once Building approval is signed off. 2. Façade must be complete prior to Final. 3. Emergency lighting test required for exterior illumination. 4. Test main entrance EXIT sign as it did not work during the last test. 5. Complete sealing up of Fire Sprinkler Riser room. All penetrations, and venting for old fire pump. The current heating must be able to maintain the room at a minimum of 40 degrees. 6. Complete fire lane stripping no parking along with ped crossing. 7. Install horn strobe on front of building. 8. Shell space requires install of Beam detectors prior to shell approvals. Fire alarm permit was for both spaces. 9. Do not use front door until an approved plan is in motion.

Building Final Inspection Passed 3/6/2025 03/06/2025
Monty Johnson ((253) 770-3326)
Comment Building Div Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Footing/Setback Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Foundation/Rebar Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Underfloor Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Block Wall Rebar Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Roof Sheathing Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Shear Wall Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Firewall/Firestop Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Energy (Insulation) Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Combination Frame And Rough In Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Re-Roof Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Hydronic Piping Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Gas Test Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Refrigeration Line Test Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Exhaust Hood Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Light Test For Grease Duct Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Exhaust/Vent Fans Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Shower Pan Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Medical Gas Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Slab/Insulation Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)
Mechanical Final Inspection VOID 03/11/2025
Monty Johnson ((253) 770-3326)

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2021 IFC and 2021 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter • In existing buildings all required service and maintenance to be completed prior to inspection for the Fire Alarm, and Fire Sprinkler Systems. • Separate permits required for Fire Alarm and Fire Sprinkler • RTU’S will be required to be tested for shut down with Fire Alarm • Smoke and Fire dampeners will be tested with Fire Alarm. Access doors are required for maintenance and visual inspection. • Fire extinguishers required per code to be installed at time of Fire Final • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
Miscellaneous Condition Open
Development & Permitting Services
A separate sign permit needs to be applied for the facade signage.
Plumbing FUW Utility Service Credit Open Standard Conditions
Engineering Division
14.5 of the 26.5 available sewer credits from PRDE20240877 have been redeemed on PRCTI20240669. 12 sewer credits remain for future development projects. See emails attached under Plumbing Fixture Worksheet submittal. [Yianni Charitou @ 07/01/2024 7:34 AM]
Ready to Issue - Need Business License Endorsement Resolved Prior to Issuance
Development & Permitting Services
Contractor needs to have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
Ready to Issue - Need Contractor Info Resolved Prior to Issuance
Development & Permitting Services
Must provide Contractor doing the work to be named on permit. Contractor must be registered with Washington State Labor and Industries AND have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.

Related Permit & Planning Applications

Reference Number Status Type
PRFS20241520 Closed Fire Sprinklers
PRUSR20241577 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRFS20241638 Closed Fire Sprinklers
PRUSR20241718 Closed Utility Service Repair/PRIVATE PROPERTY ONLY
PRFA20241727 Permit(s) Issued Fire Alarms
PRSG20241748 Closed Sign/Awning
PRFS20241876 Closed Fire Sprinklers

Documents & Images

Date Uploaded File Type Name
04/22/2024 Letter Incomplete Application Notice
04/25/2024 Receipt Receipt for transaction:2024-000850
04/25/2024 Form WA MAP
04/25/2024 Report Structural Calcs NA placeholder
05/24/2024 Letter Permit Review Correction Letter
05/24/2024 Form Building Permit Application SIGNED (Flattened)
06/04/2024 Form CORRECTION RESPONSE LETTER
06/05/2024 Receipt Receipt for transaction:2024-001180
06/21/2024 Plans CONSTRUCTION PLAN SET (Stamped)
06/21/2024 Form WSEC (Stamped)
06/21/2024 Form PLUMBING FIXTURE WORKSHEET (Stamped)
06/21/2024 Form WA (Stamped)
07/01/2024 Form RE_ PRDE20240877 Utility Service Credits
07/01/2024 Form RE_ PRDE20240877 Utility Service Credits_2
09/11/2024 Receipt Receipt for transaction:2024-001891
09/11/2024 Permit Permit - Detailed
09/11/2024 Letter Permit Job Card
10/08/2024 Report Inspection Report (Erosion And Sediment Inspection)
10/08/2024 Report Inspection Report (Sidesewer Inspection)
10/14/2024 Report Inspection Report (Plumbing Rough In Inspection)
11/05/2024 Report Inspection Report (Wallboard / Drywall Inspection)
11/12/2024 Report Inspection Report (Wallboard / Drywall Inspection)
12/02/2024 Report Inspection Report (Plumbing Final Inspection)
12/13/2024 Receipt Receipt for transaction:2024-002598
03/06/2025 Report Inspection Report (Building Final Inspection)
03/13/2025 Other Certificate of Occupancy