Summary

PRFS20251604
Fire Sprinklers
Permit(s) Issued
EAST TOWN CROSSING LLC
New
ETC Lot 1 - Fire Sprinkler System - EAST TOWN CROSSING, LOT 1 COMMERCIAL BLDG
12/08/2025
12/31/2025
08/30/2026

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 01/02/2026 12/31/2025

Fees

Paid Fees Amount Paid Owing Date Paid
Automatic Fire-Extinguishing System (New) Permit Fee $349.25 $349.25 Paid 12/31/2025
Automatic Fire-Extinguishing System (New) Plan Review Fee $227.01 $227.01 Paid 12/08/2025
Building Re-Inspection Fee $180.00 $180.00 Paid 03/05/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Fire Sprinkler Dry System Trip Test Pending
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Pending 3/10/2026
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Pending 3/10/2026
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Outstanding
03/03/2026
1. Complete Riser Room walls construction per approved plans. 2. Install Riser Room signage. 3. No fire sprinkler contractor onsite. 4. The Riser Room is a heated room. There is a significant amount of light coming through at the roof deck. This tells me the heat will not protect the Fire Sprinkler Riser or the FACP. 5. Pay reinspection’s prior to scheduling next Finals.

Hydrostatic Test 200Lbs 2Hrs Passed 1/22/2026 1/22/2026 01/23/2026
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Partial Pass 1/22/2026 1/22/2026 01/23/2026
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Failed with Fee 3/2/2026 3/3/2026 03/03/2026
David Drake ((253) 864-4171)
Corrections:


Other/Miscellaneous
Carried Forward
03/03/2026
1. Complete Riser Room walls construction per approved plans. 2. Install Riser Room signage. 3. No fire sprinkler contractor onsite. 4. The Riser Room is a heated room. There is a significant amount of light coming through at the roof deck. This tells me the heat will not protect the Fire Sprinkler Riser or the FACP. 5. Pay reinspection’s prior to scheduling next Finals.

Conditions

Condition Status Category
Fire Sprinkler System (New) Conditions Open Standard Conditions
• Provide plans and permit on site for inspection. • Cover and final inspections are required. • Contractor required at all inspections. • Hydro test will be required on all new and existing buildings. Appointment required. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment • Fire pumps will be required to be tested and witnessed by inspector. • Tool kit required at time of final. • NFPA placards required • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCNC20250094 Permit(s) Issued Commercial - New Construction
PRRWF20251393 Closed Retaining Wall
PRSG20251438 Permit(s) Issued Sign/Awning

Documents & Images

Date Uploaded File Type Name
12/08/2025 Plans FIRE SPRINKLER HYDRAULIC CALULATIONS
12/08/2025 Receipt Receipt for transaction:2025-002313
12/31/2025 Plans FIRE SPRINKLER PLANS (Stamped)
12/31/2025 Plans FIRE SPRINKLER SEISMIC CALCULATIONS (Stamped)
12/31/2025 Plans FIRE SPRINKLER CUT SHEETS (Stamped)
12/31/2025 Letter Permit - Detailed
12/31/2025 Letter Permit Job Card252
12/31/2025 Receipt Receipt for transaction:2025-002473
03/05/2026 Receipt Receipt for transaction:2026-000382


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.