CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRMU20221555


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMU20221555
Residential - New Multi-Unit
Permit(s) Issued
New
North Building of CopperBerry, R-2 Apartments 6 Plex CIVIL: PRCCP20221569 / South building PRMU20221586 - REVISION (1) - 09/11/2023 - POURING A MAXIMUM 7' WALL IN PLACE OF 4' WALL ON WEST SIDE OF FOUNDATION * REV (2) - 12/14/2023 - FOOTING & FOUNDATION NOT NEEDED FOR WEST STAIRCASE LOAD AS PER STURUCTURAL ENGINEER. PEPLACE WITH PIERS AS PER DRAWINGS & CALS
10/06/2022
08/23/2023
09/29/2024

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 01/16/2024 12/27/2023
Engineering Review Approved 10/26/2023 10/02/2023
Building Review Approved 10/26/2023 09/28/2023
Engineering Review Failed 10/16/2023 09/19/2023
Building Review Approved 10/16/2023 09/18/2023
Engineering Review Failed 09/18/2023 09/14/2023
Building Review Approved 09/18/2023 09/13/2023
Building Review Approved 05/02/2023 05/04/2023
Engineering Traffic Review VOID 05/02/2023 05/04/2023
Planning Review Approved 05/02/2023 04/28/2023
Fire Review Approved 05/02/2023 04/26/2023
Engineering Review Approved 05/02/2023 04/06/2023
Planning Review Approved 12/31/2022 01/10/2023
Building Review Failed 12/31/2022 01/05/2023
Fire Review Failed 12/31/2022 01/05/2023
Engineering Review Approved 12/31/2022 11/29/2022
Engineering Traffic Review VOID 12/31/2022 11/16/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 08/21/2023
Planning Landscape Review Fee $300.00 $300.00 Paid 08/21/2023
Appliance Vent - Separate Fee $57.60 $57.60 Paid 08/21/2023
Exhaust Hood/Range Hood - Residential Fee $84.60 $84.60 Paid 08/21/2023
Exhaust Vent Fan (Bath) Fee $253.80 $253.80 Paid 08/21/2023
Suspended, Recessed Wall, or Floor unit Heater Fee $234.60 $234.60 Paid 08/21/2023
Building Permit Fee $7,433.75 $7,433.75 Paid 08/21/2023
Planning Building Permit Fee $120.00 $120.00 Paid 08/21/2023
Garbage Disposal Fee $78.00 $78.00 Paid 08/21/2023
Plumbing Permit Fee $40.00 $40.00 Paid 08/21/2023
Plumbing Fixtures Fee $884.00 $884.00 Paid 08/21/2023
Water Heater Fee $78.00 $78.00 Paid 08/21/2023
Mechanical Permit Fee $40.00 $40.00 Paid 08/21/2023
Building Plan Review Fee $8,390.69 $8,390.69 Paid 10/06/2022
Plumbing Plan Review Fee $1,386.45 $1,386.45 Paid 10/06/2022
Mechanical Plan Review Fee $1,402.21 $1,402.21 Paid 10/06/2022
WA State Building Code Council Fee (Residential) $16.50 $16.50 Paid 08/21/2023
Building Plan Review Fee $4,831.94 $4,831.94 Paid 12/29/2022
Plumbing Plan Review Fee $702.00 $702.00 Paid 08/21/2023
Mechanical Plan Review Fee $435.89 $435.89 Paid 08/21/2023
Resubmittal Fee $130.00 $130.00 Paid 03/31/2023
Resubmittal Fee $180.00 $180.00 Paid 09/11/2023
Resubmittal Fee $180.00 $180.00 Paid 09/27/2023
Resubmittal Fee $180.00 $180.00 Paid 12/15/2023
Outstanding Fees Amount Paid Owing Date Paid
Sewer System Development Charge $30,134.00 $0.00 $30,134.00 Not Paid
Traffic Impact Fee (Commercial) $21,600.00 $0.00 $21,600.00 Not Paid
Park Impact Fee $19,747.86 $0.00 $19,747.86 Not Paid


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$71,481.86    Add Fees to My Cart

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Block Wall Rebar Inspection Pending
Shannon King ((253) 840-6684)
Shear Wall Inspection Pending
Shannon King ((253) 840-6684)
Plumbing Rough In Inspection Pending
Shannon King ((253) 840-6684)
Energy (Insulation) Inspection Pending
Shannon King ((253) 840-6684)
Ceiling Grid/T-Bar Inspection Pending
Shannon King ((253) 840-6684)
Wallboard / Drywall Inspection Pending
Shannon King ((253) 840-6684)
Gas Test Inspection Pending
Shannon King ((253) 840-6684)
Mechanical Rough In Inspection Pending
Shannon King ((253) 840-6684)
Refrigeration Line Test Inspection Pending
Shannon King ((253) 840-6684)
Light Test For Grease Duct Inspection Pending
Shannon King ((253) 840-6684)
Exhaust/Vent Fans Inspection Pending
Shannon King ((253) 840-6684)
Fire Or Smoke Damper Inspection Pending
David Drake ((253) 864-4171)
Cover Inspection/Thrust Blocks Inspection Pending
Hydrostatic Test 200Lbs 2Hrs Pending
David Drake ((253) 864-4171)
Emergency Radio Test Review Inspection Pending
David Drake ((253) 864-4171)
Job Start Inspection Pending
Engineering Daily Inspection Pending
Engineering Final Inspection Pending
Planning Final Inspection Pending
Fire Final Inspection Pending
David Drake ((253) 864-4171)
Plumbing Final Inspection Pending
Shannon King ((253) 840-6684)
Mechanical Final Inspection Pending
Shannon King ((253) 840-6684)
Building Final Inspection Pending
Shannon King ((253) 840-6684)
Storm Inspection Pending
Water Service Inspection Pending
Comment Engineering Div Inspection Pending
Sidesewer Inspection Pending
Frame Inspection Pending
Shannon King ((253) 840-6684)
Slab/Insulation Inspection Pending
Shannon King ((253) 840-6684)
Footing/Setback Inspection Pending
Shannon King ((253) 840-6684)
Firewall/Firestop Inspection Pending
Shannon King ((253) 840-6684)
Other/Miscellaneous
Outstanding
04/02/2024
1 ; talked with contractor about rated 1 hours walls in attic. (complete as per city approved plans ) not ready

Other/Miscellaneous
Outstanding
04/02/2024
1. complete drywall as discussed with contractor 2. provide letter from architect to support assembly being used

Erosion And Sediment Inspection Passed w/ Conditions 9/8/2023 9/8/2023 09/08/2023
Jason Little ((253) 435-3636)
Comment Building Div Inspection Not Ready 9/8/2023 9/8/2023 09/08/2023
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
09/08/2023
1.cancelled by contractor

Comment Building Div Inspection Not Ready 9/12/2023 9/12/2023 09/12/2023
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
09/12/2023
1.cancelled by contractor

Other/Miscellaneous
Carried Forward
09/12/2023
1 ; meet on-site with contractor to discuss footing is a min. 45 degrees away from sewer as required per code. (no footings installed and not able to verify sewer location and depth due to back filled at time of inspection. 2 ; contractor will need to provide plan revision for foundation design at rear wall of building and pot hole sewer location as rear corner of building to check 45 degree from footing to sewer at footing inspection.(contractor could have a licensed surveyor mark location of sewer with with elevation of bottom of footing and sewer )

Foundation/Rebar Inspection Not Ready 10/17/2023 10/17/2023 10/17/2023
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
10/17/2023
1 ; cancel per scott

Foundation/Rebar Inspection Failed 10/20/2023 10/20/2023 10/20/2023
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
10/20/2023
1 ; cancel per scott

Other/Miscellaneous
Carried Forward
10/20/2023
1 ; provide Geo-tech approval for soil bearing requirement of 1,500 psf as required per City approved plans. 2 ; inspection of footings only.(no pier pads or stair footings)

Storm Inspection Partial Pass 11/7/2023 11/07/2023
Jason Little ((253) 435-3636)
Sidesewer Inspection Partial Pass 11/7/2023 11/07/2023
Jason Little ((253) 435-3636)
Water Service Inspection Partial Pass 11/7/2023 11/07/2023
Jason Little ((253) 435-3636)
Comment Engineering Div Inspection Not Ready 11/8/2023 11/8/2023 11/08/2023
Jason Little ((253) 435-3636)
Sidesewer Inspection Partial Pass 11/8/2023 11/08/2023
Jason Little ((253) 435-3636)
Other/Miscellaneous
Carried Forward
11/08/2023
Need to install a plug in both side sewers to keep construction debris out during build.

Comment Building Div Inspection Not Ready 11/14/2023 11/14/2023 11/14/2023
Shannon King ((253) 840-6684)
Other/Miscellaneous
Resolved
11/14/2023
1.cancelled by contractor

Other/Miscellaneous
Resolved
11/14/2023
1 ; meet on-site with contractor to discuss footing is a min. 45 degrees away from sewer as required per code. (no footings installed and not able to verify sewer location and depth due to back filled at time of inspection. 2 ; contractor will need to provide plan revision for foundation design at rear wall of building and pot hole sewer location as rear corner of building to check 45 degree from footing to sewer at footing inspection.(contractor could have a licensed surveyor mark location of sewer with with elevation of bottom of footing and sewer )

Underfloor Inspection Not Ready 11/17/2023 11/17/2023 11/17/2023
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
11/17/2023
1. provide city approved plans on site for inspection 2.provide access to rim at common wall to verify fastening of rim and fastener itself 3. not ready

Frame Inspection Not Ready 11/21/2023 11/21/2023 11/21/2023
Shannon King ((253) 840-6684)
Underfloor Inspection Failed 11/21/2023 11/21/2023 11/21/2023
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
11/21/2023
1. provide city approved plans on site for inspection 2.provide access to rim at common wall to verify fastening of rim and fastener itself 3. not ready

Other/Miscellaneous
Carried Forward
11/21/2023
1 ; complete a34's at post to pad connection as per city approved plans. 2 ; complete anchor bolts with-in 12'' of plate break at east wall. 3 ; complete install of all hangers prior to next inspection. 4 ; complete all point loads as per city approved plans not ready

Slab/Insulation Inspection Not Ready 11/22/2023 11/22/2023 11/22/2023
Shannon King ((253) 840-6684)
Footing/Setback Inspection Failed 1/25/2024 1/25/2024 01/25/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
01/25/2024
INSP FOR STAIR FOOTINGS, DECK FOOTINGS 1: provide site plan and special inspector reports.

Footing/Setback Inspection Partial Pass 1/26/2024 1/26/2024 01/26/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
01/26/2024
stair and deck footings ok

Footing/Setback Inspection Partial Pass 1/31/2024 1/31/2024 01/31/2024
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
01/31/2024
foundation wall for ext stairs ok

Firewall/Firestop Inspection Not Ready 3/27/2024 3/27/2024 03/27/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/27/2024
1 ; talked with contractor about rated 1 hours walls in attic. (complete as per city approved plans ) not ready

Firewall/Firestop Inspection Not Ready 4/2/2024 4/2/2024 04/02/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
04/02/2024
1 ; talked with contractor about rated 1 hours walls in attic. (complete as per city approved plans ) not ready

Other/Miscellaneous
Carried Forward
04/02/2024
1. complete drywall as discussed with contractor 2. provide letter from architect to support assembly being used

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Engineering Commercial Standard Conditions Open Standard Conditions
: Development Engineering standard commercial conditions: ** Concerning the resubmittal recieved by the City on 09/28/2023 - The approval of this drawing is for the area of influence of the foundation to the existing sewer main that is west of the proposed building. It is has not been reviewed for the construction of the retaining wall. See sheet C2.0 2 ** - Prior to starting site work request an inspection for erosion and sediment. - Occupancy will not be granted until all civil work associated with PRCCP20221569 has been completed and approval has been provided. - Sediment control and erosion procedures shall be practice to eliminate and prevent off site damage. Stormwater runoff originating upgrade of exposed areas shall be controlled to reduce erosion and sediment loss during the period of exposure. Attached to the site plan is the city of puyallup’s stormwater fact sheet. or See approved civil plan PRCCP20221569 for approved method of control. - Stormwater control of roof downspouts required. See Civil Permit PRCCP20221569 - All commercial development, multi-family, mixed use facility,or irrigation systems water service connections must have installed an approved backflow prevention assembly installed as directed by the Puyallup Municipal Code 14.02.220(3) and conforming to city standard section 03.04 - backflow installation. A double detector check valve assembly (DDCVA) is required or A reduced pressure backflow assembly (RPBA) is required as directed by the City of Puyallup, Fruitland Mutual Water Company, Tacoma City Water or Valley Water District. - The applicant is responsible to schedule all utility inspections prior to backfilling - Curb, gutter, sidewalk and approach must be poured per city standards. See Civil Permit PRCCP20221569 - Driveway approach must be a minimum of 30' wide. See Civil Permit PRCCP20221569 - The builder/owner shall be responsible for keeping the existing right-of-way free of debris and dirt. Any violation of PMC chapter 21.14 pertaining to clearing, filling and grading, erosion and sediment control, and storm water discharges shall be prosecuted to the fullest extent of the law.- Any addition/expansion to the footprint of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. - The applicant is responsible to call the utility notification center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law. - No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit. - A separate right of way permit must be obtained is required by a licensed and bonded contractor to make the sanitary sewer main tap. See Civil Permit PRCCP20221569 - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Miscellaneous Condition Resolved Engineering Division Prior to Issuance
: Civil permit Development Engineering standard commercial conditions: Civil permit PRCCP20221569 must be issued prior to the issuance of this permit The site plans of this permit and civil permit PRCCP20221569 must be compared prior to issuance CIVIL PERMIT ISSUED ON 8/15/23 [Robyn Buck @ 08/15/2023 3:59 PM]
Miscellaneous Condition Open Engineering Division Prior to Occupancy
: Civil permit Civil permit Development Engineering standard commercial conditions: All work permited under civil permit PRCCP20221569 must be completed prior to occupancy
Fire Review Conditions Open Development & Permitting Services Standard Conditions
: • Comply with 2018 IFC and 2018 IBC • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Separate permits required for Fire Alarm and Fire Sprinkler • Fire Alarm is required to monitor the Fire Sprinkler System and required under the City Municipal Code for Total Coverage. • See separate conditions for Fire Sprinkler and Fire Alarm. • A Knox box is required at the riser room on the exterior of the building. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Fire Sprinkler System (New) Conditions Open Development & Permitting Services Standard Conditions
: • Provide plans and permit on site for inspection. • Cover and final inspections are required. • Fire watch is required when sprinkler system is out of service in existing buildings. • Contractor required at all inspections. • Hydro test will be required on all new and existing buildings. Appointment required. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment • Fire pumps will be required to be tested and witnessed by inspector. • Tool kit required at time of final. • NFPA placards required • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
New Fire Alarm System Conditions Open Development & Permitting Services Standard Conditions
:
Miscellaneous Condition Resolved Planning Division Prior to Issuance
: Buildings cannot cross parcel lines even when owned by the same property owner. A lot combination will be required. Lot combinations are an administratively approved permit that also requires a review and recording with the County. An approved lot combination will be required before issuance of the building permit. I have attached a link to the lot combination application below: https://www.cityofpuyallup.org/DocumentCenter/View/11646/Lot-Combination-Application Good morning, This condition can be resolved for both building permits for the Copperberry Condominiums as we will no longer require the lot combination. Thank you, Nabila Comstock (she/her) Assistant Planner | City of Puyallup
Miscellaneous Condition Resolved Development & Permitting Services Prior to Issuance
: NEED SCHOOL IMPACT FEES PAID PRIOR TO ISSUANCE [Julie Johnson @ 05/12/2023 4:18 PM] OK FOR SCHOOL IMPACT FEES TO BE PART OF FEE DEFERRAL AND WILL BE DUE PRIOR TO RECEIVING BLDG FINAL. BRIAN DEVEARUX(PSD)/JF [Jeannesha Frazier @ 08/23/2023 8:48 AM] /
Miscellaneous Condition Open Development & Permitting Services Prior to Completion
: NO FINAL OCCUPANCY UNTIL DEFERRED FEES ARE PAID & SCHOOL LETTER RECEIVED [Jeannesha Frazier @ 08/23/2023 11:32 AM]

Related Permit & Planning Applications

Reference Number Status Type
PRCCP20221569 Permit(s) Issued Civil Construction Permit
PRMU20221586 Permit(s) Issued Residential - New Multi-Unit
PRFUP20231150 Closed Franchise Utility Permit
PRFA20240334 Permit(s) Issued Fire Alarms
PRFA20240335 Permit(s) Issued Fire Alarms
PRFS20240551 Permit(s) Issued Fire Sprinklers
PRFS20240552 Permit(s) Issued Fire Sprinklers
P-21-0096 File Closed Preliminary Site Plan
P-21-0014 File Closed Pre-Application

Documents & Images

Date Uploaded File Type Name
05/12/2023 Report Structural report_Copperberry North Building - RESUB (Stamped)
05/09/2023 Form 21_136 - 2018 WSEC - Copperberry Condominiums - RESUB (Stamped)
05/08/2023 Plans PHS21_136 - Bill Riley - Copperberry Condominiums - 6 - R2 - Site Overview North and South Building - RESUB (Stamped)
05/12/2023 Plans PHS21.136 - Bill Riley - Copperberry Condominiums - North Building - RESUB (Stamped)
12/29/2022 Receipt Receipt for transaction:2022-002497
05/09/2023 Plans J1128349A LAYOUT0 (3) (Stamped)
05/09/2023 Report TRUSS SPECS - ENG STAMP (Stamped)
08/21/2023 Receipt Receipt for transaction:2023-001595
08/23/2023 Permit Permit - Detailed
08/23/2023 Letter Permit Job Card
09/08/2023 Report Inspection Report (Comment Building Div Inspection)
09/11/2023 Receipt Receipt for transaction:2023-001749
09/18/2023 Form REVISION - West Wall Foundation North Building (Flattened)
09/11/2023 Receipt Receipt for transaction:2023-001754
09/12/2023 Report Inspection Report (Comment Building Div Inspection)
10/03/2023 Plans Copperberry4002 10th St SE_RETAINING NORTH BLDG PROFILE 1 AND 2 - REVISION RESUB (Stamped)
09/19/2023 Letter Permit Review Correction Letter
09/27/2023 Receipt Receipt for transaction:2023-001847
10/17/2023 Report Inspection Report (Foundation/Rebar Inspection)
10/31/2023 Report Inspection Report (Foundation/Rebar Inspection)
10/31/2023 Report Inspection Report (Foundation/Rebar Inspection)
11/08/2023 Report Inspection Report (Sidesewer Inspection)
11/14/2023 Plans PRMU20221555 SS ASBUILTS
11/14/2023 Report Inspection Report (Comment Building Div Inspection)
11/21/2023 Report Inspection Report (Frame Inspection)
11/21/2023 Report Inspection Report (Comment Building Div Inspection)
11/21/2023 Report Inspection Report (Underfloor Inspection)
11/22/2023 Report Inspection Report (Slab/Insulation Inspection)
12/28/2023 Plans STRUCTURAL DESIGN (FOUNDATION) REV (2) (Stamped)
12/28/2023 Plans CONSTRUCTION PLAN SET - REV (2) (Stamped)
12/14/2023 Plans CORRECTION RESPONSE LETTER REV (2)
12/15/2023 Receipt Receipt for transaction:2023-002352
03/27/2024 Report Inspection Report (Firewall/Firestop Inspection)
04/02/2024 Report Inspection Report (Firewall/Firestop Inspection)