Summary

PRRRSF20231337
Residential - Remodel/Alteration
Closed
NGANGA RUTH & KABUGI PAUL
Alteration/Remodel
CONVERT GARAGE INTO (3) BEDROOMS, (1) UTILITY ROOM AND LAUNDRY ROOM.PARTITION BEDROOM C TO CREATE A STORAGE ROOM.REMODEL BATHROOM A & B TO ADD A WALK IN SHOWER.CONSTRUCT RAMP. INTERIOR REMODEL IS 700SF * REVISION (1) 2.26.2024 - INSTALL WINDOW IN STORAGE, INSTALL SINKAND DOOR IN BATHROOM B, REMOVE CLOSET IN BEDROOM F, ENTRY INTO CONVERTED GARAGE RELOCATED & OFFICE WALL EXTENDED OUT BY 36".
09/14/2023
10/13/2023
04/30/2025
11/01/2024

Locations

Reviews

Documents Returned For Corrections

Date Returned Name
02/29/2024 CONSTRUCTION PLAN SET - REV (1) (Stamped)
Review Type Outcome Est. Completion Date Completed
Building Review Approved 03/11/2024 02/28/2024
Building Review Approved 10/19/2023 10/06/2023
Building Review Failed 10/06/2023 09/22/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Building Permit Fee $643.75 $643.75 Paid 10/13/2023
Building Plan Review Fee $418.44 $418.44 Paid 09/14/2023
WA State Building Code Council Fee (Residential) $6.50 $6.50 Paid 10/13/2023
Furnace (up to 100,000 BTU) Fee $58.65 $58.65 Paid 10/13/2023
Exhaust Vent Fan (Bath) Fee $14.10 $14.10 Paid 10/13/2023
Mechanical Permit Fee $40.00 $40.00 Paid 10/13/2023
Plumbing Fixtures Fee $26.00 $26.00 Paid 10/13/2023
Plumbing Permit Fee $40.00 $40.00 Paid 10/13/2023
Mechanical Plan Review Fee $73.29 $73.29 Paid 09/15/2023
Plumbing Plan Review Fee $42.90 $42.90 Paid 09/15/2023
Resubmittal Fee $180.00 $180.00 Paid 10/05/2023
Resubmittal Fee $180.00 $180.00 Paid 02/26/2024
Building Re-Inspection Fee $180.00 $180.00 Paid 10/24/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Frame Inspection Partial Pass 11/20/2023 11/20/2023 11/20/2023
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
11/20/2023
1. provide hangers as discussed with contractor 2. ok to sheet floor in garage only 3. this was an underfloor inspection

Energy (Insulation) Inspection Not Ready 1/23/2024 1/23/2024 01/24/2024
Kevin Spruell ((253) 841-5590)
Frame Inspection Not Ready 1/23/2024 1/23/2024 01/24/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
01/24/2024
1. provide hangers as discussed with contractor 2. ok to sheet floor in garage only 3. this was an underfloor inspection

Other/Miscellaneous
Carried Forward
01/24/2024
1. complete all building, plumbing, mech and electrical as discussed with contractor 2. complete nailing of sheeting at garage wall as discussed with contractor 3.not ready

Plumbing Rough In Inspection Not Ready 2/20/2024 2/20/2024 02/20/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
02/20/2024
1. shear at garage wall approved 2.complete all framing plumbing and mech prior to next inspection 3. open wall up at W/D as discussed with contractor 4. not ready

Plumbing Rough In Inspection Partial Pass 3/1/2024 3/1/2024 03/01/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
03/01/2024
1. shear at garage wall approved 2.complete all framing plumbing and mech prior to next inspection 3. open wall up at W/D as discussed with contractor 4. not ready

Other/Miscellaneous
Carried Forward
03/01/2024
insp for two bathrooms 1:seal holes in plates 2:complete framing for floor under shower pans 3:plumbing test ok for bathrooms 4:provide complete set of approved plans to include changes.

Plumbing Rough In Inspection Partial Pass 3/5/2024 3/5/2024 03/05/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Resolved
03/05/2024
1. shear at garage wall approved 2.complete all framing plumbing and mech prior to next inspection 3. open wall up at W/D as discussed with contractor 4. not ready

Other/Miscellaneous
Carried Forward
03/05/2024
1. complete window headers at bedroom D and storage room per city approved plans 2.complete framing at back door and dryer vent and line set area as discussed with contractor 3.complete combustible air at MECH room by final 4. ok to insulate

Combination Frame And Rough In Inspection Partial Pass 3/12/2024 3/12/2024 03/12/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
03/12/2024
1. complete fan at laundry area by final as discussed with contractor 2.all other framing corrections approved 3. ok to cover

Residential Final Inspection Failed 7/29/2024 7/29/2024 07/29/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
07/29/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Residential Final Inspection Not Ready 8/27/2024 8/27/2024 08/27/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
08/27/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Residential Final Inspection Failed 10/23/2024 10/23/2024 10/23/2024
Shannon King ((253) 840-6684)
Corrections:


Other/Miscellaneous
Carried Forward
10/23/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Other/Miscellaneous
Carried Forward
10/23/2024
1 ; nobody on-site at time of inspection. (11:03 am,no access)

Residential Final Inspection Failed with Fee 10/24/2024 10/24/2024 10/24/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/24/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Other/Miscellaneous
Carried Forward
10/24/2024
1 ; nobody on-site at time of inspection. (11:03 am,no access)

Other/Miscellaneous
Carried Forward
10/24/2024
1:entered house only to find personal belongings in house, immediately left house. pay reinspect fee prior to next inspection.

Residential Final Inspection Failed 10/31/2024 10/31/2024 10/31/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/31/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Other/Miscellaneous
Resolved
10/31/2024
1 ; nobody on-site at time of inspection. (11:03 am,no access)

Other/Miscellaneous
Carried Forward
10/31/2024
see insp dated 7/29/24 1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Residential Final Inspection Passed 11/1/2024 11/1/2024 11/01/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
10/31/2024
1. complete caulking around make up air vent outside 2.provide screens at make up air inlets outside 3.complete drywall at washer and dryer area

Comment Building Div Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Comment Engineering Div Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Footing/Setback Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Foundation/Rebar Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Underfloor Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Slab/Insulation Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Shear Wall Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Gas Test Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Mechanical Rough In Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Carbon Monoxide Detectors Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Shower Pan Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Fire Sprinkler Cover Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Fire Sprinkler Final Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Fire Final Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Plumbing Final Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Mechanical Final Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Energy (Insulation) Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Frame Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Corrections:


Other/Miscellaneous
Outstanding
01/24/2024
1. complete all building,plumbing,mech and electrical as discussed with contractor 2. complete nailing of sheeting at garage wall as discussed with contractor 3.not ready

Plumbing Rough In Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Corrections:


Other/Miscellaneous
Outstanding
03/05/2024
1. complete window headers at bedroom D and storage room per city approved plans 2.complete framing at back door and dryer vent and line set area as discussed with contractor 3.complete combustible air at MECH room by final 4. ok to insulate

Combination Frame And Rough In Inspection VOID 12/16/2024
Joyce Kennedy ((253) 841-5405)
Corrections:


Other/Miscellaneous
Outstanding
03/12/2024
1. complete fan at laundry area by final as discussed with contractor 2.all other framing corrections approved 3. ok to cover

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp

Related Permit & Planning Applications

There are no related items for this permit application.

Documents & Images

Date Uploaded File Type Name
09/14/2023 Report STRUCTURAL CALCULATIONS
09/14/2023 Other 2018 Glazing Schedule
09/14/2023 Form 2018 Heating System Sizing Worksheet
09/14/2023 Form Puyallup Building Permit Application
09/14/2023 Receipt Receipt for transaction:2023-001781
09/15/2023 Receipt Receipt for transaction:2023-001786
09/25/2023 Letter Permit Review Correction Letter
10/05/2023 Receipt Receipt for transaction:2023-001907
10/09/2023 Form Permit Review - Comment Responses (Flattened)
10/09/2023 Plans CONSTRUCTION PLAN SET - RESUB (Stamped)
10/09/2023 Form ENERGY CODE WORKSHEETS - RESUB (Stamped)
10/13/2023 Permit Permit - Detailed
10/13/2023 Letter Permit Job Card
11/20/2023 Report Inspection Report (Frame Inspection)
01/24/2024 Report Inspection Report (Frame Inspection)
01/24/2024 Report Inspection Report (Energy (Insulation) Inspection)
02/26/2024 Plans REVISED SCOPE OF WORK POST APPROVAL - REV (1)
02/26/2024 Form REVISION FORM - REV (1)
02/26/2024 Receipt Receipt for transaction:2024-000351
02/29/2024 Plans CONSTRUCTION PLAN SET - REV (1) (Stamped)
03/05/2024 Report Inspection Report (Plumbing Rough In Inspection)
08/27/2024 Report Inspection Report (Residential Final Inspection)
10/23/2024 Report Inspection Report (Residential Final Inspection)
10/24/2024 Receipt Receipt for transaction:2024-002217