CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCNC20220958


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCNC20220958
Commercial - New Construction
Finaled
CITY OF PUYALLUP
New
1,200SF park restroom structure renovation/ addition at City of Puyallup's Pioneer Park
06/14/2022
02/14/2023
09/22/2024
02/08/2024

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 02/10/2023 01/23/2023
Planning Review Approved 02/10/2023 01/17/2023
Engineering Review Approved 02/10/2023 01/13/2023
Engineering Storm Review Approved 02/10/2023 01/12/2023
Building Review Approved 02/10/2023 01/12/2023
Building Review Failed 01/04/2023 01/09/2023
Fire Review VOID 01/04/2023 01/05/2023
Engineering Review Approved 01/04/2023 12/22/2022
Engineering Storm Review Approved 01/04/2023 12/21/2022
Planning Review Approved 01/04/2023 12/15/2022
Planning Review Failed 11/29/2022 12/06/2022
Building Review Approved 11/29/2022 11/30/2022
Engineering Storm Review Failed 11/29/2022 11/28/2022
Fire Review Failed 11/29/2022 11/21/2022
Engineering Review Failed 11/29/2022 11/16/2022
Planning Review Failed 08/09/2022 07/21/2022
Building Review Failed 08/09/2022 07/11/2022
Engineering Review Failed 08/09/2022 07/07/2022
Fire Review Failed 08/09/2022 07/01/2022

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 01/25/2023
Building Permit Fee $5,608.75 $5,608.75 Paid 01/25/2023
Building Plan Review Fee $3,645.69 $3,645.69 Paid 06/23/2022
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 01/25/2023
Exhaust Vent Fan (Bath) Fee $28.20 $28.20 Paid 01/25/2023
Ventilation System (apart from Heating/AC) Fee $28.20 $28.20 Paid 01/25/2023
Mechanical Permit Fee $40.00 $40.00 Paid 01/25/2023
Mechanical Plan Review Fee $62.66 $62.66 Paid 06/23/2022
Backflow Preventor Fee $26.00 $26.00 Paid 01/25/2023
Plumbing Permit Fee $40.00 $40.00 Paid 01/25/2023
Sump, Sewage, or Ejector Pumps Fee $13.00 $13.00 Paid 01/25/2023
Plumbing Fixtures Fee $221.00 $221.00 Paid 01/25/2023
Drinking Fountain, Water Cooler, Ice Machine Fee $40.25 $40.25 Paid 01/25/2023
Water Heater Fee $13.00 $13.00 Paid 01/25/2023
Plumbing Plan Review Fee $229.61 $229.61 Paid 06/23/2022
Resubmittal Fee $130.00 $130.00 Paid 11/09/2022
Resubmittal Fee $130.00 $130.00 Paid 12/15/2022
Resubmittal Fee $130.00 $130.00 Paid 01/12/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Job Start Inspection VOID 4/28/2023 04/28/2023
Jason Little ((253) 435-3636)
Plumbing Rough In Inspection Not Ready 5/18/2023 5/18/2023 05/18/2023
Monty Johnson ((253) 770-3326)
Foundation/Rebar Inspection Partial Pass 5/24/2023 5/24/2023 05/24/2023
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
05/24/2023
slab inspection approved.

Shear Wall Inspection Partial Pass 6/7/2023 6/7/2023 06/07/2023
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
06/07/2023
shear nailing against concrete ok

Frame Inspection Partial Pass 6/23/2023 6/23/2023 06/23/2023
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
06/23/2023
exterior shear and roof nailing approved

Plumbing Rough In Inspection Failed 7/11/2023 7/11/2023 07/11/2023
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Carried Forward
07/11/2023
provide test on dwv and supply

Combination Frame And Rough In Inspection Not Ready 7/11/2023 7/11/2023 07/11/2023
Monty Johnson ((253) 770-3326)
Energy (Insulation) Inspection Passed w/ Conditions 7/12/2023 7/12/2023 07/12/2023
Monty Johnson ((253) 770-3326)
Other/Miscellaneous
Outstanding
07/12/2023
passed with area between wet wall plates filled and contained with rockwool

Comment Engineering Div Inspection VOID 11/06/2023
Jason Little ((253) 435-3636)
Engineering Daily Inspection VOID 11/06/2023
Jason Little ((253) 435-3636)
Fire Final Inspection Failed 11/7/2023 11/7/2023 11/07/2023
David Drake ((253) 864-4171)
FE Fire Extinquisher
Carried Forward
11/07/2023
1. Provide Fire Extinguisher in cabinet. 2. Provide signage on cabinet. 3. Fire Extinguisher is not in a locking cabinet with a breakable front. Will this not be secured?

Building Final Inspection Failed 11/21/2023 11/21/2023
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Carried Forward
11/21/2023
1) complete exterior grading away from structure (6 inch minimum clearance for soil and 2 inch if concrete; see building code for details) 2) Complete mechanical commissioning. 3) Verify existing RPBA has been tested. 4) Electrical final for CO 5) Verify hot water is working at sinks

Building Final Inspection Partial Pass 11/28/2023 11/28/2023
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
11/28/2023
1) complete exterior grading away from structure (6 inch minimum clearance for soil and 2 inch if concrete; see building code for details) 2) Complete mechanical commissioning. 3) Electrical final for CO

Other/Miscellaneous
Resolved
03/26/2024
Temporary Occupancy - completion by January 2, 2023 or prior to reopening after electrical shut down, whichever is first. 1) Complete exterior grading away from structure (6 inch minimum clearance for soil and 2 inch if concrete; see building code for details) 2) Electrical final for CO; see email from contractor 3) Provide architect's final completion approval.

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
: 1. INSTALL ADDRESS NUMBERS PER THE FOLLOWING DISTANCES:0-50FOOT SETBACK FROM STREET NUMBERS SHALL BE 6 INCHES IN HEIGHT; 51-100 FEET 12 INCHES IN HEIGHT. ALL NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND. ADDITIONAL NUMBERS MAY BE NEEDED AT DRIVEWAY ENTRANCE IF BUILDING NUMBERS ARE NOT VISIBLE FROM THE STREET. REAR DOORS OF SUITES OR UNITS SHALL ALSO BE LABELED WITH MINIMUM 4 INCH NUMBERS. 2. FIRE HYDRANTS REQUIRED FOR CONSTRUCTION AND FIRE DEPARTMENT ACCESS SHALL BE INSTALLED AND APPROVED BY THE FIRE CODE OFFICIAL PRIOR TO THE STORAGE OR INSTALLATION OF ANY COMBUSTIBLE FRAMING MATERIAL. ACCESS ROADWAY SURFACES SHALL BE DESIGNED TO CITY STANDARDS AND BE DESIGNED TO MAINTAIN THE IMPOSED LOADS OF A 80,000 POUND FIRE APPARATUS. ASPHALT TREATED BASE, ASPHALT OR CONCRETE PAVEMENT CAN BE USED TO PROVIDE THE REQUIRED ALL-WEATHER DRIVING SURFACE. 3. ANY REQUIRED FIRE LANE MARKINGS SHALL BE INSTALLED PRIOR TO FINAL INSPECTION AND PER CITY ORDINANCE. 4. KNOX BOXES, WHEN REQUIRED, SHALL BE INSTALLED USUALLY TO THE RIGHT OF THE MAIN FRONT DOOR AND NO HIGHER THAN 6 FEET OFF OF THE GROUND. ONLY HINGED KNOX BOXES SHALL BE USED. KNOX BOXES AND KEY SWITCHES CAN BE ORDERED ONLINE AT THE "KNOX COMPANY" 5. FIRE EXTINGUISHERS WILL BE REQUIRED PER CHAPTER 9 OF THE INTERNATIONAL FIRE CODE. GENERALLY, 1 FIRE EXTINGUISHER WITH A MINIMUM RATING OF 2A 10BC SHALL BE INSTALLED PER EVERY 3,000 SQUARE FEET OF FLOOR AREA. THE LOCATION OF THE FIRE EXTINGUISHERS SHALL BE NEAR THE EXIT DOORS AND TRAVEL DISTANCE TO AN EXTINGUISHER SHALL NOT EXCEED 75 FEET. ADDITIONAL SIGNAGE MAY BE NECESSARY TO INDICATE THE FIRE EXTINGUISHER LOCATION.
Engineering Commercial Standard Conditions Open Development & Permitting Services Standard Conditions
: Development Engineering standard commercial conditions: **Prior to STARTING the applicant shall request an erosion and sediment control inspection using the CityView permit portal at least 48 hours in advance of job start ** ** See approved Stormwater Report dated November 2022 [approved on 12/21/2022] - Stormwater control of roof downspouts required. See approved Stormwater Report dated November 2022 [approved on 12/21/2022] - A commercial development must have installed a side sewer sampling tee installed in conformance to city standard section 04.03 – side sewer. - The applicant is responsible to schedule all utility inspections prior to backfilling - Curb, gutter, sidewalk and approach must be poured per city standards. - The builder/owner shall be responsible for keeping the existing right-of-way free of debris and dirt. Any violation of PMC chapter 21.14 pertaining to clearing, filling and grading, erosion and sediment control, and storm water discharges shall be prosecuted to the fullest extent of the law.- Any addition/expansion to the footprint of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. - The applicant is responsible to call the utility notification center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law. - No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit. - A separate civil permit must be obtained by a licensed and bonded contractor prior to the installation of the proposed sanitary sewer force main. - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Miscellaneous Condition Open Engineering Division Prior to Occupancy
: Prior to occupancy both the sewer sampling tee and DCVA must be installed and recieved a final approval. LL 11/09/2022
Miscellaneous Condition Resolved Engineering Division Prior to Issuance
: A utility repair permit must be issued to install both the sewer sampling tee and the DDVA prior to the issuance of the permit. LL 11/09/2022
Miscellaneous Planning Condition Resolved Planning Division Prior to Issuance
: The right-of-way vacation approved during the November 22, 2022 City Council meeting proposed for the increase of the northern property boundary adjacent to the restroom is required in order for the restroom to meet setbacks for the PF - public facilities zone. Proposed setbacks are approvable by planning as a result of the increase of the northern property boundary line and final approval of ROW permit #PRROWV20221597.
Miscellaneous Condition Resolved Development & Permitting Services Standard Conditions
: Contractor to provide CSWPPP for approval prior to start of Construction.
Miscellaneous Condition Resolved Development & Permitting Services Prior to Issuance
: PROVIDE CONTRACTOR INFORMATION, VERIFY CITY LICENSE -EM