Planning Review | Failed | 12/01/2023 | 11/30/2023 |
Josh Kubitza
((253) 284-0214)
Send Email
|
|||
Other/Miscellaneous
Outstanding
11/15/2023
The project proposes placing structures across boundary lines. Buildings crossing property lines is not permitted without a binding site plan or similar device. Therefore, the project is required to either apply for a lot combination or a boundary line adjustment prior to building permit issuance.
The BLA application can be found at www.cityofpuyallup.org/DocumentCenter/View/1500/Boundary-Line-Revision-Application-?bidId=. The title page for the BLA must match the City of Puyallup’s BLA standard title page which can be found in both .pdf and .dwg file formats at www.cityofpuyallup.org/documentcenter/view/13811and www.cityofpuyallup.org/documentcenter/view/13813.
Lot Combination Application form can be downloaded from the City website at https://www.cityofpuyallup.org/DocumentCenter/View/11646/Lot-Combination-Application
|
|||
See Document Markup
Outstanding
11/15/2023
Site Plan C-6
Show all property boundary lines.
|
|||
Other/Miscellaneous
Outstanding
11/15/2023
Permit PLPSP20220120 SEPA Condition: The Puyallup Tribe of Indians has requested that Archaeological Monitoring be present during ground disturbance as 1115 E Main is located within a high probability area for impacting cultural resources. The city is identifying this as a mitigation measure in the preparation of a SEPA MDNS. Such a condition would require the applicant to identify this requirement in the civil and building permit applications and to ensure that Archaeological Monitoring is present during ground disturbance.
|
|||
Fire Review | Failed | 12/01/2023 | 11/17/2023 |
David Drake
((253) 864-4171)
Send Email
|
|||
Other/Miscellaneous
Outstanding
11/17/2023
Review can not be started until Civil permit items have been corrected for fire. Items 1, 2, and 3.
|
|||
Engineering Traffic Review | Approved | 12/01/2023 | 11/15/2023 |
Bryan Roberts
((253) 841-5542)
Send Email
|
|||
Building Review | Failed | 12/01/2023 | 11/07/2023 |
Brian Snowden
((253) 435-3618)
Send Email
|
|||
Other/Miscellaneous
Outstanding
10/20/2023
B01)
Please 1) provide Geo-technical report for soils recommendations and 2) reference the report by name and date in either the plan set coversheet or structural calculations.
|
|||
See Document Markup
Outstanding
10/23/2023
Please correct the code referenced in General Note #1 to the 2018 International Building Code [Taco Time Main Puyallup - Building Permit - Plan Set, sheet G-101].
|
|||
See Document Markup
Outstanding
10/23/2023
Please correct the code referenced in General Note #13 to the 2018 International Building Code [Taco Time Main Puyallup - Building Permit - Plan Set, sheet G-101].
|
|||
See Document Markup
Outstanding
10/23/2023
The detail designation was not provided, and sheet S4.11 was not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-402]
|
|||
See Document Markup
Outstanding
10/23/2023
The detail designation was not provided, and sheet S4.11 was not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-402]
|
|||
See Document Markup
Outstanding
10/24/2023
This NWCB Bulletin 401 references the 2012 IBC. Please provide the edition that conforms to the 2018 International Building Code [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-551]
|
|||
See Document Markup
Outstanding
10/24/2023
Please include the detail designation and sheet number [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-401].
|
|||
See Document Markup
Outstanding
10/24/2023
Please clarify where the legend is located to determine "D" [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-401].
|
|||
See Document Markup
Outstanding
10/25/2023
The section specified is incorrect. Exposed pipes and surfaces is section 606.6 [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-213].
|
|||
See Document Markup
Outstanding
11/03/2023
Please include the detail designation and sheet number to easily locate the Reinforcing Wall Openings [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-401].
|
|||
See Document Markup
Outstanding
11/03/2023
The detail designation was not provided [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-402]
|
|||
See Document Markup
Outstanding
11/03/2023
The detail designation was not provided [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-402]
|
|||
See Document Markup
Outstanding
11/03/2023
Please verify if this leader is meant to contain a note. Please remove it if it's not needed [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-801].
|
|||
See Document Markup
Outstanding
11/06/2023
Please provide the detail number [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-151]
|
|||
See Document Markup
Outstanding
11/06/2023
Please verify these detail call-outs. Detail 1 on A-551 shows the ceiling tile to wall condition and does not appear to include ceiling performance requirements [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-151].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheet A-631 was not included in the plan set. It appears the sheet with the Assembly Requirements is A-621 [Taco Time Main Puyallup - Building Permit - Plan Set, A-151].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheet A-202 was not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-601].
|
|||
See Document Markup
Outstanding
11/06/2023
Please check this detail call-out [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-601].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheet A-501 was not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-611].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheet G-201 was not included in the plan set (typical 3 locations this sheet) [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-621].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheets G-401 and G-411 were not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-601].
|
|||
See Document Markup
Outstanding
11/06/2023
Please verify if this is meant to be a HDU5 hold-down or HD series hold-down (Simpson HD5B) [Taco Time Main Puyallup - Building Permit - Plan Set, sheet S-121].
|
|||
See Document Markup
Outstanding
11/06/2023
This note refers to the 2015 Washington State Energy Code. Please revise it so it conforms to the 2018 WSEC [Taco Time Main Puyallup - Building Permit - Plan Set, sheet E3.1].
|
|||
See Document Markup
Outstanding
11/06/2023
The UBC is not adopted by the City of Puyallup. Please revise this note so it conforms to the 2018 International Codes [Taco Time Main Puyallup - Building Permit - Plan Set, sheet E3.1].
|
|||
See Document Markup
Outstanding
11/06/2023
Sheet E0.2 was not included in the plan set [Taco Time Main Puyallup - Building Permit - Plan Set, sheet E4.1].
|
|||
See Document Markup
Outstanding
11/06/2023
The Floor Drain detail is on sheet P-8 [Taco Time Main Puyallup - Building Permit - Plan Set, sheet P-2].
|
|||
See Document Markup
Outstanding
11/06/2023
Please correct the code referenced to the 2018 UPC rather than the SPC [Taco Time Main Puyallup - Building Permit - Plan Set, sheet P-2].
|
|||
See Document Markup
Outstanding
11/07/2023
This Lighting Summary differs from the Lighting Summary attached to the plan set. Please confirm which is correct and revise the documents as needed to match [Taco Time Main Puyallup - Building Permit - Lighting Compliance Summary]
|
|||
See Document Markup
Outstanding
11/07/2023
If this is the flush control, it will need to be relocated to the open side of the water closet per ICCA 117.1-2009 section 604.6 [Taco Time Main Puyallup - Building Permit - Plan Set, sheet G-301].
|
|||
See Document Markup
Outstanding
11/07/2023
Please verify whether the freezer will be permitted separately. If the freezer will be included in this permit, please provide additional plans, sections, and details for the freezer [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-121].
|
|||
See Document Markup
Outstanding
11/07/2023
The layout of the mechanical equipment differs between the Architectural drawings, Structural drawings, Mechanical drawings, and Electrical drawings. Please revise the plans so they're consistent [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-161].
|
|||
See Document Markup
Outstanding
11/07/2023
Please include the counter heights for the condiment station [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-211].
|
|||
See Document Markup
Outstanding
11/07/2023
This NWCB Bulletin 401 references the 2012 IBC and ASCE 7-10. Please provide the most current edition (2021 International Building Code - ASCE 7-16) [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-551]
|
|||
See Document Markup
Outstanding
11/07/2023
Please include the door schedule remarks on the schedule (i.e.: Panic Hardware per WABC 1010.1.10) [Taco Time Main Puyallup - Building Permit - Plan Set, sheet A-611].
|
|||
See Document Markup
Outstanding
11/07/2023
Please show or demonstrate how the remaining 4 credits will be gained. The table above accounts for 2 credits per section C406.2 [Taco Time Main Puyallup - Building Permit - Plan Set, sheet M-3].
|
|||
See Document Markup
Outstanding
11/07/2023
Please verify whether the hood will be permitted separately. If the hood will be included in this permit, please provide additional cut sections and details for the hood [Taco Time Main Puyallup - Building Permit - Plan Set, sheet M-4].
|
|||
See Document Markup
Outstanding
11/07/2023
Please replace these Electrical Drawings with the most recent Electrical Drawings (dated 9-11-2023) [Taco Time Main Puyallup - Building Permit - Plan Set]
|
|||
See Document Markup
Outstanding
11/07/2023
Please show the locations of any proposed quick-active valve. Water Hammer Arresters shall be installed as close as possible to quick-acting valves or, where listed mechanical devices are used, follow the manufacturer's specifications as to location and method of installation [Taco Time Main Puyallup - Building Permit - Plan Set, sheet P-4].
|
|||
See Document Markup
Outstanding
11/07/2023
Site plan C-6
Please dimension setbacks from property lines.
|
|||
Ray will assist. | |||
Engineering Review | Approved | 12/01/2023 | 10/09/2023 |
Linda Lian
((253) 841-5577)
Send Email
|
|||
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Backflow Preventor Fee | $78.00 | $78.00 | Paid | 09/05/2023 |
Building Plan Review Fee | $3,491.31 | $3,491.31 | Paid | 09/05/2023 |
Mechanical Plan Review Fee | $190.55 | $190.55 | Paid | 09/05/2023 |
Plumbing Plan Review Fee | $322.56 | $322.56 | Paid | 09/05/2023 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $4,082.42 | $4,082.42 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
There are no inspections for this permit application, or you are not authorized to view them.
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Building Permit Standard Conditions | Open | Building Division | Standard Conditions | ||
:
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
|||||
Fire Review Conditions | Open | Standard Conditions | |||
:
1. INSTALL ADDRESS NUMBERS PER THE FOLLOWING DISTANCES:0-50FOOT SETBACK FROM STREET NUMBERS SHALL BE 6 INCHES IN HEIGHT; 51-100 FEET 12 INCHES IN HEIGHT. ALL NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND. ADDITIONAL NUMBERS MAY BE NEEDED AT DRIVEWAY ENTRANCE IF BUILDING NUMBERS ARE NOT VISIBLE FROM THE STREET. REAR DOORS OF SUITES OR UNITS SHALL ALSO BE LABELED WITH MINIMUM 4 INCH NUMBERS.
2. FIRE HYDRANTS REQUIRED FOR CONSTRUCTION AND FIRE DEPARTMENT ACCESS SHALL BE INSTALLED AND APPROVED BY THE FIRE CODE OFFICIAL PRIOR TO THE STORAGE OR INSTALLATION OF ANY COMBUSTIBLE FRAMING MATERIAL. ACCESS ROADWAY SURFACES SHALL BE DESIGNED TO CITY STANDARDS AND BE DESIGNED TO MAINTAIN THE IMPOSED LOADS OF A 80,000 POUND FIRE APPARATUS. ASPHALT TREATED BASE, ASPHALT OR CONCRETE PAVEMENT CAN BE USED TO PROVIDE THE REQUIRED ALL-WEATHER DRIVING SURFACE.
3. ANY REQUIRED FIRE LANE MARKINGS SHALL BE INSTALLED PRIOR TO FINAL INSPECTION AND PER CITY ORDINANCE.
4. KNOX BOXES, WHEN REQUIRED, SHALL BE INSTALLED USUALLY TO THE RIGHT OF THE MAIN FRONT DOOR AND NO HIGHER THAN 6 FEET OFF OF THE GROUND. ONLY HINGED KNOX BOXES SHALL BE USED. KNOX BOXES AND KEY SWITCHES CAN BE ORDERED ONLINE AT THE "KNOX COMPANY"
5. FIRE EXTINGUISHERS WILL BE REQUIRED PER CHAPTER 9 OF THE INTERNATIONAL FIRE CODE. GENERALLY, 1 FIRE EXTINGUISHER WITH A MINIMUM RATING OF 2A 10BC SHALL BE INSTALLED PER EVERY 3,000 SQUARE FEET OF FLOOR AREA. THE LOCATION OF THE FIRE EXTINGUISHERS SHALL BE NEAR THE EXIT DOORS AND TRAVEL DISTANCE TO AN EXTINGUISHER SHALL NOT EXCEED 75 FEET. ADDITIONAL SIGNAGE MAY BE NECESSARY TO INDICATE THE FIRE EXTINGUISHER LOCATION.
|
|||||
Engineering Commercial Standard Conditions | Open | Engineering Division | Standard Conditions | ||
:
Development Engineering standard commercial conditions:
** Prior to STARTING the applicant shall request an erosion and sediment control inspection using the CityView permit portal at least 48 hours in advance of job start **
** Sediment control and erosion procedures shall be practiced eliminating and preventing off site damage. Stormwater runoff originating upgrade of exposed areas shall be controlled to reduce erosion and sediment loss during the period of exposure. See civil permit PRCCP20231136 for specifications **
** Stormwater control of roof downspouts must be controlled. See civil permit PRCCP20231136 for specifications **
** A building permit is required for the proposed trash enclosure showing that downspouts will be routed to the onsite storm system **
**A building permit is required for the proposed retaining wall **
- Occupancy will not be granted until all civil work associated with PRCCP20231136 has been completed and approval has been provided.
- All commercial development, multi-family, mixed use facility,or irrigation systems water service connections must have installed an approved backflow prevention assembly installed as directed by the Puyallup Municipal Code 14.02.220(3) and conforming to city standard section 03.04 - backflow installation. A double detector check valve assembly (DDCVA) is required by Fruitland Mutual Water Company.
- A commercial development must have installed a side sewer sampling tee installed in conformance to city standard section 04.03 – side sewer.
- The applicant is responsible to schedule all utility inspections prior to backfilling
- The applicant is responsible to call the utility notification center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law.
- Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
|
|||||
Miscellaneous Condition | Open | Engineering Division | Prior to Issuance | ||
:
Civil permit PRCCP20231136 must be issued prior to the building permit issued. Once issued I will review the two site plans for accuracy. L 09/28/2023
|
|||||
Miscellaneous Condition | Open | Engineering Division | Prior to Occupancy | ||
:
All work associated with civil permit PRCCP20231136 must be completed and a final engineering inspection approved prior to occupancy. LL 09/28/2023
|
Reference Number | Status | Type |
---|---|---|
PRCCP20231136 | Returned for Correction | Civil Construction Permit |
PLDDG20220115 | Canceled | Downtown Design Review |
PLPSP20220120 | Waiting for Conditions | Preliminary Site Plan |
Date Uploaded | File Type | Name |
---|---|---|
09/05/2023 | Letter | Incomplete Application Notice |
09/05/2023 | Receipt | Receipt for transaction:2023-001711 |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView