CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCTI20240571
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 05/20/2024 |
Unclassified Appliance or Equipment Fee | $761.40 | $761.40 | Paid | 05/20/2024 |
Building Permit Fee | $492.25 | $492.25 | Paid | 05/20/2024 |
Mechanical Permit Fee | $40.00 | $40.00 | Paid | 05/20/2024 |
Building Plan Review Fee | $319.96 | $319.96 | Paid | 04/05/2024 |
Mechanical Plan Review Fee | $520.91 | $520.91 | Paid | 04/05/2024 |
WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 05/20/2024 |
Resubmittal Fee | $180.00 | $180.00 | Paid | 05/01/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $2,604.52 | $2,604.52 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Foundation/Rebar Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Underfloor Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Slab/Insulation Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Block Wall Rebar Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Roof Sheathing Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Shear Wall Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Firewall/Firestop Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Energy (Insulation) Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Frame Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Combination Frame And Rough In Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Ceiling Grid/T-Bar Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Wallboard / Drywall Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Re-Roof Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Hydronic Piping Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Gas Test Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Mechanical Rough In Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Refrigeration Line Test Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Exhaust Hood Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Light Test For Grease Duct Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Exhaust/Vent Fans Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Racking Anchors/Signage Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Medical Gas Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Engineering Final Inspection | Pending | |||
Planning Final Inspection | Pending | |||
Mechanical Final Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Building Final Inspection | Pending | |||
Kevin Spruell ((253) 841-5590) | ||||
Building Final Inspection | Failed | 6/21/2024 | 6/21/2024 | 06/21/2024 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
06/21/2024
1 ; provide city approved plans on-site at time of inspection.
2 ; provide special inspection approval report for anchors,
3 ; provide fire final approval prior to building final inspection.
4 ; not a complete inspection.
|
||||
Building Final Inspection | Not Ready | 7/1/2024 | 7/1/2024 | 07/01/2024 |
Kevin Spruell ((253) 841-5590) | ||||
Other/Miscellaneous
Resolved
07/03/2024
1 ; provide city approved plans on-site at time of inspection.
2 ; provide special inspection approval report for anchors,
3 ; provide fire final approval prior to building final inspection.
4 ; not a complete inspection.
|
||||
Other/Miscellaneous
Resolved
07/03/2024
1. provide fire final approval prior to scheduling this inspection
|
||||
Exit Lighting Test Inspection | Not Ready | 07/02/2024 | ||
David Drake ((253) 864-4171) | ||||
Fire Or Smoke Damper Inspection | VOID | 07/02/2024 | ||
David Drake ((253) 864-4171) | ||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 07/02/2024 | ||
David Drake ((253) 864-4171) | ||||
Emergency Radio Test Review Inspection | VOID | 07/02/2024 | ||
David Drake ((253) 864-4171) | ||||
Fire Final Inspection | Partial Pass | 07/02/2024 | ||
David Drake ((253) 864-4171) | ||||
Other/Miscellaneous
Outstanding
07/02/2024
1. Provide adequate Emergency Lighting in egress paths.
2. Approval to stock shelves.
3. Recall for Fire Final once lighting is complete.
|
||||
Building Final Inspection | Failed | 7/2/2024 | 07/03/2024 | |
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Carried Forward
07/03/2024
1 ; provide city approved plans on-site at time of inspection.
2 ; provide special inspection approval report for anchors,
3 ; provide fire final approval prior to building final inspection.
4 ; not a complete inspection.
|
||||
Other/Miscellaneous
Carried Forward
07/03/2024
1. provide fire final approval prior to scheduling this inspection
|
||||
Building Final Inspection | Failed | 07/03/2024 | ||
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Resolved
07/03/2024
1 ; provide city approved plans on-site at time of inspection.
2 ; provide special inspection approval report for anchors,
3 ; provide fire final approval prior to building final inspection.
4 ; not a complete inspection.
|
||||
Other/Miscellaneous
Carried Forward
07/03/2024
1. provide fire final approval prior to scheduling this inspection
Building final approved less fire final approval. RC 7/2/2024
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
Building Permit Standard Conditions | Open | Building Division | Standard Conditions | ||
:
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
|||||
Fire Review Conditions | Open | Standard Conditions | |||
:
• All items must be complete prior to Final. All items below will hold the Racking Permit from being Finaled if not completed and tested.
• HMIS - hazard material information sheet will be required for review.
• A copy of the HMIS will be sent to central pierce fire & rescue for review.
• Load Plaques will need to be installed before final.
• Fire Extinguishers must meet current IFC requirements.
• Fire Alarm – clear line of site required for Visual Devices. If the racking blocks the view of the strobe, devices will need to be added or moved depending on layout.
• Emergency / Exit Lighting is required and will be tested at Racking Final.
• No storage on racks until finaled.
• A fire final will be required before a building final.
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake ddrake@puyallupwa.gov
|
|||||
Ready to Issue - Need Contractor Info | Resolved | Development & Permitting Services | Prior to Issuance | ||
:
Must provide Contractor doing the work to be named on permit. Contractor must be registered with Washington State Labor and Industries AND have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
|
|||||
Ready to Issue - Need Business License Endorsement | Resolved | Development & Permitting Services | Prior to Issuance | ||
:
Contractor needs to have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
|
Reference Number | Status | Type |
---|---|---|
B-09-0688 | Closed | Commercial - New Construction |
PRHM20230009 | Closed | Hydraulic Modeling |
PRCCP20230336 | Permit(s) Issued | Civil Construction Permit |
PRPF20230347 | Closed | Pre-Fabricated Building |
PRMH20230349 | Closed | Mechanical - COMMERCIAL ONLY |
PRPF20231137 | Permit(s) Issued | Pre-Fabricated Building |
PRFS20240156 | Closed | Fire Sprinklers |
PRFA20240641 | Closed | Fire Alarms |
P-21-0021 | File Closed | Pre-Application |
PLSSP20230037 | File Closed | SEPA Standalone |
Date Uploaded | File Type | Name |
---|---|---|
04/05/2024 | Letter | Incomplete Application Notice |
04/05/2024 | Receipt | Receipt for transaction:2024-000665 |
04/07/2024 | Form | APPLICATION |
04/29/2024 | Letter | Permit Review Correction Letter |
05/01/2024 | Receipt | Receipt for transaction:2024-000897 |
05/20/2024 | Other | EXIT ILLUMINATION PLAN - RESUB (Stamped) |
05/20/2024 | Permit | Permit - Detailed |
05/20/2024 | Letter | Permit Job Card |
05/20/2024 | Other | RACKING LAYOUT & DETAILS - RESUB (Stamped) |
05/20/2024 | Receipt | Receipt for transaction:2024-001045 |
05/20/2024 | Other | STRUCT CALCS - Updated to 2021 (Stamped) |
06/21/2024 | Report | Inspection Report (Building Final Inspection) |
07/01/2024 | Report | Inspection Report (Building Final Inspection) |
12/06/2024 | Letter | Permit Expiration Notice |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView