PRCTI20240689
Commercial - Tenant Improvement/Remodel
Closed
VANNOY SARA JO & CHRISTIAN
Alteration/Remodel
Tenant Improvement of existing 1258 sq.ft. space into a cafe. Existing HVAC system to remain unchanged, new plumbing and electrical will be added. - HOLIDAY CAFE (103 W PIONEER)
04/24/2024
07/02/2024
05/17/2025
11/18/2024

Locations

Property
2960000310

Reviews

Documents Returned For Corrections

Date Returned Name
07/01/2024 WSEC (Stamped)
07/01/2024 PLUMBING FIXTRUE WORKSHEET (Stamped)
Review Type Outcome Est. Completion Date Completed
Building Review Approved 07/01/2024 06/27/2024
Fire Review Approved 07/01/2024 06/18/2024
Planning Review Approved 07/01/2024 06/18/2024
Engineering Traffic Review Approved 07/01/2024 06/17/2024
Engineering Review Approved 07/01/2024 06/17/2024
Planning Review Failed 05/29/2024 06/05/2024
Building Review Failed 05/29/2024 05/30/2024
Fire Review Approved 05/29/2024 05/28/2024
Engineering Review Approved 05/29/2024 05/13/2024
Engineering Traffic Review Approved 05/29/2024 05/13/2024

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 07/02/2024
Exhaust Vent Fan (Bath) Fee $14.10 $14.10 Paid 07/02/2024
Building Permit Fee $888.75 $888.75 Paid 07/02/2024
Mechanical Permit Fee $40.00 $40.00 Paid 07/02/2024
Backflow Preventor Fee $26.00 $26.00 Paid 04/30/2024
Plumbing Permit Fee $40.00 $40.00 Paid 07/02/2024
Grease Trap or Interceptor Fee $13.00 $13.00 Paid 07/02/2024
Plumbing Fixtures Fee $104.00 $104.00 Paid 07/02/2024
Building Plan Review Fee $577.69 $577.69 Paid 04/30/2024
Mechanical Plan Review Fee $35.17 $35.17 Paid 04/30/2024
Plumbing Plan Review Fee $110.50 $110.50 Paid 04/30/2024
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 07/02/2024
Sewer System Development ChargeFee - Tenant Improvment/Addition $7,788.60 $7,788.60 Paid 07/02/2024
Water System Development ChargeFee - Tenant Improvment/Addition $3,381.05 $3,381.05 Paid 07/03/2024
Resubmittal Fee $180.00 $180.00 Paid 06/14/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Plumbing Below Slab Inspection Not Ready 7/23/2024 7/23/2024 07/23/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
07/23/2024
NO ACCESS 9:26 AM

Plumbing Below Slab Inspection Passed 7/25/2024 7/25/2024 07/25/2024
Monty Johnson ((253) 770-3326)
Plumbing Rough In Inspection Not Ready 8/19/2024 8/19/2024 08/19/2024
Kevin Spruell ((253) 841-5590)
Corrections:


Other/Miscellaneous
Carried Forward
08/19/2024
1. no one on site at time of inspection 2 pm

Plumbing Rough In Inspection Passed 8/22/2024 8/22/2024 08/22/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
08/19/2024
1. no one on site at time of inspection 2 pm

Frame Inspection Passed 8/23/2024 8/23/2024 08/23/2024
Monty Johnson ((253) 770-3326)
Wallboard / Drywall Inspection Passed 8/26/2024 8/26/2024 08/26/2024
Monty Johnson ((253) 770-3326)
Building Final Inspection Not Ready 10/25/2024 10/25/2024 10/25/2024
Shannon King ((253) 840-6684)
Comment Engineering Div Inspection Passed 10/25/2024 10/25/2024 10/25/2024
Jeff Hill ((253) 204-5633)
Engineering Final Inspection Passed 10/25/2024
Jeff Hill ((253) 204-5633)
Fire Final Inspection Passed 10/28/2024 10/28/2024 10/28/2024
David Drake ((253) 864-4171)
Plumbing Final Inspection Failed 10/28/2024 10/28/2024 10/29/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/29/2024
provide backflow certs

Mechanical Final Inspection Not Ready 10/28/2024 10/28/2024 10/29/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/29/2024
1:provide type 2 hood for oven, install instructions state that ventilation by others, not ventless.

Building Final Inspection Failed 10/28/2024 10/28/2024 10/29/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/29/2024
1:provide hood for oven 2:siezmic equipment 3:provide back flow certs 4:provide address.

Plumbing Final Inspection Passed 10/31/2024 10/31/2024 10/31/2024
Monty Johnson ((253) 770-3326)
Mechanical Final Inspection Not Ready 10/31/2024 10/31/2024 10/31/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Outstanding
10/31/2024
install hood for oven

Building Final Inspection Failed 10/31/2024 10/31/2024 10/31/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
10/31/2024
provide hood for oven

Building Final Inspection Partial Pass 11/4/2024 11/4/2024 11/04/2024
Monty Johnson ((253) 770-3326)
Corrections:


Other/Miscellaneous
Carried Forward
11/04/2024
complete code required ventilation hood for oven. (oven has been disabled) 15 day TCO approved.

Building Final Inspection Partial Pass 11/7/2024 11/7/2024 11/07/2024
Ray Cockerham ((253) 841-5585)
Building Final Inspection Passed 11/18/2024 11/19/2024 11/18/2024
Ray Cockerham ((253) 841-5585)
Mechanical Final Inspection Passed 11/18/2024
Ray Cockerham ((253) 841-5585)
Comment Building Div Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Footing/Setback Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Foundation/Rebar Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Slab/Insulation Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Roof Sheathing Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Shear Wall Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Firewall/Firestop Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Energy (Insulation) Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Combination Frame And Rough In Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Ceiling Grid/T-Bar Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Exit Lighting Test Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Hydronic Piping Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Mechanical Rough In Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Refrigeration Line Test Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Exhaust Hood Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Light Test For Grease Duct Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Exhaust/Vent Fans Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Medical Gas Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Fire Or Smoke Damper Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Hydrostatic Test 200Lbs 2Hrs VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Emergency Radio Test Review Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)
Planning Final Inspection VOID 11/18/2024
Ray Cockerham ((253) 841-5585)

Conditions

Condition Status Category
Building Permit Standard Conditions Open Standard Conditions
Building Division
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Standard Conditions
• Comply with 2021 IFC and 2021 IBC • L&I Final required prior to Fire Final • Fire extinguishers required per code to be installed at time of Fire Final • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake ddrake@puyallupwa.gov
Engineering Commercial Standard Conditions Resolved Standard Conditions
Engineering Division
Development Engineering standard commercial conditions: ** An internal grease trap is required. It must meet the requirements based upon the manufacture model specification calculations and that of the 2018 Uniform Plumbing Code or as directed by the Building Plan’s examiner ** - The builder/owner shall be responsible for keeping the existing right-of-way free of debris and dirt. Any violation of PMC chapter 21.14 pertaining to clearing, filling and grading, erosion and sediment control, and storm water discharges shall be prosecuted to the fullest extent of the law.- Any addition/expansion to the footprint of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. - No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit. - A separate right of way permit must be obtained is required by a licensed and bonded contractor to make the sanitary sewer main tap and or a water service connection. - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.

Related Permit & Planning Applications

Reference Number Status Type
PRSG20241054 Closed Sign/Awning

Documents & Images

Date Uploaded File Type Name
04/30/2024 Receipt Receipt for transaction:2024-000882
06/14/2024 Receipt Receipt for transaction:2024-001267
07/01/2024 Plans CONSTRUCTION PLAN SET - RESUB (Stamped)
07/01/2024 Form WSEC (Stamped)
07/01/2024 Form PLUMBING FIXTRUE WORKSHEET (Stamped)
07/02/2024 Letter Permit - Detailed
07/02/2024 Receipt Receipt for transaction:2024-001371
07/03/2024 Receipt Receipt for transaction:2024-001389
08/19/2024 Report Inspection Report (Plumbing Rough In Inspection)
10/31/2024 Report Inspection Report (Plumbing Final Inspection)
11/18/2024 Other Certificate of Occupancy