Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Automatic Fire-Extinguishing System (New) Permit Fee | $3,188.95 | $3,188.95 | Paid | 05/13/2024 |
Automatic Fire-Extinguishing System (New) Plan Review Fee | $2,072.82 | $2,072.82 | Paid | 03/13/2024 |
Resubmittal Fee | $180.00 | $180.00 | Paid | 06/12/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $5,441.77 | $5,441.77 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Fire Sprinkler Cover Inspection | Failed | 7/22/2024 | 7/22/2024 | 07/22/2024 |
David Drake ((253) 864-4171) | ||||
Corrections:
Fire Sprinkler
Carried Forward
07/22/2024
1. No one onsite. 7:30am
2. Provide City approved plans for inspection.
3. Roof concealed spaces were covered without inspection. Building inspectors warned GC not to move forward without approval over a month ago. Remove all walls for full access, we will not crawl through areas to inspect.
4. The fire sprinkler system standpipe FDC connections have no caps and are wide open to vandalism. Requirement, flush standpipe for possibly debris in system from being left open at all floors.
|
||||
Hydrostatic Test 200Lbs 2Hrs | Failed | 7/23/2024 | 7/22/2024 | 07/22/2024 |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Dry System Trip Test | Failed | 7/22/2024 | 07/22/2024 | |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Cover Inspection | Partial Pass | 7/24/2024 | 7/23/2024 | 07/23/2024 |
David Drake ((253) 864-4171) | ||||
Corrections:
Fire Sprinkler
Carried Forward
07/23/2024
1. No one onsite. 7:30am
2. Provide City approved plans for inspection.
3. Roof concealed spaces were covered without inspection. Building inspectors warned GC not to move forward without approval over a month ago. Remove all walls for full access, we will not crawl through areas to inspect.
|
||||
Hydrostatic Test 200Lbs 2Hrs | Partial Pass | 7/23/2024 | 7/23/2024 | 07/23/2024 |
David Drake ((253) 864-4171) | ||||
Erosion And Sediment Inspection | Stop Work | 11/22/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Erosion And Sediment Inspection | Passed | 12/03/2024 | ||
Jeff Hill ((253) 204-5633) | ||||
Hydrostatic Test 200Lbs 2Hrs | Passed | 12/16/2024 | 12/16/2024 | 12/16/2024 |
David Drake ((253) 864-4171) | ||||
Fire Sprinkler Cover Inspection | Partial Pass | 12/16/2024 | 12/16/2024 | 12/16/2024 |
David Drake ((253) 864-4171) | ||||
Corrections:
Fire Sprinkler
Carried Forward
12/16/2024
1. No one onsite. 7:30am
2. Provide City approved plans for inspection.
3. Roof concealed spaces were covered without inspection. Building inspectors warned GC not to move forward without approval over a month ago. Remove all walls for full access, we will not crawl through areas to inspect.
|
||||
Fire Sprinkler Cover Inspection | Failed | 6/20/2025 (10:00 to 11:00) | 6/20/2025 | 06/20/2025 |
Ray Cockerham ((253) 841-5585) | ||||
Corrections:
Fire Sprinkler
Carried Forward
06/20/2025
1. No one onsite. 7:30am
2. Provide City approved plans for inspection.
3. Roof concealed spaces were covered without inspection. Building inspectors warned GC not to move forward without approval over a month ago. Remove all walls for full access, we will not crawl through areas to inspect.
|
||||
Other/Miscellaneous
Carried Forward
06/20/2025
Canceled inspection, not ready.
See outstanding and previous corrections.
Two questions asked 1) is fire sprinkler head required an electric track elevator 2) on first floor with no commodities. Can some ceiling tiles be left out: ceiling cover must first be approved. first floor only no commodities all tiles must be installed at sprinkler heads: removal and replacement of tiles; all tiles must be installed for installation of any commodities
|
||||
Hydrostatic Test 200Lbs 2Hrs | Failed | 6/20/2025 (10:00 to 11:00) | 6/20/2025 | 06/20/2025 |
Ray Cockerham ((253) 841-5585) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
06/20/2025
System repair in progress, contractor canceled inspection today
|
||||
Fire Sprinkler Final Inspection | Not Ready | 7/8/2025 | 7/8/2025 | 07/08/2025 |
David Drake ((253) 864-4171) | ||||
Hydrostatic Test 200Lbs 2Hrs | Partial Pass | 7/7/2025 | 7/8/2025 | 07/08/2025 |
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Carried Forward
07/08/2025
System repair in progress, contractor canceled inspection today
|
||||
Other/Miscellaneous
Carried Forward
07/08/2025
Fire pump run test complete. Did not do flows or tampers.
|
||||
Fire Sprinkler Cover Inspection | Passed | 07/22/2025 | ||
David Drake ((253) 864-4171) | ||||
Corrections:
Fire Sprinkler
Resolved
07/23/2025
1. No one onsite. 7:30am
2. Provide City approved plans for inspection.
3. Roof concealed spaces were covered without inspection. Building inspectors warned GC not to move forward without approval over a month ago. Remove all walls for full access, we will not crawl through areas to inspect.
|
||||
Other/Miscellaneous
Resolved
07/23/2025
Canceled inspection, not ready.
See outstanding and previous corrections.
Two questions asked 1) is fire sprinkler head required an electric track elevator 2) on first floor with no commodities. Can some ceiling tiles be left out: ceiling cover must first be approved. first floor only no commodities all tiles must be installed at sprinkler heads: removal and replacement of tiles; all tiles must be installed for installation of any commodities
|
||||
Hydrostatic Test 200Lbs 2Hrs | VOID | 07/22/2025 | ||
David Drake ((253) 864-4171) | ||||
Corrections:
Other/Miscellaneous
Outstanding
07/08/2025
System repair in progress, contractor canceled inspection today
|
||||
Other/Miscellaneous
Outstanding
07/08/2025
Fire pump run test complete. Did not do flows or tampers.
|
||||
Fire Final Inspection | Passed | 07/22/2025 | ||
Joyce Kennedy ((253) 841-5405) | ||||
Fire Sprinkler Dry System Trip Test | VOID | 07/23/2025 | ||
David Drake ((253) 864-4171) |
Condition | Status | Category |
---|---|---|
Fire Sprinkler System (New) Conditions | Open | Standard Conditions |
• Provide plans and permit on site for inspection.
• Cover and final inspections are required.
• Fire watch is required when sprinkler system is out of service in existing buildings.
• Contractor required at all inspections.
• Hydro test will be required on all new and existing buildings. Appointment required.
• Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment.
• Fire pumps will be required to be tested and witnessed by inspector.
• Tool kit required at time of final.
• NFPA placards required.
• In existing buildings all upright fire sprinklers to remain, do not remove.
• In existing buildings all required service and maintenance to be updated prior to inspection.
• Due to unforeseeable construction design, all head locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first.
David Drake ddrake@puyallupwa.gov
|
Reference Number | Status | Type |
---|---|---|
E-20-0070 | Issued | Civil Construction Permit |
B-20-0180 | Permit(s) Issued | Commercial - New Construction |
E-20-0283 | Closed | Alternative Methods / Materials Request |
PRDE20220405 | Closed | Demolition |
PRCWSA20240533 | Closed | Certificate of Water/Sewer Availability |
PRFA20240566 | Closed | Fire Alarms |
PRCCP20240922 | Permit(s) Issued | Civil Construction Permit |
PRSG20241236 | Permit(s) Issued | Sign/Awning |
PRCWSA20241550 | Closed | Certificate of Water/Sewer Availability |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView