CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFS20250019


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS20250019
Fire Sprinklers
Permit(s) Issued
WAL-MART RE BUSINESS TR 2403
Alteration/Remodel
(1675) SPRINKLERS ~ WALMART
01/07/2025
02/10/2025
10/18/2025

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 02/10/2025 02/10/2025

Fees

Paid Fees Amount Paid Owing Date Paid
Automatic Fire Sprinkler System Alteration Fee $1,583.75 $1,583.75 Paid 01/07/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Hydrostatic Test 200Lbs 2Hrs Pending
David Drake ((253) 864-4171)
Fire Sprinkler Dry System Trip Test Pending
David Drake ((253) 864-4171)
Fire Sprinkler Final Inspection Pending
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Pending
David Drake ((253) 864-4171)
Fire Sprinkler Cover Inspection Partial Pass 2/28/2025 3/3/2025 03/03/2025
Ray Cockerham ((253) 841-5585)
Fire Sprinkler Cover Inspection Partial Pass 4/21/2025 4/21/2025 04/21/2025
David Drake ((253) 864-4171)

Conditions

Condition Status Category
Fire Sprinkler System (New) Conditions Open Standard Conditions
• Provide plans and permit on site for inspection. • Cover and final inspections are required. • Fire watch is required when sprinkler system is out of service in existing buildings. • Contractor required at all inspections. • Hydro test will be required on all new and existing buildings. Appointment required. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment. • Fire pumps will be required to be tested and witnessed by inspector. • Tool kit required at time of final. • NFPA placards required. • In existing buildings all upright fire sprinklers to remain, do not remove. • In existing buildings all required service and maintenance to be completed prior to inspection. • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first. David Drake ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20241053 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20241065 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRFA20241975 Permit(s) Issued Fire Alarms
PRFW20250341 Closed Fire Watch
PRFA20250391 Permit(s) Issued Fire Alarms

Documents & Images

Date Uploaded File Type Name
01/07/2025 Receipt Receipt for transaction:2025-000040
01/08/2025 Letter Incomplete Application Notice
02/10/2025 Form APPLICATION (Flattened)
02/10/2025 Plans FIRE SPRINKLER PLANS (Stamped)
02/10/2025 Plans FIRE SPRINKLER CALCULATIONS. (Stamped)
02/10/2025 Plans FIRE SPRINKLER CUT SHEETS (Stamped)
02/10/2025 Permit Permit - Detailed
02/11/2025 Letter Permit Job Card
03/03/2025 Report Inspection Report (Fire Sprinkler Cover Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.