CITY OF PUYALLUP PERMITTING PORTAL

Engineering Permit Application Status

PRAMR20251080


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRAMR20251080
Alternative Methods / Materials Request
Closed
MULTICARE HEALTH SYSTEM
Not Applicable
Alternative Means and Methods request for an above-ground, grease interceptor to serve the expanded MultiCare GSH Kitchen space. - MULTICARE GOOD SAMARITAN HOSPITAL KITCHEN
08/11/2025
08/29/2025
02/25/2026
08/29/2025

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Engineering Civil Review Approved 09/05/2025 08/28/2025
Engineering Review Approved 09/05/2025 08/28/2025

Fees

Paid Fees Amount Paid Owing Date Paid
Alternative Method/Construct Fee $250.00 $250.00 Paid 08/14/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

There are no inspections for this engineering permit application, or you are not authorized to view them.

Conditions

Condition Status Category
Miscellaneous Condition Open Standard Conditions
Development & Permitting Services
The AMR is approved with Conditions as follows: -Only Schier GB-500-B units shall be used. The Schier GB-500 is NOT approved for use. -The installer shall maximize the length of pipe entering the unit to the maximum extent possible in an effort minimize turbulent flow into the unit. -Due to the unique circumstances of the proposed installation, the City will increase inspections of the outlet sewer line and/or downstream sewer main for a one year period. After the one year timeframe, routine inspections will be performed to confirm that the Grease Interceptors are functioning properly. If there is found to be regular and chronic accumulation of Fats/Oils/Grease (FOG) in the line in exceedance of City Standards which is 100 mg/l, the applicant will be required to install Grease Traps at the sinks in the kitchen to be coordinated with the City. If the addition of the Grease Traps does not result in adequate improvement of the FOG removal performance of the pretreatment system, the applicant will then be required to design and install an exterior installation that complies with current City regulations.

Related Permit & Planning Applications

Reference Number Status Type
PRCTI20250548 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20250558 Permit(s) Issued Commercial - Tenant Improvement/Remodel
PRCTI20251049 Returned for Correction Commercial - Tenant Improvement/Remodel
PRFS20251125 Permit(s) Issued Fire Sprinklers
PRFA20251154 Permit(s) Issued Fire Alarms
PLPRE20250019 File Closed Pre-Application

Documents & Images

Date Uploaded File Type Name
08/14/2025 Receipt Receipt for transaction:2025-001601
08/29/2025 Form AMR Approval or Denial Letter
08/29/2025 Form AMMR - Kitchen Expansion Grease Interceptor1 (Final)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.