CITY OF PUYALLUP PERMITTING PORTAL
Permit Application Status
PRCNC20220578
| Paid Fees | Amount | Paid | Owing | Date Paid |
|---|---|---|---|---|
| Fire Review Fee (Commercial Building) | $265.00 | $265.00 | Paid | 08/08/2025 |
| Planning Landscape Review Fee | $90.00 | $90.00 | Paid | 08/08/2025 |
| Building Permit Fee | $1,415.75 | $1,415.75 | Paid | 08/08/2025 |
|
$1,441.75
|
||||
| Planning Building Permit Fee | $30.00 | $30.00 | Paid | 08/08/2025 |
| Backflow Preventor Fee | $26.00 | $26.00 | Paid | 03/30/2022 |
| Building Plan Review Fee | $1,191.94 | $1,191.94 | Paid | 03/30/2022 |
| Mechanical Plan Review Fee | $166.40 | $166.40 | Paid | 03/30/2022 |
| Plumbing Plan Review Fee | $322.56 | $322.56 | Paid | 03/30/2022 |
| WA State Building Code Council Fee (Commercial) | $25.00 | $25.00 | Paid | 08/08/2025 |
| Resubmittal/Revision Fee | $130.00 | $130.00 | Paid | 08/03/2022 |
| Resubmittal/Revision Fee | $130.00 | $130.00 | Paid | 02/27/2023 |
| Resubmittal/Revision Fee | $180.00 | $180.00 | Paid | 11/13/2024 |
| Resubmittal/Revision Fee | $180.00 | $180.00 | Paid | 04/22/2025 |
| Outstanding Fees | Amount | Paid | Owing | Date Paid |
| Sewer System Development Charge | $0.00 | $0.00 | Not payable | Not Paid |
| Water System Development Charge | $0.00 | $0.00 | Not payable | Not Paid |
| Totals: | $4,152.65 | $4,152.65 | $0.00 | |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
| Inspection | Outcome | Requested | Scheduled | Date Inspected |
|---|---|---|---|---|
| Erosion And Sediment Inspection | Pending | |||
| Comment Building Div Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Comment Engineering Div Inspection | Pending | |||
| Underfloor Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Slab/Insulation Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Block Wall Rebar Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Shear Wall Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Firewall/Firestop Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Energy (Insulation) Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Frame Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Ceiling Grid/T-Bar Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Wallboard / Drywall Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Refrigeration Line Test Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Exhaust/Vent Fans Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Fire Or Smoke Damper Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Hydrostatic Test 200Lbs 2Hrs | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Emergency Radio Test Review Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Engineering Final Inspection | Pending | |||
| Floodproof Certification Inspection | Pending | |||
| Elevation Verification Inspection | Pending | |||
| Planning Final Inspection | Pending | |||
| Fire Final Inspection | Pending | |||
| David Drake ((253) 864-4171) | ||||
| Building Final Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Foundation/Rebar Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
|
Corrections:
Other/Miscellaneous
Outstanding
09/23/2025
1. Have rebar complete at time of inspection.
2. Have water removed from footing or show water removal in progress.
|
||||
| Footing/Setback Inspection | Pending | |||
| Shannon King ((253) 840-6684) | ||||
| Foundation/Rebar Inspection | Failed | 9/23/2025 | 9/23/2025 | 09/23/2025 |
| James LaVergne ((253) 841-5590) | ||||
|
Corrections:
Other/Miscellaneous
Carried Forward
09/23/2025
1. Have rebar complete at time of inspection.
2. Have water removed from footing or show water removal in progress.
|
||||
| Footing/Setback Inspection | Partial Pass | 9/24/2025 | 9/24/2025 | 09/24/2025 |
| Shannon King ((253) 840-6684) | ||||
| Condition | Status | Category |
|---|---|---|
| Building Permit Standard Conditions | Open | Standard Conditions |
|
* Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
|
||
| Fire Review Conditions | Open | Standard Conditions |
|
• Field verify fire lane dimensions, a minimum 20' clear road with is required. Bollards are not allowed in fire lane.
• Comply with 2021 IFC and 2021 IBC
• A fire truck will be used to demonstrate code compliance at Final. The City will make the appropriate arrangements for the fire truck.
Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays.
David Drake 253-864-4171 ddrake@puyallupwa.gov
|
||
| Engineering Commercial Standard Conditions | Open | Standard Conditions |
|
** The applicant shall request an inspection with a City Engineering Inspector through the CityView portal least 48 hours in advance of job start **
** OCCUPANCY WILL NOT BE GRANTED UNTIL ALL CIVIL WORK ASSOCIATED WITH PRCCP20220589 IS COMPLETED AND APPROVAL HAS BEEN PROVIDED **
** THE APPLICANT IS RESPONSIBLE TO SCHEDULE INSPECTIONS. UTILITY INSPECTIONS ARE REQUIRED PRIOR TO BACKFILLING **
** The stormmain shown on the site plan will be rerouted to the north of the concession and restroom structure. See approved Civil Plans PRCCP20220589 **
** The concession and restroom structure is shown 11' (ft) from the existing watermain. It must remain at least 10' (ft) from watermain **
** STORMWATER CONTROL OF ROOF DOWNSPOUTS MUST BE CONTROLLED. SEE CIVIL PERMIT PRCCP20220589 FOR SPECIIFCATIONS **
** SEDIMENT CONTROL AND EROSION PROCEDURES SHALL BE PRACTICE TO ELIMINATE AND PREVENT OFF SITE DAMAGE. STORMWATER RUNOFF ORIGINATING UPGRADE OF EXPOSED AREAS SHALL BE CONTROLLED TO REDUCE EROSION AND SEDIMENT LOSS DURING THE PERIOD OF EXPOSURE. SEE CIVIL PERMIT PRCCP20220589 FOR SPECIIFCATIONS **
* Any addition/expansion to the foot print of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction.
* The applicant is responsible to call the Utility Notification Center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law.
* No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit.
* Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
* All commercial development water service connections are to be protected by a reduced pressure backflow assembly (RPBA), as directed by the Puyallup Municipal Code 14.02.220(3) and conforming to City Standard Section 3.2.2 and Details 03.04.02-1, 03.04.02-2 and 03.04.03.
* All commercial developments, irrigation systems and multi family water service connections shall be protected by at reduced pressure backflow assembly (RPBA), as directed by the City, Fruitland Mutual Water Company, Tacoma City Water or Valley Water District conforming to City Standard Details 03.04.02-1, 03.04.02-2 and 03.04.03.
|
||
| Miscellaneous Condition | Open | Prior to Completion |
|
Engineering Division
At this time (9/9/2025) the approved scope of work shall only be for the scoreboard and lighting installation. Bleacher installation and track & field is contingent on PRCCP20220589 approval. Any work done prior to PRCCP20220589 approval will be at risk of the applicant and any conflicts with the approved civil plans (PRCCP20220589) shall be redone at the applicants expense. [Adam Hunt @ 09/09/2025 2:26 PM]
|
||
| Miscellaneous Condition | Open | Prior to Completion |
|
Engineering Division
Prior to occupancy all civil work associated with permit PRCCP20220589 must be completed and approval granted. LL 08/15/2022
|
||
| Ready to Issue - Need Contractor Info | Resolved | Prior to Issuance |
|
Development & Permitting Services
Must provide Contractor & Plumber doing the work to be named on permit. Contractor must be registered with Washington State Labor and Industries AND have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
|
||
| Ready to Issue - Need Business License Endorsement | Resolved | Prior to Issuance |
|
Development & Permitting Services
Contractor needs to have a valid City of Puyallup business license endorsement with Washington State Department of Revenue.
|
||
| Date Uploaded | File Type | Name |
|---|---|---|
| 03/30/2022 | Receipt | Receipt for transaction:2022-000598 |
| 08/03/2022 | Receipt | Receipt for transaction:2022-001499 |
| 02/27/2023 | Receipt | Receipt for transaction:2023-000305 |
| 11/13/2024 | Receipt | Receipt for transaction:2024-002386 |
| 04/22/2025 | Receipt | Receipt for transaction:2025-000780 |
| 06/20/2025 | Form | CCS-TF-Doc_Fixture Worksheet (Stamped) |
| 06/20/2025 | Plans | CCS TF-Rev02-Scoreboard_Strct Calc (Stamped) |
| 06/20/2025 | Plans | CCS TF-Rev02-Scoreboard_Strct Det (Stamped) |
| 06/20/2025 | Report | CCS TF-Rev03-Bleacher_Calc (Stamped) |
| 06/20/2025 | Plans | CCS TF-Rev03-Scoreboard_Product - (Stamped) |
| 06/20/2025 | Report | CCS TF-Rev04-Doc_Lightpole_Calc - STRUCTURAL CALCS - (Stamped) |
| 06/20/2025 | Plans | CONSTRUCTION PLAN SET - (Stamped) |
| 06/20/2025 | Plans | SITE PLAN - (Stamped) |
| 08/08/2025 | Receipt | Receipt for transaction:2025-001561 |
| 09/11/2025 | Permit | Permit - Detailed |
| 09/24/2025 | Report | Inspection Report (Footing/Setback Inspection) |
| 02/18/2026 | Letter | Permit Expiration Notice |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.