CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFA20230879


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFA20230879
Fire Alarms
Permit(s) Issued
ST OF WA PIERCE COLLEGE
New
INSTALL FIRE ALARM SYSTEM PIERCE COLLEGE STEM BLDG - REV (1) - 4/12/2024 - ADDITIONAL SMOKE DETECTION
06/13/2023
08/17/2023
08/13/2024

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 04/26/2024 04/17/2024
Fire Review Approved 08/25/2023 08/16/2023
Fire Review Failed 07/19/2023 07/14/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Alarm Systems (New) Fee $657.50 $657.50 Paid 06/13/2023
Building Division Fee (Hourly) $540.00 $540.00 Paid 07/24/2023
Resubmittal Fee $180.00 $180.00 Paid 04/17/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Piv And Tamper Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Cover Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Test Inspection Pending
David Drake ((253) 864-4171)
Fire Alarm Final Inspection Pending
David Drake ((253) 864-4171)

Conditions

Condition Status Department Category Expiration Date Due Date
New Fire Alarm System Conditions Open Standard Conditions
: • Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling. • Provide plans and permit on site for inspection. • Complete labor and industries inspections prior to requesting city inspection. • Exterior fire bell required outside fire sprinkler room. • Above ceiling detection is required. • Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof. • Total coverage is required, subject to field inspection. Comply with NFPA 72. • Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified. • Pre-test shall be conducted with a printout for inspector at time of inspection. • Labeling of all devices above and below ceiling required. • Fire sprinkler tamper valves and PIV will be required to be tested at inspection. Fire sprinkler contractor to be onsite. • RTU’S and smoke dampeners will be required to be tested during inspection. • In existing buildings all above ceiling detection is to remain. Do not remove. • Due to unforeseeable construction design, all device locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCCP20220770 Permit(s) Issued Civil Construction Permit
PRCNC20221036 Permit(s) Issued Commercial - New Construction
PRFS20230673 Permit(s) Issued Fire Sprinklers
PRFA20230910 Returned for Correction Fire Alarms
PRDK20240314 Submittals Incomplete Deck/Porch/Patio
PRFA20240386 Permit(s) Issued Fire Alarms
PLPRE20210007 File Closed Pre-Application

Documents & Images

Date Uploaded File Type Name
08/17/2023 Plans Pierce College STEM Bldg DWG 07-27-2023 - RESUB (Stamped)
07/24/2023 Receipt Receipt for transaction:2023-001402
08/17/2023 Permit Permit - Detailed
08/17/2023 Letter Permit Job Card
01/09/2024 Letter Permit Expiration Notice
04/17/2024 Plans CONSTRUCTION PLAN SET Pierce College STEM Bldg (Stamped)
04/17/2024 Receipt Receipt for transaction:2024-000783


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.