CITY OF PUYALLUP PERMITTING PORTAL

Development Permit Application Status

PRFS20230673


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS20230673
Fire Sprinklers
Closed
New
Design and installation of a fire sprinkler system for the new STEM building on Pierce CO College campus. system is made of 5 wet riser assemblies and 1 manual standpipe in each stair. 702 sprinkler heads in total * REV (1) 3/27/2024 - ADDED ANTIFREEEZE SYSTEM TO DRAWING
05/16/2023
07/28/2023
03/10/2025
09/11/2024

Locations

Reviews

Review Type Outcome Est. Completion Date Completed
Fire Review Approved 04/10/2024 04/10/2024
Fire Review Approved 07/27/2023 07/27/2023
Fire Review Failed 07/03/2023 07/05/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Automatic Fire-Extinguishing System (New) Permit Fee $2,096.95 $2,096.95 Paid 07/28/2023
Automatic Fire-Extinguishing System (New) Plan Review Fee $1,363.02 $1,363.02 Paid 05/16/2023
Resubmittal Fee $180.00 $180.00 Paid 07/11/2023
Resubmittal Fee $180.00 $180.00 Paid 03/27/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Hydrostatic Test 200Lbs 2Hrs Partial Pass 1/31/2024 1/31/2024 01/31/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
01/31/2024
hydro & inspection for floors 0, 1 and the east canopy

Fire Sprinkler Cover Inspection Partial Pass 1/31/2024 1/31/2024 01/31/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
01/31/2024
5 areas highlighted on approved plans for cover.

Hydrostatic Test 200Lbs 2Hrs Partial Pass 3/12/2024 3/12/2024 03/14/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
03/14/2024
hydro & inspection for floors 0, 1 and the east canopy

Fire Sprinkler
Outstanding
03/14/2024
Hydro approved on floor 2 and 3.

Fire Sprinkler Cover Inspection Partial Pass 3/12/2024 3/12/2024 03/14/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
03/14/2024
5 areas highlighted on approved plans for cover.

Other/Miscellaneous
Outstanding
03/14/2024

Hydrostatic Test 200Lbs 2Hrs Partial Pass 3/27/2024 3/27/2024 03/27/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
03/27/2024
hydro & inspection for floors 0, 1 and the east canopy

Fire Sprinkler Cover Inspection Partial Pass 3/27/2024 3/27/2024 03/27/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
03/27/2024
5 areas highlighted on approved plans for cover.

Fire Sprinkler
Outstanding
03/27/2024
Stair 2 stand pipe

Hydrostatic Test 200Lbs 2Hrs Partial Pass 4/16/2024 4/16/2024 04/16/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
04/17/2024
hydro & inspection for floors 0, 1 and the east canopy

Fire Sprinkler Cover Inspection Partial Pass 4/16/2024 4/16/2024 04/16/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Carried Forward
04/17/2024
5 areas highlighted on approved plans for cover.

Hydrostatic Test 200Lbs 2Hrs VOID 09/11/2024
David Drake ((253) 864-4171)
Fire Sprinkler Partial Cover
Outstanding
04/17/2024
hydro & inspection for floors 0, 1 and the east canopy

Conditions

Condition Status Department Category Expiration Date Due Date
Fire Sprinkler System (New) Conditions Open Standard Conditions
: • Provide plans and permit on site for inspection. • Cover and final inspections are required. • Contractor required at all inspections. • Hydro test will be required on all new and existing buildings. Appointment required. • Hydro test, two inspections will be required 2hrs apart. Call to schedule times. Am/pm is not guaranteed without appointment • Fire pumps will be required to be tested and witnessed by inspector. • Tool kit required at time of final. • NFPA placards required • Due to unforeseeable construction design, all head locations to be field verified for compliance. Schedule your inspection online through the city of puyallup online permit system after requesting appointment from inspector. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov

Related Permit & Planning Applications

Reference Number Status Type
PRCCP20220770 Permit(s) Issued Civil Construction Permit
PRCNC20221036 Closed Commercial - New Construction
PRFA20230879 Closed Fire Alarms
PRFA20230910 Canceled Fire Alarms
PRDK20240314 Permit(s) Issued Deck/Porch/Patio
PRFA20240386 Closed Fire Alarms
PLPRE20210007 File Closed Pre-Application

Documents & Images

Date Uploaded File Type Name
03/27/2024 Receipt Receipt for transaction:2024-000602
04/11/2024 Plans CONSTRUCTION PLAN SET - REV (1) (Stamped)
04/11/2024 Plans FIRE SPRINKLER CALCS - REV (1) (Stamped)
04/11/2024 Plans FIRE SPRINKLER CUT SHEETS - REV 1 (Stamped)
04/11/2024 Plans REV FORM - REV (1) (Flattened)
04/11/2024 Plans SEISMIC BRACE REPORT - REV (1) (Stamped)
05/16/2023 Receipt Receipt for transaction:2023-000873
05/17/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Calcs
05/17/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Seismic Calcs
05/17/2023 Letter Incomplete Application Notice
07/05/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Material Book 0 (Flattened)
07/05/2023 Form Fire Code Permit Application (Flattened)
07/05/2023 Letter Permit Review Correction Letter
07/11/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Plans R01
07/11/2023 Receipt Receipt for transaction:2023-001300
07/26/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Plans R01 (10)
07/27/2023 Plans 22-3698 -Pierce College STEM Bldg - FS - Plans R01 (10) (Stamped)
07/27/2023 Form 22-3698 -Pierce College STEM Bldg - Review submission leter (Flattened)
07/27/2023 Form Revisions to Existing Residential or Commercial Applications (PDF) (Flattened)
07/28/2023 Letter Permit - Detailed
07/28/2023 Receipt Receipt for transaction:2023-001433
12/05/2023 Letter Permit Expiration Notice


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.