CITY OF PUYALLUP PERMITTING PORTAL
Development Permit Application Status
PRFA20241763
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Fire Alarm Systems (New) Fee | $402.50 | $402.50 | Paid | 11/14/2024 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $402.50 | $402.50 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Piv And Tamper Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Fire Alarm Cover Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Fire Alarm Final Inspection | Pending | |||
David Drake ((253) 864-4171) | ||||
Other/Miscellaneous
Outstanding
01/03/2025
Typical all FA permits PHS
1) UL certificate update in question.
2) please review zone one reporting. Want to make sure the portable report separate and unique. Changes in fire access require unique ID. Please review with City for any questions.
3) other portables are not functioning correctly, confirm operational. Test may be required.
T CO 30 days
|
||||
Fire Alarm Final Inspection | Partial Pass | 1/3/2025 | 1/3/2025 | 01/03/2025 |
Ray Cockerham ((253) 841-5585) | ||||
Other/Miscellaneous
Outstanding
01/03/2025
Typical all FA permits PHS
1) UL certificate update in question.
2) please review zone one reporting. Want to make sure the portable report separate and unique. Changes in fire access require unique ID. Please review with City for any questions.
3) other portables are not functioning correctly, confirm operational. Test may be required.
T CO 30 days
|
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
New Fire Alarm System Conditions | Open | Fire Prevention | Standard Conditions | ||
:
• Appointment required for all inspections am/pm is not guaranteed without appointment. Larger systems taking more than 1 hour will require 48-72hr notice prior to scheduling.
• Provide plans and permit on site for inspection.
• Complete labor and industries inspections prior to requesting city inspection.
• Above ceiling detection is required.
• Device maps required at the annunciator and fire alarm panel prior to calling in final. The annunciator map will need to be weatherproof.
• Total coverage is required, subject to field inspection. Comply with NFPA 72.
• Fire alarm system shall be placarded per NFPA 72. The UL certificate shall be posted at time of final inspection. The system will need to be UL certified.
• Pre-test shall be conducted with a printout for inspector at time of inspection.
• Labeling of all devices above and below ceiling required.
• The city of Puyallup allows one FACP per building. The panel will need to be large enough to handle multiple tenants if applicable.
• Due to unforeseeable construction design, all device locations to be field verified for compliance.
Schedule your inspection online through the city of puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email morning of inspection between 7am – 8am for scheduled date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. For larger system please make an appointment prior to scheduling first.
David Drake ddrake@puyallupwa.gov
|
Reference Number | Status | Type |
---|---|---|
PRPF20241042 | Permit(s) Issued | Pre-Fabricated Building |
PRPF20241043 | Permit(s) Issued | Pre-Fabricated Building |
PRPF20241044 | Permit(s) Issued | Pre-Fabricated Building |
PRROW20241104 | Permit(s) Issued | Right-of-Way Permit |
PRCCP20241123 | Permit(s) Issued | Civil Construction Permit |
PRFA20241766 | Permit(s) Issued | Fire Alarms |
PRFA20241767 | Permit(s) Issued | Fire Alarms |
PROLP20241838 | Canceled | Oversized Load/House Move Permit |
PLCUP20230109 | File Closed | Conditional Use Permit |
PLLC20240058 | File Closed | Lot Combination |
Date Uploaded | File Type | Name |
---|---|---|
11/14/2024 | Form | APPLICATION |
11/14/2024 | Receipt | Receipt for transaction:2024-002389 |
12/11/2024 | Plans | ALARM PLANS (Stamped) |
12/11/2024 | Plans | BATTERY CALCS (Stamped) |
12/11/2024 | Plans | CUT SHEETS (Stamped) |
12/11/2024 | Permit | Permit - Detailed |
12/11/2024 | Plans | VOLTAGE DROPS (Stamped) |
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.
Powered by CityView
![CityView Logo](/Portal/Content/CityViewClockTower.png)