Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review
|
Approved
|
10/25/2024
|
10/21/2024
|
|
|
|
See Document Markup
3 parcels will need to be combined as part of the referenced lot combination application. (5870000190, 5870000200 (infiltration trench is proposed on 5870000200 therefore this will need to be included in the parcel combination), and 5870000231)
|
|
See Document Markup
Please note, building permit PRPF20241042 shall not be issued until civil permit PRCCP20241123 is issued first. The building permit site plan must match the approved civil plans. A final comparison of the building and civil plans are required prior to building permit issuance. The applicant shall be responsible for coordinating final building permit submission to avoid redundant reviews and building permit fees.
|
|
See Document Markup
Add correct parcel number and site address from lot combination tied to civil permit application PRCCP20241123.
|
Engineering Traffic Review
|
Approved
|
10/25/2024
|
10/17/2024
|
|
|
Building Review
|
Approved
|
10/25/2024
|
10/16/2024
|
|
|
|
See Document Markup
Please provide site specific engineering, and omit any details not needed to eliminate confusion.
|
|
See Document Markup
Please clarify compliance with IMC 102.7 and 105.4 with regards to the existing mechanical systems.
This item has not been fully addressed. When mechanical equipment is relocated to a new jurisdiction, it must comply with the current codes (IMC 102.7). Additionally, all materials and equipment require approval from the code official (IMC 105.4). If materials or equipment are intended for reuse, they must be reconditioned, tested, and restored to proper working condition (IMC 105.4). Please provide documentation confirming that the equipment has been reviewed and, if necessary, serviced to ensure it is in good working order. Additionally, provide evidence that the existing equipment meets the ventilation standards required for classrooms.
|
|
See Document Markup
Please provide beam splice detail at pier connection
|
|
See Document Markup
Omit Duplicate modular plan pages that are not being used and/or that are not current.
|
Fire Review
|
Approved
|
10/25/2024
|
10/15/2024
|
|
|
Planning Review
|
Approved
|
10/25/2024
|
10/14/2024
|
|
|
Engineering Review
|
Failed
|
08/01/2024
|
08/01/2024
|
|
|
|
See Document Markup
3 parcels will need to be combined as part of the referenced lot combination application. (5870000190, 5870000200 (infiltration trench is proposed on 5870000200 therefore this will need to be included in the parcel combination), and 5870000231)
|
|
See Document Markup
Please note, building permit PRPF20241042 shall not be issued until civil permit PRCCP20241123 is issued first. The building permit site plan must match the approved civil plans. A final comparison of the building and civil plans are required prior to building permit issuance. The applicant shall be responsible for coordinating final building permit submission to avoid redundant reviews and building permit fees.
|
|
See Document Markup
Add correct parcel number and site address from lot combination tied to civil permit application PRCCP20241123.
|
Planning Review
|
Approved
|
08/01/2024
|
07/31/2024
|
|
|
Engineering Traffic Review
|
Approved
|
08/01/2024
|
07/31/2024
|
|
|
Fire Review
|
Approved
|
08/01/2024
|
07/23/2024
|
|
|
Building Review
|
Failed
|
08/01/2024
|
07/17/2024
|
|
|
|
See Document Markup
Please provide site specific engineering, and omit any details not needed to eliminate confusion.
|
|
See Document Markup
Please clarify compliance with IMC 102.7 and 105.4 with regards to the existing mechanical systems.
|
|
See Document Markup
Please provide beam splice detail at pier connection
|
|
See Document Markup
Omit Duplicate modular plan pages that are not being used and/or that are not current.
|