B-21-0421
In order to request inspections, you need to be signed in.
Paid Fees | Amount | Paid | Owing | Date Paid |
---|---|---|---|---|
Boilers & Compressors/Heat Pump (1,000,001 - 1,750,000 BTU or 30-50 HP) Fee | $366.50 | $366.50 | Paid | 03/07/2022 |
Mechanical Duct Work Fee | $14.10 | $14.10 | Paid | 03/07/2022 |
Boilers & Compressors/Heat Pump (up to 100,000 BTU or up to 3 HP) Fee | $77.60 | $77.60 | Paid | 03/07/2022 |
Air Handling Unit (Up to 10,000 cfm) Fee | $14.10 | $14.10 | Paid | 03/07/2022 |
Mechanical Permit Fee | $40.00 | $40.00 | Paid | 03/07/2022 |
Mechanical Plan Review Fee | $368.81 | $368.81 | Paid | 03/07/2022 |
Gas Piping (Mechanical) Fee | $12.80 | $12.80 | Paid | 03/07/2022 |
$0.00
|
||||
Building Division Fee (Hourly) | $130.00 | $130.00 | Paid | 03/07/2022 |
Unclassified Appliance or Equipment Fee | $42.30 | $42.30 | Paid | 03/07/2022 |
Outstanding Fees | Amount | Paid | Owing | Date Paid |
No outstanding fees. | ||||
Totals: | $1,066.21 | $1,066.21 | $0.00 |
Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.
$0.00
Inspection | Outcome | Requested | Scheduled | Date Inspected |
---|---|---|---|---|
Mechanical Final Inspection | Failed | 6/28/2022 | 6/28/2022 | 06/28/2022 |
Shannon King ((253) 840-6684) | ||||
Other/Miscellaneous
Carried Forward
06/28/2022
1 ; provide balance report with o.s.a. at time of mechanical final inspection.
2 ; complete condensate drain at r.t.u. about tire shop.
3 ; paint gas pipe at r.t.u.'s on roof.
4 ; complete insulation at refrigeration line set on roof.
5 ; cap abandoned condensate drain of roof.
6 ; provide electrical final prior to mechanical final.
7 ; complete install of angle brace at unit above pharmacy.
|
||||
Mechanical Final Inspection | Failed | 7/26/2022 | 7/26/2022 | 07/26/2022 |
Monty Johnson ((253) 770-3326) | ||||
Other/Miscellaneous
Carried Forward
07/26/2022
1 ; provide balance report with o.s.a. at time of mechanical final inspection.
2 ; complete condensate drain at r.t.u. about tire shop.
3 ; paint gas pipe at r.t.u.'s on roof.
4 ; complete insulation at refrigeration line set on roof.
5 ; cap abandoned condensate drain of roof.
6 ; provide electrical final prior to mechanical final.
7 ; complete install of angle brace at unit above pharmacy.
|
||||
Other/Miscellaneous
Carried Forward
07/26/2022
1:provide balance report with osa.
2:line set insulation on roof to have uv protection.
|
||||
Plumbing Below Slab Inspection | VOID | 08/24/2022 | ||
Monty Johnson ((253) 770-3326) | ||||
Gas Test Inspection | VOID | 08/24/2022 | ||
Monty Johnson ((253) 770-3326) | ||||
Mechanical Rough In Inspection | VOID | 08/24/2022 | ||
Monty Johnson ((253) 770-3326) | ||||
Plumbing Final Inspection | VOID | 08/24/2022 | ||
Monty Johnson ((253) 770-3326) | ||||
Comment Building Div Inspection | VOID | 08/24/2022 | ||
Monty Johnson ((253) 770-3326) |
Condition | Status | Department | Category | Expiration Date | Due Date |
---|---|---|---|---|---|
General Permit Conditions | Resolved | Building Division | Standard Conditions | ||
:
* Final approval by the Building Official is required prior to use or occupancy.
* Work shall not proceed until the inspector has approved the stages of construction.
* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.
* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance.
* By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington.
* TO SCHEDULE INSPECTIONS, CHECK PERMIT STATUS OR TO MAKE PAYMENTS ON THE CITY WEB SITE VISIT https://secure.puyallupwa.gov
|
|||||
Roof Top Screening Standard Conditions | Resolved | Building Division | Standard Conditions | ||
:
PERMIT CONDITIONS:
ALL EXTERIOR MECHANICAL EQUPMENT SHALL BE SCREENED FROM VIEW OF SURROUNDING PUBLIC STREETS AND RESIDENTIAL PROPERTIES.
***SUBJECT TO FINAL INSPECTION***
Call the inspection line at 1-877-232-6456 to schedule inspections. Use the Permit ID located at the top right of the permit when prompted for Permit ID. The City attempts to honor the AM/PM requested inspection, but cannot guarantee that service. Please call Monty - East of Meridian at 253-770-3326 or Shannon - West of Meridian at 253-840-6684 before 8:30 AM on the day of inspection to verify time.
|
There are no related items for this permit application.
Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.