CITY OF PUYALLUP PERMITTING PORTAL

Permit Application Status

PRCTI20230447


In order to request inspections, you need to be signed in.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRCTI20230447
Commercial - Tenant Improvement/Remodel
Closed
IDIL PUYALLUP LLC
Alteration/Remodel
Installation of manufacturing equipment and machines, crane structure, assembly and testing workstations and storage racking within existing warehouse building. Work includes existing slab modifications for new equipment foundations, equipment anchorage, and new roof penetrations for equipment exhaust piping.
04/09/2023
05/03/2023
01/29/2025
08/01/2024

Locations

Reviews

Documents Returned For Corrections

Review Type Outcome Est. Completion Date Completed
Building Review Approved 11/02/2023 10/19/2023
Building Review Failed 10/20/2023 10/11/2023
Engineering Review Approved 10/20/2023 10/11/2023
Engineering Review Approved 05/11/2023 04/28/2023
Building Review Approved 05/11/2023 04/28/2023
Fire Review Approved 05/11/2023 04/28/2023
Planning Review VOID 05/11/2023 04/27/2023
Engineering Traffic Review VOID 05/11/2023 04/27/2023
Engineering Review Failed 05/11/2023 04/27/2023
Fire Review Failed 05/11/2023 04/27/2023
Building Review Failed 05/11/2023 04/27/2023
Planning Review VOID 05/11/2023 04/27/2023
Engineering Traffic Review VOID 05/11/2023 04/27/2023
Engineering Review Failed 05/08/2023 04/14/2023
Fire Review Failed 05/08/2023 04/13/2023
Building Review Failed 05/08/2023 04/13/2023
Planning Review Approved 05/08/2023 04/12/2023
Engineering Traffic Review Approved 05/08/2023 04/12/2023

Fees

Paid Fees Amount Paid Owing Date Paid
Fire Review Fee (Commercial Building) $265.00 $265.00 Paid 05/03/2023
Building Permit Fee $4,896.25 $4,896.25 Paid 05/03/2023
Building Plan Review Fee $3,182.56 $3,182.56 Paid 04/09/2023
WA State Building Code Council Fee (Commercial) $25.00 $25.00 Paid 05/03/2023
Resubmittal Fee $180.00 $180.00 Paid 04/21/2023
Plumbing Fixtures Fee $52.00 $52.00 Paid 10/19/2023
Plumbing Permit Fee $40.00 $40.00 Paid 10/19/2023
Plumbing Plan Review Fee $59.80 $59.80 Paid 10/06/2023
Resubmittal Fee $180.00 $180.00 Paid 10/06/2023
Plumbing Plan Review Fee $59.80 $59.80 Paid 10/19/2023
Water System Development ChargeFee - Tenant Improvment/Addition $699.22 $699.22 Paid 10/19/2023
Sewer System Development ChargeFee - Tenant Improvment/Addition $2,550.30 $2,550.30 Paid 10/19/2023
Resubmittal Fee $180.00 $180.00 Paid 10/19/2023
Resubmittal Fee $180.00 $180.00 Paid 10/19/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


Permit(s) will not be issued until outstanding fees have been paid in full. Fee details shown above only include currently payable fees, there might be addtional fees to be paid before issuance.

$0.00

Inspections

Inspection Outcome Requested Scheduled Date Inspected
Comment Building Div Inspection Failed 5/4/2023 05/04/2023
Ray Cockerham ((253) 841-5585)
Comment Building Div Inspection Not Ready 5/5/2023 5/5/2023 05/05/2023
Ray Cockerham ((253) 841-5585)
Comment Building Div Inspection Not Ready 5/8/2023 05/08/2023
Shannon King ((253) 840-6684)
Comment Building Div Inspection Partial Pass 5/12/2023 05/12/2023
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
05/12/2023
Fins press Expander Hair pin L&I approval complete; partial phase 3

Comment Building Div Inspection Partial Pass 5/23/2023 5/23/2023 05/23/2023
Shannon King ((253) 840-6684)
Comment Building Div Inspection Partial Pass 6/30/2023 6/30/2023 06/30/2023
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Outstanding
06/30/2023
Remaining items - General UL, electrical and anchors. No discrepancies noted: this is progress status. Good progress almost complete with the first phase 2 Phase 5 about50% will do a 5-A and 5-B area. Initial inspection on 02 and Nitrogen generation; not complete. Gas pipe inspection progress; almost complete.

Gas Test Inspection Partial Pass 7/18/2023 7/18/2023 07/18/2023
Shannon King ((253) 840-6684)
Electric Vehicle Charging Inspection VOID 10/30/2023
Chris Beale ((253) 841-5418)
Comment Building Div Inspection Not Ready 1/17/2024 1/17/2024 01/17/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
01/17/2024
1. cancelled per Todd

Comment Building Div Inspection Not Ready 1/23/2024 1/23/2024 01/26/2024
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Carried Forward
01/26/2024
site walk through. will work on permit status report to Todd, due by 1/31/2024

Plumbing Final Inspection Failed 2/14/2024 2/14/2024 02/14/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Carried Forward
02/14/2024
1.complete DWV thru roof and retest 2. insulate hot water lines 3. provide signage at non potable sink as discussed with contractor

Plumbing Final Inspection Partial Pass 3/6/2024 3/6/2024 03/06/2024
Shannon King ((253) 840-6684)
Other/Miscellaneous
Carried Forward
03/06/2024
1.complete DWV thru roof and retest 2. insulate hot water lines 3. provide signage at non potable sink as discussed with contractor

Plumbing Final Inspection Partial Pass 4/2/2024 4/2/2024 04/02/2024
Kevin Spruell ((253) 841-5590)
Other/Miscellaneous
Resolved
04/02/2024
1.complete DWV thru roof and retest 2. insulate hot water lines 3. provide signage at non potable sink as discussed with contractor

Planning Final Inspection VOID 07/15/2024
Nabila Comstock ((253) 770-3361)
Building Final Inspection Failed 7/23/2024 7/23/2024 07/23/2024
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
08/02/2024
Engineering final required.

Comment Building Div Inspection Passed w/ Conditions 08/02/2024
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
08/02/2024
site walk through. will work on permit status report to Todd, due by 1/31/2024

Comment Building Div Inspection Passed w/ Conditions 08/02/2024
Ray Cockerham ((253) 841-5585)
Comment Building Div Inspection Passed w/ Conditions 08/02/2024
Ray Cockerham ((253) 841-5585)
Other/Miscellaneous
Resolved
08/02/2024
1. cancelled per Todd Inspection by KS, notes updated to close permit RC

Conditions

Condition Status Department Category Expiration Date Due Date
Building Permit Standard Conditions Open Building Division Standard Conditions
: * Final approval by the Building Official is required prior to use or occupancy.* Work shall not proceed until the inspector has approved the stages of construction.* Surface storm water shall be diverted from the building site and shall not drain onto adjacent properties.* I hereby acknowledge that I have read this Permit/Application, that the information given is correct; that I am the owner or the duly authorized agent of the owner; that plans submitted herewith are in compliance with all applicable city, county and state laws and that all construction will proceed in accordance with said laws. This permit shall expire if work is not commenced with 180 days or if the work is suspended for a period of 180 days. Permits expire two years from issuance. * By leaving the contractor information section blank, I hereby certify further that contractors (general or subcontractors) will not be hired to perform any work in association with this permit. I also certify that if I do choose to hire a contractor (general or subcontractor) I will only hire those contractors that are licensed by the State of Washington. If you are a property owner, contractor or permittee and you are paying for someone to perform the work, they must have a valid contractor registration and the person(s) installing plumbing inside a structure must meet the plumbing certification requirements. If you have any questions regarding these regulations, you may contact the Washington State Department of Labor and Industries or you can find more information on-line at: http://www.lni.wa.gov/TradesLicensing/Contractors/HireCon/default.asp
Fire Review Conditions Open Fire Prevention Standard Conditions
: RedDot Phasing requirements with Permit Conditions • Once permit is issued a phasing plan can be established. • Phase 2 will be allowed to have Partial occupancy under the following conditions. o Make up air or exhausting is not required or called out by the engineers for phase 2. o Oxygen, Natural Gas or Nitrogen are not being used unless they are in approved individual cylinders meeting allowable quantities. o L&I approval has been given for all electrical in phase 2. o Emergency lighting is tested and approved. o Modular Units are not part of phase 2. o Egress path is marked on floor per floor plan. o All operational permits have been obtained by RedDot through Central Pierce Fire & Rescue that are needed for that area. • Phase 3, 4, and 5 o The following areas will not be allowed occupancy until all requirements in that phased area are met. If any of the listed items below are required and not installed, inspected, tested, and approved by L&I and City, those areas will not be approved for partial occupancy. ? Fire Sprinklers ? Suppression ? Fire Alarm ? Mechanical Ventilation and Exhaust ? Oxygen/Nitrogen tank install and piping ? Bay door will be allowed to be secured open as a temporary measure prior to install of louvered system • Any items not listed above that were previously called out by an engineer will still be required and may alter timelines or phasing. The City strongly suggests that previous reports are reviewed and understood prior to asking for occupancy or phasing. • Failing to comply with permit conditions will result in revoking the Partial/TCO approval for occupancy in the warehouse for all phases.
Engineering Commercial Standard Conditions Open Engineering Division Standard Conditions
: Development Engineering standard commercial conditions: - Any and all deferred submittals from City of Puyallup permits B-20-0235, B-21-0386, E-20-0137, PRCTI20220873, and PRCTI20221916 shall be addressed under this building permit for the manufacturing facility. A pre-treatment application is required as are civil plans stamped by a qualified Professional Engineer (PMC 14.06). - The manufacturing equipment is only permitted to connect to City water under permit PRCTI20230447. The 16 water fixture units totaled in the Plumbing Fixture Count Summary were used to calculate and assess water system development fees for PRCTI20221916. The water SDCs collected under PRCTI20221916 apply to all manufacturing equipment. Until the City approves the pre-treatment facilities, the manufacturing process water shall be pumped and hauled off site for treatment. The sanitary sewer connection for the manufacturing area requires a permit revision or new utility connection permit to assess sanitary sewer SDCs. - All commercial development, multi-family, mixed use facility, or irrigation systems water service connections must have installed an approved backflow prevention assembly installed as directed by the Puyallup Municipal Code 14.02.220(3) and conforming to city standard section 03.04 - backflow installation. - Any violation of PMC chapter 21.14 pertaining to clearing, filling and grading, erosion and sediment control, and storm water discharges shall be prosecuted to the fullest extent of the law.- Any addition/expansion to the footprint of the building including decks and porches not originally shown on the approved set of plans must obtain proper permits prior to construction. - The applicant is responsible to call the utility notification center at 1-800-424-5555 before beginning any excavation. Call before you dig, it's the law. - No work shall be done in or on the public right of way without a licensed and bonded contractor first obtaining a right of way permit. - Any code requirement that may have been overlooked in this plan review does not imply that the requirements have been waived.
Fire Review Conditions Open Fire Prevention Standard Conditions
: Manufacturing Permit Fire Conditions • Comply with 2018 IFC, 2018 IBC and current NFPA codes and standards • FPE report to be fully completed and may require a closeout letter stating all items are code compliant. • All other permits must be Finaled prior to this permit • Total coverage required in the city of puyallup • L&I Final required prior to Fire Final • Exit lighting test required, contractor to provide light meter, each phase will be tested separately. After all phases are installed a final light test will be required. • Separate permits required for Fire Alarm and Fire Sprinkler. • Fire extinguishers required per code and will be field verified for placement. • Elevator – L&I Final required prior to inspection; Fire Alarm contractor required onsite for inspection. • A Knox box is required at the front entry on the exterior of the building if equipped with a Fire Alarm System or Fire Sprinkler System. • PIV must have a Knox lock or approved lock with an extra key provided in Knox box • Existing buildings will need to contact central pierce fire & rescue and update the key in the Knox box • All above items to be completed prior to fire final. Fire final required before building final Schedule your inspection online through the City of Puyallup online permit system. This is a request for inspection only. A date and time will be selected by Inspector depending on availability. Email prior to inspection for date and time. Fire Inspections are Monday – Thursday there will be no inspections on Fridays. David Drake 253-864-4171 ddrake@puyallupwa.gov
Miscellaneous Condition Resolved Engineering Division Prior to Issuance
: According to PMC Chapter 14, water and sanitary sewer system development charges shall be paid prior to permit issuance. In order to assess the system development fees, the applicant shall first submit a revised water/wastewater plumbing plan depicting the water and wastewater plumbing for each proposed plumbing fixture including the paint booth, brazing station, testing station, and tank/filter room. The revised plans must address all of Engineering's corrections from the last plan review correction letter. Second, all plumbing fixtures should be listed on the Plumbing Fixture County Summary on sheet P0.0 of the water/wastewater plumbing plans. Finally, the revised water/wastewater plumbing plans and CoP Plumbing Fixture Worksheet must be completed and returned to assess the water and sewer system development charges. After the fees are paid, permit PRCTI20230447 can be issued. [Yianni Charitou @ 04/28/2023 2:51 PM] When the City calculated the water (and future sewer) SDCs for the Red Dot powder coat paint booth permit PRCTI20221916, we reviewed 2018 UPC Tables 610.4 and 702.2 to determine the FUW based on the water supply pipe size, length, and water meter size. With the FUW, we then calculated and assessed the SDCs per Puyallup Municipal Code. Since the powder coat booth shares the same nonpotable water service line as all the other manufacturing equipment, the City will apply the water SDCs collected for the powder coat booth to the entire manufacturing area. The same will apply to the sewer SDCs when the manufacturing area is connected to sanitary sewer. [Yianni Charitou @ 05/02/2023 3:57 PM]
Miscellaneous Condition Resolved Engineering Division Prior to Occupancy
: In order to evaluate the requirements for the proposed waste water treatment unit, pre-treatment facilities require engineered plans and specifications prepared by a Professional Engineer. This requirement was deferred to this Manufacturing Tenant Improvement permit application. Upon submission, it will be reviewed by Development Review Engineering and the Waste Water Treatment Plant (WWTP). This submittal may also be subject to third party review at the expense of the applicant. A Discharge Application is also be required by the Puyallup WWTP. [Yianni Charitou @ 04/14/2023 9:26 AM] Under the direction of Jamie Carter, the pretreatment condition has been resolved as explained in the attached email RE: Pretreatment Streamlining Rule. [Yianni Charitou @ 04/10/2024 7:39 AM]

Related Permit & Planning Applications

Reference Number Status Type
PRRWF20220381 Canceled Retaining Wall
PRCTI20220873 Closed Commercial - Tenant Improvement/Remodel
PRFS20221095 Closed Fire Sprinklers
PRSG20221172 Closed Sign/Awning
PRFA20221284 Closed Fire Alarms
PRCTI20221624 Closed Commercial - Tenant Improvement/Remodel
PRCTI20221709 Closed Commercial - Tenant Improvement/Remodel
PRCTI20221916 Closed Commercial - Tenant Improvement/Remodel
PRFA20230034 Closed Fire Alarms
PRCTI20230167 Closed Commercial - Tenant Improvement/Remodel
PRFA20230302 Closed Fire Alarms
PRCP20230511 Closed Carport
PRFS20230711 Closed Fire Sprinklers
PRCP20230996 Closed Carport
PRCTI20230997 Closed Commercial - Tenant Improvement/Remodel
PRMH20231156 Closed Mechanical - COMMERCIAL ONLY
PRFS20231516 Closed Fire Sprinklers
PRFS20240612 Closed Fire Sprinklers
PRCTI20240671 Closed Commercial - Tenant Improvement/Remodel
PRCCP20241039 Returned for Correction Civil Construction Permit

Documents & Images

Date Uploaded File Type Name
01/17/2024 Report Inspection Report (Comment Building Div Inspection)
02/14/2024 Report Inspection Report (Plumbing Final Inspection)
04/02/2024 Report Inspection Report (Plumbing Final Inspection)
04/09/2023 Receipt Receipt for transaction:2023-000593
04/09/2023 Other Red Dot Shop TI - MANUFACTURING Fire Code Report
04/09/2023 Other Red Dot Shop TI - MANUFACTURING Phase Plan
04/09/2023 Form Red Dot Shop TI - MANUFACTURING WSEC ENV Forms
04/10/2023 Form Red Dot Shop TI - MANUFACTURING Fire Sprinkler Report
04/14/2023 Form CoP Plumbing Fixture Worksheet (Flattened)
04/14/2023 Letter Permit Review Correction Letter
04/14/2023 Form Red Dot Shop TI - MANUFACTURING Permit Application (Flattened)
04/21/2023 Receipt Receipt for transaction:2023-000687
04/28/2023 Plans Red Dot Shop TI - MANUFACTURING Permit Application (Rev1) (Flattened)
05/03/2023 Permit Permit - Detailed
05/03/2023 Letter Permit Review Correction Letter
05/03/2023 Receipt Receipt for transaction:2023-000783
05/03/2023 Report Red Dot Shop TI - MANUFACTURING Bridge Crane + Structural Calcs (Stamped)
05/03/2023 Plans Red Dot Shop TI - MANUFACTURING Compressor+Generators (Stamped)
05/03/2023 Plans Red Dot Shop TI - MANUFACTURING Gas Plumbing (Stamped)
05/03/2023 Plans Red Dot Shop TI - MANUFACTURING Gate Details (Stamped)
05/03/2023 Plans Red Dot Shop TI - MANUFACTURING Permit ReSub (Rev1) no EN (Stamped)
05/03/2023 Plans Red Dot Shop TI - MANUFACTURING Plumbing Set (Final) (1) (Stamped)
05/08/2023 Report Inspection Report (Comment Building Div Inspection)
05/23/2023 Report Inspection Report (Comment Building Div Inspection)
07/18/2023 Report Inspection Report (Gas Test Inspection)
08/02/2024 Other Certificate of Occupancy
10/06/2023 Form CORRECTION RESPONSE LETTER
10/06/2023 Receipt Receipt for transaction:2023-001926
10/11/2023 Letter Permit Review Correction Letter
10/11/2023 Form Plumbing fixture worksheet_202012021825172385 (Flattened)
10/11/2023 Plans PLUMBING PLANS REV (1) (Flattened)
10/19/2023 Receipt Receipt for transaction:2023-001993
10/19/2023 Plans REDDOT - P_10.16.2023 (Stamped)
10/19/2023 Plans RedDot TI - Manufacturing Revision
10/20/2023 Report Inspection Report (Plumbing Below Slab Inspection)
10/24/2023 Report Inspection Report (Foundation/Rebar Inspection)


Should you need assistance, please contact the Permit Center at (253) 864-4165 option 1.